no heat on first floor bad taco 007 circulator replaced,purged air

  Рет қаралды 126,996

steven lavimoniere

steven lavimoniere

9 жыл бұрын

replaced bad taco 007 circulator ,purged air from zones.

Пікірлер: 86
@drummerdem50
@drummerdem50 9 жыл бұрын
Thanks for sharing Steve.
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
drummerdem50 thanks for watching
@leroybertzyk9270
@leroybertzyk9270 7 жыл бұрын
Hi Steve, I am a retired HVAC-R oil & gas burner service mechanic, pneumatic controls, centrifugal chillers service mechanic after 47 years. I have been retired for 8 years. I enjoy your videos very much. Brings back the good old days. In watching the videos I was curious why you don't use the rotation tester and A C indicator, that you use on solenoid valves to see if there are energized, to check if the grundfos or taco circulators are running. Just hold it to the center back of the motor and it will rotate in the same direction as the motor. Keep up the good videos.
@lalaniathielen8917
@lalaniathielen8917 2 жыл бұрын
Hey Leroy I have a few old school plumbing and heating questions if you would like to chat..house built 1956 Thanks in advance! ~CT
@lalaniathielen8917
@lalaniathielen8917 2 жыл бұрын
Appreciate the suggestions... Simply put!
@lotusvines5168
@lotusvines5168 Жыл бұрын
Thx! I’m buying one now.
@danielsteele7544
@danielsteele7544 2 жыл бұрын
Thankyou, what a pro,u didn't waste one movement.
@jonathansmith3019
@jonathansmith3019 9 жыл бұрын
Steve, Thanks for posting another great video. it looks like you got a new transfer pump.
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
Jonathan Smith a small one i like to use on waterheaters .
@arniegrote319
@arniegrote319 9 жыл бұрын
Good Job Steve, Makes the job tough when things are intermittent.
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
Arnie Grote yes i agree but this time i was there it was not working.so i could pin point the problem easy
@harrydickson4575
@harrydickson4575 9 жыл бұрын
Another great job and video Steve keep them coming !!!!!
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
Harry Dickson i will try
@letseeitplease
@letseeitplease 9 жыл бұрын
now that was some serious work going down right there,,, great job steven, great job,
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
letseeitplease thanks for the comment @ for watching
@Brad1237202
@Brad1237202 9 жыл бұрын
You were right Steven about that system "Having Several Issues!" It was a nice 55 degrees today. You can see the snow melting before your eyes!
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
Brad1237202 its melting slow but sure
@jkeee123e
@jkeee123e 7 жыл бұрын
Be careful guys. I just tried this easy method of installing this pump and it failed miserably. It leaked like hell. He does warn us about this possibility. As it turns out the newer pump housings are machined for an Oring, but the old housing is machined for a quad ring, and the supplied new Oring does not fit the old quad ring grove properly. Close but no cigar. Tried several times to use new Oring, and the old quad ring but all attempts leaked. Bit the bullet and reassembled the new pump back to the new pump housing, and took out the complete old unit, put in the complete new unit and everything was just perfect.. No leaks and fired up perfect. This is a fast easy method if both the old and new pumps are close in age where it is likely there are no design changes.
@lalaniathielen8917
@lalaniathielen8917 2 жыл бұрын
Thanks for your helpful advice... Much appreciated
@ilirkarafili1598
@ilirkarafili1598 4 жыл бұрын
Thanx for video.
@DJTPA007
@DJTPA007 7 жыл бұрын
Nice work Steve.
@jpraimundo4100
@jpraimundo4100 9 жыл бұрын
Great video steven lavimoniere I was at a job yesterday to change a pump and tried that trick. The homeowner was watching and he made me change the whole assembly lol. "Better to change everything " he said, " this way it's all new and I won't have any problems"
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
JP Raimundo well the housing and gaskets on the older pump were fine .if they were iffy i would have changed out the whole pump.
@jpraimundo4100
@jpraimundo4100 9 жыл бұрын
Same thing here. The pump burned during a power spike ( electrician that wired the thing didn´t put the right breaker) after a power outage. The housing and gaskets were perfect. The customer just didn´t want the old one.
@EminHVAC
@EminHVAC 9 жыл бұрын
Good job Steve. I do the same , I just replace the motor. unless I have to replace the entire assembly.
