Fault finding car park lamp posts

  Рет қаралды 15,986

Residual Electrical

Residual Electrical

Күн бұрын

Пікірлер: 69
@richardkear9840
@richardkear9840 Жыл бұрын
Still one of the best most comprehensive you tubers out there. Keep up the great work mate.
@mjd_double-ya3904
@mjd_double-ya3904 Жыл бұрын
IR test at the load side of each post with supply disconnected. No lifter needed. Admittedly it's a ball ache. Good luck with the wedding.
@adrianraith3831
@adrianraith3831 Жыл бұрын
My normal method with these is to disconnect all the posts and see if the RCBO will reset to prove the supply cable, and then reconnect posts either individually or in groups and see if it'll reset; it's just a bit time consuming covering a big site. Lampposts tend to be a PITA at the best of times simply because they suffer a lot from wind / weather damage, especially (as many people seem to like doing) with pre-flexed floods wired (badly) into junction boxes.
@sergiofernandez3725
@sergiofernandez3725 Жыл бұрын
Hi Mike I am not a Spark but I love your content been watching you for a couple of years. Its great to see you doing installs or troublshooting. You take pride in your work and your work methodically and to a high standard. When you go back to that site can you link out the lighting columns and disconnect all but 1 lamp and then test. Then onto the next one. I have a strong suspicion that the faillure is due to inrush current or a faulty ballast but if one of the light units is filled with water that will not help. Good luck for the wedding. I look forward to your future content
@shuichinz
@shuichinz Жыл бұрын
I wasnt a spark when i started watching, started my apprenticeship as an industrial spark 6 months ago shoutout from NZ
@Arachnoid_of_the_underverse
@Arachnoid_of_the_underverse Жыл бұрын
If you do go back test each disconnected post individually at the base taking a note of all your readings. It will give a clearer indication of if its an accumulation of these earth leakage issues causing the problem. As has been mentioned it may well be water ingress in the lamp head or deterioration of the units themselves thats the problem but you could lay the facts before the client and suggest a course of action i.e. fitting repalcements
@Paul_Holmes
@Paul_Holmes Жыл бұрын
Good to see you again. Totally understand regarding your load, family first, we'll be here when you publish :)
@ettselectricalservices9428
@ettselectricalservices9428 Жыл бұрын
Hi Mike. As I see this… DNO supply separate from the office block so it’s not classed as a final circuit feeding outside lighting. (No additional protection required) If the rated OCPD satisfies a Zs reading that disconnects within 5s an RCD is not required for street lighting metal or not 👍🏻 Just put it on an MCB and it will still comply with those IR readings. Good work…. 👌🏼
@wolvolad25
@wolvolad25 Жыл бұрын
So pleased for the load out business, great news
@BigBangSparky
@BigBangSparky Жыл бұрын
That regulation about lighting that is accessible to the public needing to be protected by an RCD (714.411.3.4) excludes street lighting. Also maybe those thorn bushes are there to make the street lights inaccessible to the public as well as electricians😅
@martin54123
@martin54123 Жыл бұрын
So that's where Thorn electrical came from😂😂😂
@ia4387
@ia4387 Жыл бұрын
Keep the fault finding videos coming. Great video here.
@polarbear7720
@polarbear7720 Жыл бұрын
Had something similar some years back on a railway station turned out to be cumulative earth leakage on the lamposts, could get so many on before it tripped , did not matter what order the fuses were replaced in the lampost cut outs stripped the whole circuit down trying to pin a single fault down, outside lighting a nightmare on rcbo especially older installs.
@M0PAX
@M0PAX Жыл бұрын
love a good fault find
@davidpenn2518
@davidpenn2518 Жыл бұрын
At least you can add pruning to your CV 😊
@danwatson8790
@danwatson8790 Жыл бұрын
Not a spark but international protection I thought it stood for thanks for the knowledge
@MrUtube1916
@MrUtube1916 Жыл бұрын
Great video Mike! Love to see a bit of fault finding. Where'd you get that jacket man? Looks decent
@BeaconFTW
@BeaconFTW Жыл бұрын
Man made this job 20x longer than it should have been, first port of call should have been halfway and split
@anthonybragg
@anthonybragg Жыл бұрын
It was a shame the cutouts were not D.P. or disconnect the neutral of the flex. I bet some of the control gears are rusting.
@cliveramsbotty6077
@cliveramsbotty6077 Жыл бұрын
i did a job in thatcham. set the fire alarm off. and it was one of them that automatically summons the fire brigade.
@admirableawesome2317
