Ptac leaking water into the room?? Try this!

  Рет қаралды 37,182

Ptac Solutions

Ptac Solutions

Күн бұрын

Пікірлер: 76
@goingolfn1999
@goingolfn1999 3 жыл бұрын
I wish you would have shown how to clean the clogging of the drain pan to the outer part of the PTAC. There were some good points but just demonstrating the fixes would have been nice.
@kelm1123
@kelm1123 2 жыл бұрын
Yes that would help a lot.
@sethneal3081
@sethneal3081 Жыл бұрын
You absolutely rock for uploading these videos. Hot as heck here recently, and the old ptac was not getting enough cold air out. Took care of the standing water/gunk problem, and she's blowing out some sweet Alaskan tunes. Thank you sir.
@bigeddie2136
@bigeddie2136 3 жыл бұрын
Love your videos. They are great. Full respect. Please just lower background music. I was ready to throw the ptac out of the 3rd floor window. Lol 🎶
@PtacSolutions
@PtacSolutions 3 жыл бұрын
Lol.. duly noted. Thanks for watching
@Prebound_
@Prebound_ 3 жыл бұрын
Our old GE dial units never leak, nor do our Amanas', but all the Friedrichs do. We have a wall sleeve issue as well and are currently shimming with fat door stops. XD
@eduardohandyman
@eduardohandyman 3 жыл бұрын
the reason why the ptacs leak inside the room, is because since the cold cleaner came out in spry , no one wants to remove the unit to wash with coil cliner and water,theis only spraye them with the coil cleaner spray and that is everithing is ready clean they say, and oll the dust in the wet coil closes the drain of the ptac and when the water cannot come out from behind, it overflows in from of the room
@tonygray9174
@tonygray9174 2 жыл бұрын
Readjusting the wall sleeve tilt solved the problem for me.
@PtacSolutions
@PtacSolutions 2 жыл бұрын
Hello Tony Yeah, I would say that's one of the main reasons why they leak
@josephgarza9377
@josephgarza9377 Жыл бұрын
Would it be okay to just drill a hole in thw back side?
@jimmysmith9957
@jimmysmith9957 Жыл бұрын
Is it possible to remove the entire PTAC from the drain pan without opening the refrigeration lines so that the drain pan can be painted? I have a unit with the coating on the drain pan that is coming off and the pan is starting to rust. Great Channel!!!
@PtacSolutions
@PtacSolutions Жыл бұрын
Hey Jimmy Thank you!!.. question for you is the pan foam or the plastic one?
@jimmysmith9957
@jimmysmith9957 Жыл бұрын
@@PtacSolutions Metal. I'm talking about the metal pan / base plate all the components are assembled in and attached to. The part that comes into contact with the sleeve at the bottom.
@PtacSolutions
@PtacSolutions Жыл бұрын
Oh ok well Yes its possible, but it's going to be a lot of work
@lllzergeouslll74
@lllzergeouslll74 3 жыл бұрын
I have a ptac unit and its not draining and blowing a visible steam like mist out of the vents worried it may be leaking freon it blows cold and no smell no weird sounds and I seen the drain pan does have standing water .
@PtacSolutions
@PtacSolutions 3 жыл бұрын
Hello, the mist you see coming from the vents is usually condensation picked up by the blower that's usually normal... is the unit leaking water into the room?
@stevenlapham5254
@stevenlapham5254 2 жыл бұрын
great review of something quite a bit of entry level guys don't get - good job.
@gabbyamo4509
@gabbyamo4509 3 жыл бұрын
Music too loud.
@paolaquintero520
@paolaquintero520 Жыл бұрын
Just a question can closed the back of the unit outside on winter and heat up the room if I have a vinyl covering the outside Sometimes the cold air comes in making the room cold again.
@HadesMcFisher2023
@HadesMcFisher2023 Ай бұрын
How to remove the inside of the unit, after removing the cover??
@josh88113
@josh88113 14 күн бұрын
I have a 150 of these leaky things. It’s the wall sleeve on everyone. I’m gonna try to cant them out
@cantwaitkid
@cantwaitkid Жыл бұрын
Do you have a video that covers when unit is turned on, compressor comes on and has cold air then compressor kicks off too soon and never re- engages.
@PtacSolutions
@PtacSolutions Жыл бұрын
No, but I would check for a dirty condenser coil, the funtion of the condenser motor or broken fan blade. How old is the unit?
@cantwaitkid
@cantwaitkid Жыл бұрын
@@PtacSolutions the unit is a 2006 Carrier. I work at a hotel and we have this happening to several units, then we have guests complaining. Do you suppose these units are getting too hot on the outside of the unit? Is there a safety thermal switch?
