Blown Taco SR501 Switching Relay - How to Test Resistance on Taco 007 Circulator

  Рет қаралды 22,307

Mikey Pipes - Pipe Doctor Plumbing & Heating & Air

Mikey Pipes - Pipe Doctor Plumbing & Heating & Air

2 жыл бұрын

The resistance on a Taco 007 should be between 130-160 ohms. Out of range? Replace! Blown Taco SR501 switching relay replaced on this Burnham Independence Steam boiler SIN4. How to test resistance on circulator.
What’s in your Veto? Here is mine:
Veto TP-XXL amzn.to/3zX10vg
Milwaukee M12 Fuel 1/4" Impact Driver amzn.to/3I9yLfI
Wiha Allen Keys: amzn.to/33ipGmb
HIKMICRO B20 amzn.to/33iGklx
Furnace Switch amzn.to/31X89PT
Milwaukee Light amzn.to/3I38Lmh
Wagos amzn.to/34QoiaU
Milwaukee Set amzn.to/33vnQOz
Torpedo Level amzn.to/3no1oOk
Crescent set amzn.to/3GtZeV8
Wiha 7 piece set amzn.to/3rkISaK
Milwaukee step bit amzn.to/3I395Bv
Flare wrench amzn.to/3noJZ8s
Ridgid 10” wrench amzn.to/3GvRnqa
Fluke non-contact tester amzn.to/31VQgAQ
Klein drivers amzn.to/3qoe21W
Knipex Wrenches amzn.to/3trzFjS
Klein 11-1 amzn.to/3tpsPLD
12” crescent amzn.to/3A0CZ6S
Gerber Gear Pocket Knife amzn.to/3foaW7I
Yellow Jacket Hand Ratchet amzn.to/3nrDgup
I am on Discord & WhatsApp!
Discord: / discord
WhatsApp Group: chat.whatsapp.com/CHZWtZe4KMG...
Mikey Pipes Uncensored: / @mikeypipesuncensored
New oval raised silver stickers are from:
Armored Decal Company Inc.
35 Victoria St. E, Unit 9
Alliston, Ontario L9R 1T3
(p) 705-435-6665
(e) ken@armoreddecal.com
(Tell them Mikey Pipes sent you)
Please support this channel and Mikey Pipes and consider the following…
Pipe Doctor long-sleeve shirts are available in Medium, Large & XL
Minimum donation of $34 is appreciated
Pipe Doctor FlexFit Embroidered Caps
Minimum donation of $37 is appreciated
(If you are international - please add a minimum of $40 for shipping/postage)
Shopping on Amazon? Please use my referral link amzn.to/2PjjS4v
Sticker Requests:
Do you want a sticker to show your support of this channel? Email your request to me! mike@mikeypipes.com
Name
Address
City, State, Zip
Consider making a donation of $5.00, or ANY amount, to the postage fund! I literally mail out stickers all over the globe. I've sent stickers to HVAC guys in Afghanistan, New Zealand & all over Europe.
PayPal is: office@pipedoc.net
Venmo: @PipeDoctor
CashApp: $mikeypipesny
Want to send a love letter, note or gift? Our mailing address is:
Mikey Pipes
C/O Pipe Doctor Plumbing
80 E Hawthorne Ave
Valley Stream, NY 11580
#Taco #Relay #Circulator

Пікірлер: 68
@larryboy8821
@larryboy8821 2 жыл бұрын
A little KR. Bailed out of California in January, the place has gone insane. Retired early to Nebraska, found Mikey Pipes because I didn't know anything about boilers, water softeners and RO systems. I do now! Thanks Pipes!!
@Lewdacris916
@Lewdacris916 2 жыл бұрын
wish i could leave the state but all my family and friends are here! definitely wont be able to retire here with the way the housing market is going!