@admirableawesome2317 Жыл бұрын
really enjoy all the information you share!!
@carlflatman9496
@carlflatman9496 Жыл бұрын
Congratulations to both of you the 16th enjoy the day.
@YGELLYPIKER
@YGELLYPIKER Жыл бұрын
I’m at 7 mins in I’m guessing photocell full of water
@ElectricianTV
@ElectricianTV Жыл бұрын
Really good video, Mikey I always thought IP rating was international protection, learn something new every day. Them time clock are so expensive. they are bombproof.
@EPD993
@EPD993 Жыл бұрын
I was also taught international protection and i think its in part 2 of bs7671 at abbreviations
@simonmartin3433
@simonmartin3433 Жыл бұрын
That's because it is international protection .
@cumberland1234
@cumberland1234 Жыл бұрын
Love those Sangamo solar time clocks - no need for a photocell. Just remember to set them to GMT.
@YGELLYPIKER
@YGELLYPIKER Жыл бұрын
@@residualelectrical was on my way to wholesalers to pick one of them up got blinded by sun and drove into oncoming bus
@thetruth6693
@thetruth6693 Жыл бұрын
Another cracking video mate 👌
@TheHomeent
@TheHomeent Жыл бұрын
Wedding on 16th June...!! You posted this on the 14th June and I'm watching today on the 15th. So either your heath kick is super massive, or its not this year... 😁 Either way all the best and congratulations. I'm sure she will appreciate the effort but would love you either way, I wish you both all the best. 🎉🎉
@ForTheBirbs
@ForTheBirbs Жыл бұрын
Thanks for another interesting video. Congratulations on your wedding
@cumberland1234
@cumberland1234 Жыл бұрын
Best wishes for Friday 👍
@walseee
@walseee Жыл бұрын
Guys what’s the best bag to buy on loadout?
@TheHomeent
@TheHomeent Жыл бұрын
You wondered how many of us watching are electricians. You'll need to run a poll. 1 tick in the electrician poll from me. Would have tested slightly different, once you've pulled all the fuses and proven supply cables I would have IR'd the posts individually at the post. Just as quick probably as putting three back together and walking back to the board to test. All the best on the wedding. I don't expect an answer as its your big day tomorrow.
@pichacker
@pichacker Жыл бұрын
Might have missed it but was the contactor bridged when testing?
@eS-jb6iv
@eS-jb6iv Жыл бұрын
Can you please elaborate on why the lamppost requires RCD protection? Lighting only needs to be covered by an RCD if it serves a special location
@JimWhitaker
@JimWhitaker Жыл бұрын
Given that RCD protection is so cheap, why would you not install one? Notwithstanding the regs.
@eS-jb6iv
@eS-jb6iv Жыл бұрын
@@JimWhitaker Because RCDs are renown for nuisance tripping and in that situation a very dark road will be left without street lights. Same reasons as to why you don’t put medical equipment like life support systems on an RCD. It says in BS7671 (in amendment 2 also) that street lights are omitted from RCD protection, for this very reason. Not sure where Residual is getting this regulation from. I do a lot of Highway Work and if you put street lightning on an RCD you will get the sack. No hate towards Residual, I was genuinely curious is there was an update to this regulation that I missed but it would appear not
@rjkelectrical6086
@rjkelectrical6086 Жыл бұрын
@@eS-jb6iv regulations are so contradicting, so many book so many difference of opinions. Why do street light not need need RCD protection other than nuisance tripping?
@MS-Patriot2
@MS-Patriot2 Жыл бұрын
@@rjkelectrical6086the person who knew about street lighting and risk management was on holiday the week the IET made up that rule. It’s a huge Vicky Pollard ‘yeah but, no but……’.
@mastergraphic9998
@mastergraphic9998 Жыл бұрын
​@@rjkelectrical6086 because mcb or rcbo are prone to nuisance tripping and corrosion in damp or humid environments. All street lighting should be using a 6amp or 10amp bs88 fuse. Commando sockets on columns need rcbo
@bradnihill2116
@bradnihill2116 Жыл бұрын
Personally I would have just picked what I thought was the pole in the middle of the circuit and split it there to start with.
@mattjones5726
@mattjones5726 Жыл бұрын
surly it would of been easier to remove all fuses then turn the circuit on then put one fuse in at a time to find the fault
@wisey3954
@wisey3954 Жыл бұрын
Ye were cutting aboot they bushes like Tarzan ya madman
@electricalstuff259
@electricalstuff259 Жыл бұрын
Congrats on the marriage my man.
@chrisardern4594
@chrisardern4594 Жыл бұрын
Earth clamping direct onto the swa ? Time delay RCBO might get you over the start up current if you can find one. Or even a c type rcbo.
@Ragnar8504
@Ragnar8504 Жыл бұрын
A type C isn't going to help if the RCD side trips out and at up to 25 mA that's certainly the case. C only affects the magnetic trip of the MCB part, not even the thermal trip.