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
Emin HVAC a small trick to show the young guys
@BigmoRivera
@BigmoRivera 2 жыл бұрын
Nicely Done 👍🏽
@nickfeucht6527
@nickfeucht6527 7 жыл бұрын
Thanks for the video Steve! My supply house told me a quiet pump was still working, but it turns out it was performing on its last legs. Signs I should have paid more attention to that easily showed my simple one zone system had a bad circulator pump: radiators one branch were really warm, while others on other branch were very cold, I had about a 50/50 split, interesting not upper units vs lower, just one branch vs the other branch-within that one branch the 2nd floor radiators were much hotter, that I could not shut valves at the unit and control the heat (heat was coming through return also, and more recently my boiler was rapidly cycling on before shutting off at the upper temperature limit and the pressure kept climbing way up and the release valve was whistling like a barber shop quartet during firing, then both temp and pressure would fall rapidly. Thanks for the help, was a really easy fix, no need to change housing out either good pointer there. I was quoted $815 to do the work, but given I had the tools and knowledge of how to hook up and restart a system it was a matter of the pumps cost and my time. Keep posting!
@lalaniathielen8917
@lalaniathielen8917 2 жыл бұрын
Similar issues I appreciate your comment
@lalaniathielen8917
@lalaniathielen8917 2 жыл бұрын
With the tools and know-how.... Exactly!
@Juegosdecartas101
@Juegosdecartas101 9 жыл бұрын
Nice job Steve
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
Jorge Mejia thanks for commenting
@bearmaintenance5749
@bearmaintenance5749 9 жыл бұрын
Good video enjoyed it.
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
bear maintenance thanks for the support
@CHIBA280CRV
@CHIBA280CRV 5 жыл бұрын
Hold on there paying for a pump replacement, which means installing new Flanders gaskets as well. So now if it leaks from the flange gasket , it's another that could have taken care of at this job. That's kind of messed up brother, just cause You want to save time ...this is a job I have to say , you should have done the right thing and swapped out the whole unit that was paid for ..I wouldn't let you get away with that...! I enjoy your videos but when your wrong your wrong..
@timbradley8890
@timbradley8890 7 ай бұрын
Plus, the right way is probably faster than this. Why go through all that trouble when you can just swap out the whole thing? No way this is faster than changing the flanges. Plus, you probably void any warranty by swapping new into old. It's going to fail again soon. Why eat the cost?
@erronblack1321
@erronblack1321 7 жыл бұрын
nice work
@chadrayl9648
@chadrayl9648 Жыл бұрын
How do u purge wo a purge station?
@1planters
@1planters 7 жыл бұрын
I HAD four Bell & Gossett(?) circulators. I was away hunting when the wife called to say the heat wasn't working. I said call "the" plumber and she called "A" plumber. Well when I got back and reviewed the bill the jerk had replaced all four circulators to Tacos and charged me $380 EACH!! He also replaced the 4 zone control thingy with a Taco as well and charged me $400 for that. He billed me for two guys for 8 hours ($150.00 X 8). I also got 2 check valves changed out which were the only ones he could get to easily. I went on line with Cheapo Depot and his cost for the circulators was $100.00 each as was the zone control. They left all the trash behind but took the old copper heavy circulators with them. The bill was just over $3500.00. I suggested he had a better chance of seeing God if he thought I was going to pay him a nickel. I figured he deserved nothing for trying to screw me over as badly as he did. Is a 400% markup on a $100.00 item considered gouging. My usual guy said he thought I got screwed without getting kissed first. What do you think?
@jagpalsukhraj
@jagpalsukhraj 4 жыл бұрын
You were charged basically double what you should have been if not more than
@lroct6654
@lroct6654 8 жыл бұрын
well done ! steve
@stevenlavimoniere
@stevenlavimoniere 8 жыл бұрын
+Leonardo RamireZ007 thanks for watching& commenting
@TruckguyTruckguy
@TruckguyTruckguy 9 жыл бұрын
Now with the warmer weather the no heats are coming in like crazy!
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
Truckguy900 Truckguy900 work is a good thing
@6aNapoleon
@6aNapoleon 6 жыл бұрын
I have three heating zones, and one pump needs replacing. All of the circulating pumps are installed above the level of the boiler. Is it necessary to drain the entire system, or can I just isolate the affected zone, drain only that zone and purge only that zone after replacing the pump?
@TheTruthSeeker756
@TheTruthSeeker756 5 жыл бұрын
How much you charge travel time 1 hr 20 minutes to North of WORCESTER? Need to replace one of these, plus a valve on the pipe feeding it, plus install some shut off valves on cold water / hot water pipes, plus solve water hammer problem
@lyleyazzie4649
@lyleyazzie4649 3 жыл бұрын
can you take apart the taco to check the inside without causing damage?
