As always great explanation with great illustrations. Thanks Ryan for sharing your knowledge and expertise. Your contribution to the trad is much appreciated.
@lukasvilla2657 Жыл бұрын
You are very knowledgeable. I am a first year apprentice. This helps alot. Thank you.
@RyanJacksonElectrical Жыл бұрын
Glad to help!
@ROBERTELECTRIC18 ай бұрын
Thanks Lot. You make over complicated Code book very simple understandable. God Bless You.
@herbertvela9545 Жыл бұрын
I love the way you teach you really helping me out in my school. Thank you so much.
@altuber99_athlete Жыл бұрын
As your photo clearly showed, I think the NEC should address conduit fill for large gauge wires and/or large diameter conduit with small gauge wires. For example, 54 #10-AWG THW wires in a 2” EMT, or 10 #2-AWG THW wires in a 2” EMT, are both crazy (hard to work with and to do maintenance or inspection) yet it’s code compliant.
@ElectricalTime Жыл бұрын
Hi Ryan, excellent video on Raceway / Conduit Fill, look forward to Part II of this series, thanks, Steve K
@John-l3x2j7 ай бұрын
Great video! Thank you for making these incredible videos and sharing your knowledge!
@ScipioAndycanus Жыл бұрын
Great stuff, Ryan. Thank you, sir.
@SelinaAl-Shaer3 ай бұрын
There are cables and cords that are listed in table 400.4 and communication cables in table 800.154(a) that we don't have total area for.
@RyanJacksonElectrical3 ай бұрын
@@SelinaAl-Shaer Agreed. We have to get the actual dimensions from the manufacturer for those instances.
@ErnieLA-4 ай бұрын
This Guy is Great 👍
@matthewb1601 Жыл бұрын
I learned things because of this video. Thank you!
@OhmMyGod18 ай бұрын
Excellent discussion, and a very thorough analysis Ryan. However, as pertaining to the NM cable calculations at 36:17 I believe if you had two 12-2 cables you would be limited to 31% of the Cross -Sectional area not 40% of the conduit per Chapter 9 table 1.
@rubenmartinez2437 ай бұрын
I was about to ask they same.
@pld89936 ай бұрын
Correct.
@chadgerman746711 ай бұрын
awesome video my friend!!!! the King of tehcode
@allegreUno11 ай бұрын
Thank you. Appreciate your hard work.
@yvonneagundez19949 ай бұрын
Enjoy the talk . With 24" raceway 60% fill, do you got to factor derate rule. And up size wires.?
@RyanJacksonElectrical9 ай бұрын
You do not need to apply ampacity adjustments for raceways shorter than 24".
@citygirljace Жыл бұрын
19:47 - Just what someone with the “Steel Tube Institute” would say 👀
@RyanJacksonElectrical Жыл бұрын
Of course! LOL
@Kevin-dp5hvАй бұрын
Excellent explanations
@dan9372 Жыл бұрын
Would a micrometer be an acceptable calculation method?
@RyanJacksonElectrical Жыл бұрын
I would think so.
@Steveeg12311 ай бұрын
Ryan....doesn't the .8 rule allow 2 12/2 in a ¾ emt?