@eddiew.6485
@eddiew.6485 2 жыл бұрын
I was digging your conversation with the Homeowner…….wished there was more! 😎 Nice job as always, Mikey👍
@brucerobak145
@brucerobak145 2 жыл бұрын
A thought. Use a temporary power cord to test each circulator motor seperately first before removing the circulator control. Doing this you'll isolate the parts to find where the problem is, be it with the circulators or circulator control. Noisy circulator bearings, impeller problem, shorts in the motor or wiring will be revealed. Isolate and divide up the components to find the problem to conquer it.
@georgiamurray1878
@georgiamurray1878 2 жыл бұрын
Getting better and better all the time
@isobelmason1069
@isobelmason1069 2 жыл бұрын
You have the best ideas
@charliewest5377
@charliewest5377 2 жыл бұрын
My friend Thanks for sharing this
@libbyjames4513
@libbyjames4513 2 жыл бұрын
Thank you so much for sharing
@rosehunt6158
@rosehunt6158 2 жыл бұрын
lovely video
@teresaoehler9309
@teresaoehler9309 2 жыл бұрын
Pleasant video
@victoriasaunders2342
@victoriasaunders2342 2 жыл бұрын
I Love the look
@annemacomber9736
@annemacomber9736 2 жыл бұрын
stupendaaaa,Super ! You are so striking!
@karrierace8661
@karrierace8661 2 жыл бұрын
Nice video you have there
@johncavaco6491
@johncavaco6491 2 жыл бұрын
It depends if the capicator is charge. Take capicator out of the circuit to read the motor windings.
@careydecker4427
@careydecker4427 2 жыл бұрын
Yes love it
@pabloolivas5197
@pabloolivas5197 Жыл бұрын
Hello Mikey.. I have a situation that room temperature rises above the thermostat setting. For example, it's 75 (and rising) while the thermostat setting is 70. I found that the Taco SR501 red indicator light (call for heat) is always on, with or without the thermostat connected to the system. So I think the problem is not the thermostat but rather the Taco SR501 switch relay. To control temperature, I have to manually switch off the power to the heating system. What could cause the red indicator light on all the time? How do I know for sure that the Taco SR501 relay is the problem? Thanks for your insights.
@bobcat138
@bobcat138 2 жыл бұрын
So you show hot on the white wire using the no contact tester ? Or maybe I saw it wrong on the vid
@marionbaker7424
@marionbaker7424 2 жыл бұрын
With much respect..you are fantastic...and you are stunning
@papascoobs4096
@papascoobs4096 2 жыл бұрын
Sigh...This is what happens when plumbers play with electrical.I was screaming at the screen "MIKEY THE FUSE LOOK AT THE FUSE, DONT TAKE IT OFF MIKE"!!!But to your credit you found it in the end.
@pamelaojeda8879
@pamelaojeda8879 2 жыл бұрын
Bravo
@aliciagriffin9560
@aliciagriffin9560 2 жыл бұрын
CHEERS!!
@ednadean7984
@ednadean7984 2 жыл бұрын
love
@mikeobrien9404
@mikeobrien9404 2 жыл бұрын
Should there be a strainer on the entering side of each side of the plate type heat exchanger.
@throttlebottle5906
@throttlebottle5906 2 жыл бұрын
yes, but those clog very fast in such service. it shouldn't pull off the very bottom of boiler, it should come from an elevated tapping below operating water level and above the bottom, then return into the very bottom or close. most have specific tapping's just for feeding heating loops, usually listed and labeled for domestic hot water indirect tanks.
@mikeobrien9404
@mikeobrien9404 2 жыл бұрын
@@throttlebottle5906 So it is better to change the heat exchanger the clean strainers
@kennethbailey2616
@kennethbailey2616 5 ай бұрын
We don’t have a sales tax here in Montana.
@tomdube971
@tomdube971 2 жыл бұрын
I’m trying to figure out the reason for the hot plate heat exchanger. Is there glycol in that zone or what? Maybe that zone is used to melt snow on the sidewalk? And while you’re talking finance with the customer you should have Peter pipe those relief valves to the floor
@throttlebottle5906
@throttlebottle5906 2 жыл бұрын
a good inspector would catch the lack of relief valve on the hydronic loop. but most of them would be too busy flagging and writhing over multiple other issues to even notice.