@lesio333
@lesio333 4 жыл бұрын
I have air scoop installed in my system. Would it take care of purging the air or I would have attach the house and bleed it like you did?
@jhhvacplumbing1944
@jhhvacplumbing1944 9 жыл бұрын
Nice work Steve , snow is melting and had a few flooded basements today . How's it by u ?
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
justin henning snow is melting no flood calls yet
@erronblack1321
@erronblack1321 7 жыл бұрын
JH HVAC & Plumbing
@jhhvacplumbing1944
@jhhvacplumbing1944 7 жыл бұрын
london johnson what's up ?
@sdanville
@sdanville 7 жыл бұрын
when i changed my pump , i took is off without draining, just did it fast. lost a quart of water. it was fast.
@kennyplay5982
@kennyplay5982 4 жыл бұрын
I might try that. Need to replace a pump
@phineaswhipsnade8551
@phineaswhipsnade8551 7 жыл бұрын
I have a bad taco 007-f3, will a new pump motor (007) bolt in like you did in this video? Are they universal fit to the cast iron part? Thanks, great vid
@awsom70
@awsom70 9 жыл бұрын
Good work steve! Sometimes things like to act up when were not there and work fine when we are there its a pain but it happens to us all! What do you think about weather responsive controls steve? Ever put any on? Like em, hate em?
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
awsom70 i am not a fan of outside reset controls on a older system like this one .on the newer condensating boilers yes,, depends on the system there hooked up to .
@johnleveille2110
@johnleveille2110 3 жыл бұрын
Where are the isolation valves?
@natedaniels2854
@natedaniels2854 7 жыл бұрын
hay steven what do you do when you see that the basement still have expedites down their or on the pipes.
@mom4818
@mom4818 3 жыл бұрын
The old pump looked beat up. Why not replace the whole pump? the old O rings between the inlet and outlet of the pump might be in bad shape. It is a good time to change the whole pump since you are draining the system. These are the corner cutting that contractors do.
@sheepspinning
@sheepspinning 8 жыл бұрын
my pipes are hot but the downstairs is cold and the upstairs is normal, what could be the issue?
@stevenlavimoniere
@stevenlavimoniere 8 жыл бұрын
+Dawn n i would have to be there to see whats going on ,
@noweare1
@noweare1 5 жыл бұрын
Your pipes are hot because your 2nd floor return is near the 1st floor return. Steel is a good conductor. I have the same problem as you. Sure you fixed it now but I bet it was the taco recirculator pump like the one he's replacing in the video.
@KhaiNguyen-ow1ll
@KhaiNguyen-ow1ll 6 жыл бұрын
hey steven i have a raypak water heater at work can you help me please. My work asked me to lubricate the motor & pump bearings where would that be located?
@Yodumeee
@Yodumeee 2 жыл бұрын
Find them yet 🤣
@Deafjustin
@Deafjustin 9 жыл бұрын
Tube and Knob wiring from 1930's
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
Justin Vancouver not quite that old ..but old enough
@michaellicitra7632
@michaellicitra7632 9 жыл бұрын
Why no air eliminator? Shouldn't there be one? The air in the new water will be less soluble as it is heated and come out of solution.
@stevenlavimoniere
@stevenlavimoniere 9 жыл бұрын
Michael Licitra a lot of system i work on do not have and air scoop purge it well and you will be fine .
@raffsr3143
@raffsr3143 7 жыл бұрын
Isn’t that cheating? i mean not changing the entire housing with the 2 gaskets?
@lynnenash5209
@lynnenash5209 3 жыл бұрын
Is the O-ring for the cartridge installed Dry or did you lubricate it first?
@salmonhunter7414
@salmonhunter7414 8 жыл бұрын
I thought you would change the whole part because of the warranties
@stevenlavimoniere
@stevenlavimoniere 8 жыл бұрын
+James Splint i do what i have to to get her fixed
@Tworth23
@Tworth23 3 жыл бұрын
Why would this plumber not replace the whole unit unless it’s not a paying customer. I didn’t watch the whole thing?
@johnleveille2110
@johnleveille2110 3 жыл бұрын
You are draining the system why not replace the entire pump..
@safemoonflatearther8892
@safemoonflatearther8892 7 жыл бұрын
steven my boiler comes on, but heat not circulating even if i manually open the Taco valves... pump is not making any noises... what are your thoughts
@rebelsprophet7185
@rebelsprophet7185 7 жыл бұрын
Mine too Steve!