@PtacSolutions
@PtacSolutions Жыл бұрын
@@cantwaitkid well that code is due to the ouyside temperature is above normal, have you checked inside the condenser fan shroud if the coil is dirty?
@weslawsonsilverback
@weslawsonsilverback 3 жыл бұрын
I will have to adjust the wallsleeve
@panzerd5248
@panzerd5248 Жыл бұрын
Good video, but it’s hard to hear you over the music
@PtacSolutions
@PtacSolutions Жыл бұрын
Yes, I know. Sorry about that
@BrandyRant
@BrandyRant Жыл бұрын
Will getting it draining properly also fix it not cooling like it should?
@PtacSolutions
@PtacSolutions Жыл бұрын
Hello, No, if the unit is not cooling properly there could be other problems
@BrandyRant
@BrandyRant Жыл бұрын
@@PtacSolutions I will search through your other videos 😀
@hugohernandez8783
@hugohernandez8783 3 жыл бұрын
Thank you amigo ¡¡.
@michaelbell5699
@michaelbell5699 2 жыл бұрын
I have a suburban dynaline making loud Humming noise when ac is on. Any thoughts?
@PtacSolutions
@PtacSolutions 2 жыл бұрын
Hey Michael I'm not familiar with that type of unit, but maybe we can try to figure it out. That humming noise does it sound like it's coming from the electrical compartment?
@rickellis8964
@rickellis8964 3 жыл бұрын
can you put chlorine tablets in drain pan to keep sludge and muck from forming?
@PtacSolutions
@PtacSolutions 3 жыл бұрын
Hey Rick You can use some of these.. not sure if these were the ones you are referring to www.amazon.com/dp/B000KM3BUY/ref=cm_sw_r_awdo_navT_g_ZWWM6K1Z743H0PCN2EKH
@ianharkins2172
@ianharkins2172 3 жыл бұрын
Hey, so from the outside through the grate I can see the drain pan is holding standing water. The wall sleeve has a visible drain pipe to the outside, but where is the drain pan supposed to drain from?
@PtacSolutions
@PtacSolutions 3 жыл бұрын
Hello, the water goes from the ptac drain pan to wall sleeve where the drain pipe is connected. The unit has some holes on the back side where the water drains, also some of the water is picked up by the fan and shoot through the condenser coil
@ianharkins2172
@ianharkins2172 3 жыл бұрын
@@PtacSolutions thank you. So if I’m getting water on the carpet inside, there’s probably something preventing the condensation from flowing to the back of the drain pan.
@PtacSolutions
@PtacSolutions 3 жыл бұрын
@@ianharkins2172 it could be one of many, clogged drain pipe or pan, wall sleeve could be tilted inward(unlevel) or maybe the unit may just need to be washed
@ianharkins2172
@ianharkins2172 3 жыл бұрын
@@PtacSolutions very helpful thank you
@ronlebron4876
@ronlebron4876 3 ай бұрын
I washed the unit still draining into the room ​@@PtacSolutions
@mr.orim0782
@mr.orim0782 2 жыл бұрын
Wish there was no music so I could hear what your were saying better
@PtacSolutions
@PtacSolutions 2 жыл бұрын
Hello Ricky Yeah messed up by leaving the music really loud.
@PlasticStrws
@PlasticStrws 3 жыл бұрын
Lift the front of the PTAC and screw it into the sleeve this will make the unit lean back and drain. Or drill some holes into the wall sleeve so it’ll drain. Lol so many easier methods
@PtacSolutions
@PtacSolutions 3 жыл бұрын
Hello To drill holes into the wall sleeve would work if the the back of the sleeve was sticking out to the outside of the building, but there situations where that's not the case, like if they would be on the second or third floor, the water would just come into the building through the sheetrock or ceiling tile.
@angelojuvera5885
@angelojuvera5885 3 жыл бұрын
@@PtacSolutions True . I've dealt with that. Had to caulk the inside corners and openings of the sleeve so that the only place for water to flow was the drain itself.
@prestonberg9604
@prestonberg9604 3 жыл бұрын
Damn those are some nasty looking units.good Lord. Ones in the hospital are from 2006 and look new
@PtacSolutions
@PtacSolutions 3 жыл бұрын
Yeah I know.. I see a lot of them like that
@pedvag10
@pedvag10 3 жыл бұрын
Friend! So I got a pmh093 that I discovered today with the electronics compartment full of water I noticed that on the drain pan on the id coil it was chipped (missing a little bit maybe a 1/4 inch right at the lip) this is visible right were the metering piston is will you say that's were the water is leaking to the electronics bay,? I was confused so I watch your video because of this will you know if this series of ptacs drain to the OD blower like the one on this videos ? thanks so much man!
