@jamespatrick9449
@jamespatrick9449 2 жыл бұрын
Far from a horrible Tech. I really like your videos, I always learn something new. To the point and informative. Thanks for taking the time to make them.
@josephmoxley5792
@josephmoxley5792 3 жыл бұрын
Mini Splits on Commercial Roof tops usually have this issue. They aren't meant to be on top of the roof. Lighting strikes Electrical Surges doesn't take much to get the CPU fried. Need some type of Surge protection to slow the electrical issues. Put an AMP Fuse so It pops the fuse and the board.
@hvacmania8323
@hvacmania8323 Жыл бұрын
Shade
@KuntalGhosh
@KuntalGhosh Жыл бұрын
That is not a cpu. That is called ipm. Basically the huge chip that is screwed onto the heatsink. Contains a full bridge 3 phase igbt set and control circuitry with protections and other sensors. This is the part that makes the 3 phase ac at variable frequency to control compressor speed and cooling power. I have 5 panasonic inverter mini splits and they are working fine since 2017 , not a single issue on one of them. They run 12 hours a day in Indian summer heat. Today it was 44c and it has been above 40 for this whole month touching 45 sometimes. None of these inverters have issues with the heat. You just keep them in shade and oversize the units. I have 1200sq ft floor space and installed capacity of 7tons. It uses 2 3 tons of capacity when the set temperature is reached. This puts lot less strain on the inverter. And i will never go back to those non inverters.
@tyl8ter
@tyl8ter 3 жыл бұрын
Nighthawk...keep them comin...great vidz
@Yukonjackman1
@Yukonjackman1 Жыл бұрын
Mine was a poor connection in the electric part had no heat on its setting.
@gpowerdragon9852
@gpowerdragon9852 Жыл бұрын
if the electronics break often it's usually indication of high voltage Spike like thunderstrike that has been close by before you need surge protector plug on it
@SuperSincere1
@SuperSincere1 2 жыл бұрын
But why does the boards keep blowing?????
@jhoney2346
@jhoney2346 Жыл бұрын
I’m dealing with this exact problem currently. Any more issues from this unit after this video?
@NighthawkHVAC
@NighthawkHVAC Жыл бұрын
It’s still going.
@chrislester3152
@chrislester3152 Жыл бұрын
So that might help in the future to make sure that none of these inverter mini splits are put on twin breaker because it will cause a compressor over current protection code and probably burn one up if not fixed after a while
@dom2.075
@dom2.075 3 ай бұрын
how do you know someone put dye in the unit
@NighthawkHVAC
@NighthawkHVAC 3 ай бұрын
When I put my probes on dye came out and got all over them.
@christianneal8204
@christianneal8204 2 жыл бұрын
You might want to put a Koolguard 2 on that system. It's a voltage monitoring surge protector.
@hvacmania8323
@hvacmania8323 Жыл бұрын
Outstanding 🎉 videos thanks for posting. You think maybe some shade would prevent this issue?
@zigavucic754
@zigavucic754 9 ай бұрын
I think you will be back for same problem,this is a compressor winding problem.
@TandNServices
@TandNServices 2 жыл бұрын
As soon as I saw the back of the board @ 5:11 I knew it was because of the thermal paste not being installed properly. I warn guys all the time about the importance of it.
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
100%. Agreed. Love your channel by the way!
@gowkarranpooran4771
@gowkarranpooran4771 10 ай бұрын
Thanks for sharing
@perryfree3903
@perryfree3903 3 ай бұрын
Yeah they're supposed to be screws there
@westsidehvac1097
@westsidehvac1097 10 ай бұрын
compressor is bad is gonna keep popping pct board
@UltraElite-ju8bb
@UltraElite-ju8bb 7 ай бұрын
Tech support free resource
@theduffster2581
@theduffster2581 3 жыл бұрын
What about installing a phase monitor?
@NighthawkHVAC
@NighthawkHVAC 3 жыл бұрын
My thoughts exactly. Client didn’t want to pay for it though.
@theduffster2581
@theduffster2581 3 жыл бұрын
@@NighthawkHVAC I figured as much bud 👍🏻 benn through it many times but the callbacks become costly sometimes
@NighthawkHVAC
@NighthawkHVAC 3 жыл бұрын
I told him if it happens again it’s on him.
@calvinnewcastle5899
@calvinnewcastle5899 7 ай бұрын
Nice work brother
@zabalaan
@zabalaan 6 ай бұрын
Solid red and yellow and 11 blinks on green. What does that mean? The manuals dont even mention green led on the outside unit
@haochen6247
@haochen6247 2 жыл бұрын
The suction pressure looks too high isn't? Is the system over charge which is causing the high compressor over current protection?
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
This system has a variable compressor and charge can’t be determined by pressures as they may look high or low. The only way to check the charge is to weigh the charge. This units charge was to factory specifications.
@haochen6247
@haochen6247 2 жыл бұрын
@@NighthawkHVAC I agree that inverter unit is best to weight in refrigerant. However, as alternative, you can also have all the indoor unit run at the max cooling mode, and charge it based on the gauge reading to around 125. There got to be reason for repeated blown circuit board. The mini split come with pre-charged refrigerant up to certain length and also have requirement for minimum total pipe length. For what I have seem with many Fujitsu and other brand that I have fixed, in cooling mode, when compressor is running, it never get this high suction pressure. while when the compressor is not running, it could get above 200 psi. I would suggest if all choice is out, check if the system is overcharged.