@realestateservicessaleshea99
@realestateservicessaleshea99 2 жыл бұрын
Did you charge him for the conversation 🤔 🤣🤣🤣😎 Thanks again for the videos! Stay safe. Retired (werk'n)keyboard super tech. Wear your safety glasses!
@ATSNorthernMI
@ATSNorthernMI 2 жыл бұрын
At least an hour. If it's not a full hour, just bullshit until it gets there. That way you don't charge the customer for an extra hour and it only being 20 minutes in.
@atlasfueloilinc.2421
@atlasfueloilinc.2421 2 жыл бұрын
Still only circulating the mud on the bottom of the boiler. Which is also the coolest water.
@throttlebottle5906
@throttlebottle5906 2 жыл бұрын
🤣🤣🤣🤣
@petem6291
@petem6291 2 жыл бұрын
Mike , it would’ve been Interesting to see how many amps the bad motor was drawing ?? Being that you work with the 007 all the time it would be good to know what a good amp draw is I guess you could test a few of them When there are new and when they have been in service…
@throttlebottle5906
@throttlebottle5906 2 жыл бұрын
the max allowable current draw is on the rating plate and in manuals/documentation. the actual current draw varies with feet of head (flow resistance), it should never be above the rating on the tag/manual, per circulator.
@hollydavidson5219
@hollydavidson5219 2 жыл бұрын
Superlike
@StephenWolver
@StephenWolver 2 жыл бұрын
Just a reminder current=voltage/resistance. If the motor resistance is 200+ ohms it draws less current than at 160 ohms.
@throttlebottle5906
@throttlebottle5906 2 жыл бұрын
that's an AC motor though, so throw out much of what you know for DC circuits, because impedance and other factors throw a huge monkey wrench in there, far more math and data needed 😵
@ATSNorthernMI
@ATSNorthernMI 2 жыл бұрын
Probably not a bad idea to change the control relay just to eliminate a potential problem later on down the road.
@duwayneodom1297
@duwayneodom1297 2 жыл бұрын
@mikeypipes you look like a discount Kurt Russell 😂
@chriscurran416
@chriscurran416 2 жыл бұрын
Hi mike about 200/220 ohms on circulator
@chriscurran416
@chriscurran416 2 жыл бұрын
Bearing im in uk voltage here is higher than 110 in the states so i would say 130-150 states
@atlasfueloilinc.2421
@atlasfueloilinc.2421 2 жыл бұрын
I always wondered how you got out of a customer’s house before they started talking to you.
@snidelywhiplash8923
@snidelywhiplash8923 Жыл бұрын
What's the purpose of the heat exchanger?
@snidelywhiplash8923
@snidelywhiplash8923 Жыл бұрын
@@PipeDoctor I understand what a heat exchanger is, even an in-room radiator can be described as a heat exchanger. My question, and sorry if poorly worded, is ----why is this heat exchanger here, what purpose is it used for this home? Is its use here typical of what's done with other home HVAC systems in your area? Thanks.
@MrDmadness
@MrDmadness 4 ай бұрын
​@@snidelywhiplash8923separates system glycol in the heat loops from boiler primary loop, if there was a rupture on the radiator the boiler doesn't go down
@snidelywhiplash8923
@snidelywhiplash8923 4 ай бұрын
@@MrDmadness In the first 60 seconds of the video, MP says points to a pump on the heat exchanger and says it's circulating water to the basement zone. Why would a house occupied presumably 12 months of the year need to have glycol circulating in some radiant zones?
@MrDmadness
@MrDmadness 4 ай бұрын
@@snidelywhiplash8923 because proper glycol levels will not allow the zone to freeze in the case its not used and it gets cold, it's very common in high mass and baseboard heating applications. Glycol also prevents internal corrosion as its an oil so not oxidizing due to the water. The caveat is that it can jelly up if left un circulating too long
@miketimmins697
@miketimmins697 2 жыл бұрын
Kurt Russell ... YES !