@PtacSolutions
@PtacSolutions 3 жыл бұрын
Hello, If the drain pan is missing a piece than more than likely that's how the water is overflowing to the electrical compartment. I have used some putty to create a boarder so the water won't overflow. It has worked for me, you could try it just make sure the pan is completely dry. So, you can eliminate that possibility
@kelm1123
@kelm1123 2 жыл бұрын
Can you make a video on replacing a steam trap valve.
@PtacSolutions
@PtacSolutions 2 жыл бұрын
Hey Kel I haven't worked on one of those yet..is that for a gas heater ptac?
@kelm1123
@kelm1123 2 жыл бұрын
@@PtacSolutions oh Ok, the boiler is oil based.
@d0805446
@d0805446 3 жыл бұрын
Is the space right under the monitor display legitimately allowed to hold the water? Because mine not only the drain place under the coil has the water, but also the place I mentioned,
@PtacSolutions
@PtacSolutions 3 жыл бұрын
No, that means the water is overflowing from the drain pan because is not draining properly
@d0805446
@d0805446 3 жыл бұрын
@@PtacSolutions thx, do you know where is the front drain vent? (in video you only pointed out the back drain vent, I've clean that out but I also like to clean from the start point)
@jay-c6128
@jay-c6128 Жыл бұрын
@@PtacSolutions would that cause it to not cool adequately? With water maybe cooling the coils ?
@Zawo254
@Zawo254 3 жыл бұрын
I have 3 Ptacs (GE Zoneline) Compressor kicking on inside fan working but the outside fan blades that blow into the room arent kicking on. Any reason why.? Please help
@PtacSolutions
@PtacSolutions 3 жыл бұрын
Hey Zee Make sure the fan is not caught on something(seen that a lot) .. if not check the capacitor or any loose wires. If all that checks out, next I would check if the board is sending power to the motor
@perryclemons3090
@perryclemons3090 Жыл бұрын
The jelly stuff is what i call ectoplasm lol. Use clorine tabs after you clean that shit out
@soflofan
@soflofan 3 жыл бұрын
Jelly substance is skin!
@Jonnytjat
@Jonnytjat 6 ай бұрын
Nice and useful video but my lord was it difficult to hear what you were saying. That background music was insanely loud and I even put headphones on to try and hear you more clearly and it was still crazy loud. Especially with no captions. Nice and helpful video but please lower or eliminate the music. Especially some techno music like that. Was expecting maintenance tips. Not a rave 😂😂
@Picwajzzz
@Picwajzzz 5 ай бұрын
you can turn captions on just click CC
@TamyB1000
@TamyB1000 Жыл бұрын
Music isn’t needed. Can’t hear you!
@bigspeaker781
@bigspeaker781 Жыл бұрын
Why the music tho
@PtacSolutions
@PtacSolutions Жыл бұрын
Yeah my bad
@danielcontee7851
@danielcontee7851 Жыл бұрын
Cannot hear over the music
@heyvakoo1221
@heyvakoo1221 11 ай бұрын
WHY THE MUSIC????
@calvinmckinney2268
@calvinmckinney2268 Жыл бұрын
Music too loud!!
@PtacSolutions
@PtacSolutions Жыл бұрын
Hey Calvin Yes I know, sorry about that
@karimyoussef8493
@karimyoussef8493 4 ай бұрын
I hoop with out music
@kr4536
@kr4536 10 ай бұрын
Subtract the music please. It's not necessary
@jordonbramwell5486
@jordonbramwell5486 5 ай бұрын
Too much music how the hell show we hear you
@Carpediem6706
@Carpediem6706 3 ай бұрын
DID NOT HELP AT ALL
PTAC Heating/Cooling Unit - Leak Diagnosis
4:27
Paul
Рет қаралды 15 М.
PTAC Leaking water DIY Easy Fix
12:31
GoAsFarAs YouCanSee
Рет қаралды 2,4 М.
Players vs Pitch 🤯
00:26
LE FOOT EN VIDÉO
Рет қаралды 128 МЛН
HELP!!!
00:46
Natan por Aí
Рет қаралды 71 МЛН
Каха и лужа  #непосредственнокаха
00:15
How to clean hotel ptac units, Amana ptac, GE
4:20
www.cleanairptacs.com
Рет қаралды 73 М.
Blocked Drain 942
19:33
Drain Addict
Рет қаралды 964 М.
Diagnostic of Ptac Ac not cooling
6:25
Ptac Solutions
Рет қаралды 49 М.
BEST AC Drain Line Cleaning Tool | 92 % DON'T Know This
5:51
Deanin' It Yourself
Рет қаралды 863 М.
You Need To Know How To Put Out Chimney Fires.
10:22
Health And Homestead
Рет қаралды 535 М.
How to Flush a Water Heater? | Flushing Will Probably Not Fix Your Problem
8:06
The Grumpy Plumber
Рет қаралды 3,1 МЛН
Amana Ptac External Drain Kit & Wall Sleeve Installation Explanation.
5:59
HVAC Service & Install
Рет қаралды 18 М.
Drain Water from Window or Wall Air Conditioner Drip Pan
8:43
Frugal DIY
Рет қаралды 65 М.
Tricks to help you troubleshoot ptac unit easier...
3:06
Ptac Solutions
Рет қаралды 106 М.
Players vs Pitch 🤯
00:26
LE FOOT EN VIDÉO
Рет қаралды 128 МЛН