@tomorichard
@tomorichard Жыл бұрын
Just purchased one of those lunch boxes from you. Ju St what I was looking for
@piotrlobacz
@piotrlobacz Жыл бұрын
IP stands for international protection 😉
@samfish6938
@samfish6938 6 ай бұрын
water in fixtures
@lewisreynods5358
@lewisreynods5358 Жыл бұрын
IP means international protection btw 👍🏼
@lewisreynods5358
@lewisreynods5358 Жыл бұрын
@@residualelectrical Check your abbreviations in your brown book. International protection code.
@looking9175
@looking9175 Жыл бұрын
It would be nice to have these types of documents affordably priced. This one's about £330
@wolvolad25
@wolvolad25 Жыл бұрын
People naming there own stores the with similar names ? 37:40
@deltalima4
@deltalima4 Жыл бұрын
Congrats with the marriage!
@J1T
@J1T Жыл бұрын
chage to D curve rcbo, pack bags n go home job done😎
@J1T
@J1T Жыл бұрын
@@residualelectrical I know 😂 we see a lot of faults with column lighting like the ones in the video; usually just the fitting needs replaced due to water ingress over the years in poor installs. Never seen earth leakage causing tripping before so was good to see that and get a better understanding from it. Great video once again!
@simonmartin3433
@simonmartin3433 Жыл бұрын
WOW.
@G7OEA
@G7OEA Жыл бұрын
I'm and Ex-spark. I qualified on the 16th edition, but left the industry to go into IT / Networking.
@kevy427
@kevy427 Жыл бұрын
SiteAuditPro is brilliant. I’ve been using it for a few years and is ideal for providing a report along with your EICR or fault-finding jobs. It’s easy to use and saves faffing around with trying to organise a PDF or Word document with photos, words, arrows and circles. Another great video👍
@brianhewitt8618
@brianhewitt8618 Жыл бұрын
👌
@YGELLYPIKER
@YGELLYPIKER Жыл бұрын
If you had stuck in at school you wouldn’t have ended up a sparky now they don’t teach that at school
@tschubb1992
@tschubb1992 Жыл бұрын
Not a spark, but surely the next step is to disconnect the Neutral and CPC at the base of each lamppost, then retest/test the flex going up the post? Interesting stuff on the health side 👍 Great content as always, cheers 👍
@Ragnar8504
@Ragnar8504 Жыл бұрын
@@residualelectrical Yeah, I'd be tempted to pull all fuses at the lampposts and reconnect them one by one, measuring earth leakage every time. That way you can rule out the ballasts. Possibly even liven up the circuit with all the lamps out of the circuit first. I've got zero experience with discharge lighting but that inrush leakage sounds a lot like ballast to me. If my math is correct, you need an IR as low as 7.7 kΩ for 230 V mains voltage to drive 30 mA through an earth fault, so the 4 MΩ isn't the issue, it has to be that blip at startup.
@Ragnar8504
@Ragnar8504 Жыл бұрын
@@residualelectrical It's Ohm's law. R=V/I, V being 230 V mains voltage and I the nominal trip current of the RCD in amps, in this case 0.03 A. In reality you need to err on the side of caution because the actual voltage can be up to 253 V (230 V +10%) and the RCD can trip as low as 18 mA if I remember correctly but you still need horribly low IR values for an actual RCD trip. Your initial readings around 0.01 MΩ were dangerously close to tripping conditions though, definitely something wrong there. A very good video, I love systematic fault finding!
@malcolmcroll7556
@malcolmcroll7556 Жыл бұрын
who is the Boss you or your new to-be wife ??
@AdamSparky
@AdamSparky Жыл бұрын
Site audit pro is a game changer been using it for a good few years now
Re-wiring fire damaged sub-main circuits
31:58
Residual Electrical
Рет қаралды 18 М.
WORST DIY ELECTRICS I'VE EVER SEEN! 🤯
22:52
Artisan Electrics
Рет қаралды 764 М.
Beat Ronaldo, Win $1,000,000
22:45
MrBeast
Рет қаралды 144 МЛН
Don’t Choose The Wrong Box 😱
00:41
Topper Guild
Рет қаралды 51 МЛН
Fault finding INFESTED external lighting columns
49:38
Residual Electrical
Рет қаралды 31 М.
Commercial EV charger testing
32:17
Residual Electrical
Рет қаралды 23 М.
FAULT FINDING - RING CIRCUITS
15:38
LEARN ELECTRICS
Рет қаралды 44 М.
Early morning mains shutdown - KQ Load Center Install
28:13
Residual Electrical
Рет қаралды 21 М.
This Is Why Builders SHOULDN'T Do Electrics! 🫣
19:59
Artisan Electrics
Рет қаралды 62 М.
Electrical Fault Finding UK
24:54
Artisan Electrics
Рет қаралды 91 М.
Fault finding on some tripping spot lights!
7:59
The Cable Guy
Рет қаралды 9 М.
Replacing 110V step down transformers
28:39
Residual Electrical
Рет қаралды 15 М.
THE IMPOSSIBLE FAULT FIND - Electrician Life
25:04
Artisan Electrics
Рет қаралды 70 М.
Beat Ronaldo, Win $1,000,000
22:45
MrBeast
Рет қаралды 144 МЛН