@hkhsm359
@hkhsm359 3 жыл бұрын
Nice video. Thanks for sharing
@briandonovan7099
@briandonovan7099 Жыл бұрын
Sorry to sound like a newbie but how do you use that reset lever on the back 😂
@julieanehurley-hv4bv
@julieanehurley-hv4bv 7 ай бұрын
Good question...the exact box on the mini split I have has the fuses.
@garry9586
@garry9586 2 жыл бұрын
Where is the surge protector at?
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
Lol. Good luck getting a client to pay for that!
@KuntalGhosh
@KuntalGhosh Жыл бұрын
Always keep air conditioners in under shed. Make tiny sheeds around them . Putting them under direct sunlight not only increase your electricity bill it also puts lot more strain on the inverter parts. These do not like to run hotter than 70c internally. You don't need too much paste . The thing that you need to do is to properly clean both the heatsink and the ipm chip with tissue and isopropyl to remove any oil residue and old crusty paste. Then install fresh thermal paste and spread it with the supplied spoon that comes with lots of pc thermal paste. And you can use pc thermal paste those are lot better than these thermal grease. They aren't much more expensive and you can get the 30gram tubes of noctua h1 or h2 and that would last you 60 installations.
@KevinfinityDrums
@KevinfinityDrums 11 ай бұрын
What? You should never restrict or stifle air flow around a unit.
@mikemoore466
@mikemoore466 2 жыл бұрын
They make surge protectors for these units. I would definitely install one on this unit.
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
I agree. The client doesn’t what to pay for it though.
@mikemoore466
@mikemoore466 2 жыл бұрын
@@NighthawkHVAC well they can keep installing boards then. 👍
@frankcastillo9199
@frankcastillo9199 6 ай бұрын
Great tips 👌
@djsm0609ify
@djsm0609ify 3 жыл бұрын
Great video, babe!
@perryfree3903
@perryfree3903 3 ай бұрын
Those power pc boards can be a bear to change.You gotta take everything apart. And make sure you don't miss any wires because you're going to be tearing it back off and putting the thermal paste back on it a second time.Ask me how I know this😂
@roundedges2
@roundedges2 Жыл бұрын
Ok but what causes 2 boards to burn?
@NighthawkHVAC
@NighthawkHVAC Жыл бұрын
First one was a surge. 2nd one the previous tech did not use thermal paste and did not secure the board to the heat sink properly.
@winkhvac62
@winkhvac62 2 жыл бұрын
Good video
@chrislester3152
@chrislester3152 Жыл бұрын
I have cured protect compressor codes by changing them off Tandom breakers , they don’t like being on them ,
@Ricky32908
@Ricky32908 Жыл бұрын
That board should have insulation on whatever is on top of it. If it doesn’t and it’s bare metal it will short every time
@Patriot20233
@Patriot20233 5 ай бұрын
Thanks
@pcar5
@pcar5 2 жыл бұрын
You will be beck. Something is causing the failures. Always told my techs...troubleshoot the cause not the symptom.
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
Been over a year and still works. I think the previous tech didn’t tighten the screws tight enough to make good contact to the heat sink causing it to overheat.
@jhonnybenito7464
@jhonnybenito7464 Жыл бұрын
Maybe someone seated on top of it and create the short
@ezhilbenit630
@ezhilbenit630 2 жыл бұрын
comprser heter
@trinito97
@trinito97 Жыл бұрын
Put a new one
@PabloRodriguez-ck7ph
@PabloRodriguez-ck7ph 2 жыл бұрын
Pues qué fácil es repararlo cambiando toda la tarjeta, sería mucho mejor tratar de reparar la tarjeta Eso sería algo mejor.
@sparkyobrian6417
@sparkyobrian6417 Жыл бұрын
i have 4 large Mitsubishi units (5 years old) and they have been nothing but trouble , labor is very high , and the companies in my area have a hard time fixing them. ill never buy Mitsubishi high dollar junk again
Who is More Stupid? #tiktok #sigmagirl #funny
0:27
CRAZY GREAPA
Рет қаралды 10 МЛН
How to have fun with a child 🤣 Food wrap frame! #shorts
0:21
BadaBOOM!
Рет қаралды 17 МЛН
How to Work on Mini Splits?
30:30
Taddy Digest
Рет қаралды 126 М.
Technically Speaking EP1: Mitsubishi Electrical Troubleshooting
6:08
Tech Tips: How to Diagnose a Shorted Power Board (L)
4:07
Mitsubishi Electric Trane US
Рет қаралды 46 М.
Mini Split Not Heating Leaking Refrigerant
11:02
Taddy Digest
Рет қаралды 84 М.
I HATE Mitsubishi MiniSplits
15:41
HVACR Survival
Рет қаралды 139 М.
MINI SPLIT Parts Explained! Understand What They Do!
19:31
AC Service Tech LLC
Рет қаралды 672 М.
Mitsubishi Ductless Split Shut Off on OverCurrent Faults
24:25
The HVAC Hacker
Рет қаралды 44 М.
Mitsubishi Mini Split Repair
20:24
T&N Services LLC.
Рет қаралды 110 М.
Multi-zone split type Air Conditioner installation
16:49
craftsman tv
Рет қаралды 493 М.