@demijenkins9486
@demijenkins9486 2 жыл бұрын
Süper Off
@dorothygoff3224
@dorothygoff3224 2 жыл бұрын
T O P
@johng1077
@johng1077 2 жыл бұрын
You aren’t double taxed if you remember you said you pay the difference from what you had already paid when you bought the part. I am surprised NY done;t have tax resale certificate it it probably one of the most widely used things for resellers along with NEXUS. Connections with particular taxing jurisdiction.
@reedjr5281
@reedjr5281 2 жыл бұрын
200ohms
@gordonfrancis4039
@gordonfrancis4039 7 ай бұрын
1st brass circulator 2 strainer 3 insulation fiberglass on the piping 4 you used black pipe on your relief valve biggest no no
@patmcnally6
@patmcnally6 2 жыл бұрын
No Mike you do not look like Kurt Russell but You can take the lead Part in ESCAPE FROM THE STATE OF INSANITY.
@scotts4125
@scotts4125 2 жыл бұрын
You can't have him. Gov. DeSantis that is. We love him.
@joseph-ine452
@joseph-ine452 Жыл бұрын
Sweet potatoes that was long video.
@macinieves3863
@macinieves3863 2 жыл бұрын
Good
@lisaholliman6097
@lisaholliman6097 2 жыл бұрын
"Strong"
@katysalter2021
@katysalter2021 2 жыл бұрын
Immensely killer
@melissalawrence4465
@melissalawrence4465 2 жыл бұрын
ohhhhhh God So beautiful
@Hvac-dude
@Hvac-dude 2 жыл бұрын
THE resistance should be 0.3 and 2 ohms
@throttlebottle5906
@throttlebottle5906 2 жыл бұрын
arc flashes for you. 🤣
@jimmyjamesl2318
@jimmyjamesl2318 Жыл бұрын
completely wrong about how resale tax works
Homeowner Tries To Fix Gas Boiler and Fails Miserably How to Bled or Purge Zones
31:54
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 113 М.
Actual HVAC Service Call: Central AC Isn’t Cooling Indoor 89 Degrees Decades Old Rheem Low on Freon
12:09
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 2,1 М.
Пробую самое сладкое вещество во Вселенной
00:41
Incredible magic 🤯✨
00:53
America's Got Talent
Рет қаралды 59 МЛН
Nutella bro sis family Challenge 😋
00:31
Mr. Clabik
Рет қаралды 12 МЛН
Boiler Explosion: Help! What to Do When Your Boiler Blows!
22:23
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 34 М.
How Did They Expect This To Work? How to wire a 2 zone Taco switching relay for circulators
16:05
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 29 М.
Zone Valves, Circulators, Relays & Controls
1:58:56
Taco Comfort Solutions
Рет қаралды 27 М.
How to install/Wire Taco SR504-4 Switching Relay
3:12
Shalom G Construction
Рет қаралды 29 М.
Hydrotherm Gas Boiler No Heat Bad Zone Switching Relay Replaced Taco SR501 Installed
15:12
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 14 М.
Zone Valve Wiring for Beginners - How to Wire Multiple Honeywell Zone Valves to Stats and Boiler
42:21
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 84 М.
Taco 007e high efficiency circulator pump available at Torrco
11:25
Weil McLain Gas Boiler Overheating on High Temperature and Not Heating The House
28:38
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 42 М.
no heat on first floor bad taco 007 circulator replaced,purged air
21:32
steven lavimoniere
Рет қаралды 126 М.
JFK Airport Hotel Not Cooling from Daikin Ducted Mini Split System
12:16
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 12 М.
The screw cap can also be played like this
0:20
Dice Master_1910
Рет қаралды 6 МЛН
Let me show you (P12)
0:21
Discovery Boy
Рет қаралды 6 МЛН
Как красиво снять полет #marim #shortsvideo
0:15
Лучшая краска для стен и потолков, которая не желтеет, не покроется грибком и не имеет запаха
0:22
БуСтройМаркет | Строительный склад-магазин СПб
Рет қаралды 4 МЛН