@safemoonflatearther8892
@safemoonflatearther8892 7 жыл бұрын
REBELS PROPHET turned out to be the circulator pump
@rebelsprophet7185
@rebelsprophet7185 7 жыл бұрын
I have now power to the Honeywell Aqua Stat and then power stops at that point. The emergency on/off switch being 60 years old was shot and arc's. The Taco C-P is not picking up current, as when listening, there is a Hum while on standby. What ever happened this Repco broke down i in series of 3's. 1st the on/off switch. 2nd the Thermo-coupler and 3rd the C-P. I will have tackle the CP on my own was i trouble shot the other two. And now as i see these new Taco's C-P's, they are with out a Capacitor as the old C-P's have being 27 years old.
@ritchiepitchie8839
@ritchiepitchie8839 7 жыл бұрын
Why would you buy a whole circulator ? Just replace the cartridge?!?!?!~?!?
@rebelsprophet7185
@rebelsprophet7185 7 жыл бұрын
Where can i purchase a cartridge for a Taco C-P?
@gino007able
@gino007able 4 жыл бұрын
FYI, if one radiator is not working and you let the room out and they decided no to pay rent, check the on/off valve even if you think the valve is frozen.
@user-yl7zu5tw8i
@user-yl7zu5tw8i 7 жыл бұрын
There are 2 things wrong with this video: 1: You didnt show us what was wrong with the old unit. What exactly was wrong???? 2: Why didnt you just change the cartridge instead of the whole circulator???
@stevenlavimoniere
@stevenlavimoniere 7 жыл бұрын
because i can buy the whole cerculator for the same price as just the cartridge... why would i buy just the cartridge ?? from your comment i can tell your not in the trade
@albertbranca4644
@albertbranca4644 7 жыл бұрын
J ,
@raph11spd
@raph11spd 7 жыл бұрын
Thanks for posting this video, I'm diagnosing my own heating system and the taco pump to my upstairs will burn your hand if you touch it but the pipes its supposed to circulate are barely luke warm. Tells me the pump is busted. Your video helped me confirm my guess, especially with this comment!
Blown Taco SR501 Switching Relay - How to Test Resistance on Taco 007 Circulator
36:25
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 22 М.
bad taco zone valve replaced ,purged air from hydronic system
17:54
steven lavimoniere
Рет қаралды 48 М.
Finger Heart - Fancy Refill (Inside Out Animation)
00:30
FASH
Рет қаралды 20 МЛН
Самый Молодой Актёр Без Оскара 😂
00:13
Глеб Рандалайнен
Рет қаралды 12 МЛН
Опасность фирменной зарядки Apple
00:57
SuperCrastan
Рет қаралды 9 МЛН
burnham gas boiler no heat call bad circulator
24:02
steven lavimoniere
Рет қаралды 98 М.
Hydronics System Components
12:31
Tec Tube
Рет қаралды 370 М.
Confused Gas Heat System! Either No Heat or Overheats! Bad Circulator & Check Valve - Problem Solved
16:14
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 16 М.
why some hot water baseboard just doesnt get hot
8:56
louis tsalikis
Рет қаралды 294 М.
Taco zone valve leaking water
23:31
steven lavimoniere
Рет қаралды 24 М.
Top 10 Circulator Pump Problems Found on Boilers!
20:11
AC Service Tech LLC
Рет қаралды 221 М.
purged air from heating zones with zone valves,bad zone head
15:38
steven lavimoniere
Рет қаралды 61 М.
How To Replace Your Taco Circulator Pump
19:10
MrV2u
Рет қаралды 31 М.
Installing the Radiant Floor components
9:43
Comfy Homestead
Рет қаралды 56 М.
No Heat Williamson Gas Boiler - How to Purge Your Single Zone Hydronic System
8:40
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 25 М.
REAL OR FAKE?
0:10
dednahype
Рет қаралды 8 МЛН
Самый ДОБРЫЙ мальчик!😎
1:00
Petr Savkin
Рет қаралды 4,9 МЛН
не так кладёшь #карелия #рыбалка #природа #сегозеро
0:13
Север - Родина смелых
Рет қаралды 2,8 МЛН
I drew a picture for my brother @ohiofinalboss.
0:22
竹やぶgames
Рет қаралды 23 МЛН
На сколько опасна рыба меч?
0:40
Fact Fusion
Рет қаралды 2,4 МЛН