Severely Oil Logged TXV Takes OUT Compressor!

  Рет қаралды 2,562

Jeff’s HVAC Adventures

Jeff’s HVAC Adventures

29 күн бұрын

In this video we replace the compressor, TXV, and Filter drier on a carrier central AC system after a severe oil wash out situation!
Check out these great tools I use on a daily basis! Use the links…SAVE SOME CASH!
TOPTES Combustible Gas Leak Detectors.
4 TO CHOSE FROM!
PT210S
amzn.to/3QSHJEu
Discount Code: GSYQFS4Z
PT299
amzn.to/3R38JlS
Discount Code: 4A3HH88Q
PT199
amzn.to/3M5kTYs
10% off with code: N83SX3Q6
PT520B+ Professional Gas Leak Detector amzn.to/494fISD
10% off with code: R98D8JH8
TOPTES CT-300 CO Detector: amzn.to/499s23E
Discount Code: 953OHRKL
Get yourself a HIK Micro B20 Thermal Imaging Camera. Use this Link!
amzn.to/3KwRw0m
Inficon Gas-Mate Combustible Gas Leak Detector amzn.to/40ifEdL
Tesman TN-213 NCV Tester amzn.to/3rVZY3j
10% off with code: FJDYR4W3
Topdon Thermal Camera for Android amzn.to/46Wldkf
Topdon Thermal Camera for iPhone amzn.to/46Twvpu
WisePro Tradesman Backpack:
amzn.to/4912DYW
WisePro 1000v Insulated Screwdriver set: amzn.to/43nBUV6
If there are any other tools and products I use in my videos that interest you…just ask! I’ll get you a link!
Support the Channel with a Super Thanks or
PayPal: ​⁠@JeffsHVACAdventures
CashApp: $JeffsHVACAdventures
Venmo: @JeffsHVACAdventures
Like and Subscribe!
Questions, comments or to just say Hi, email me
jeffshvacadventures@gmail.com

Пікірлер: 34
@TomLawson05
@TomLawson05 26 күн бұрын
As always Jeff good job getting the costumer up and going
@JeffsHVACAdventures
@JeffsHVACAdventures 25 күн бұрын
Thanks brother
@bohanger6315
@bohanger6315 25 күн бұрын
My coworker had that on the fieldpiece pump and ended up having to send it in for the power board to be replaced. Happened again and they sent him a new one. He had to threaten to never buy another product since it was costing him time on jobs. So far so good on that one I think.
@JeffsHVACAdventures
@JeffsHVACAdventures 25 күн бұрын
Glad he got it straightened out.
@MariosACandRefrigeration
@MariosACandRefrigeration 27 күн бұрын
nice video,Check for oil traps on the line set in the attic.
@JeffsHVACAdventures
@JeffsHVACAdventures 27 күн бұрын
Good idea.
@zekenzy6486
@zekenzy6486 27 күн бұрын
Great video. Thank you for sharing
@hahapinktaco
@hahapinktaco 14 күн бұрын
i have the same field piece pump - it trips most all gfis on startup
@JeffsHVACAdventures
@JeffsHVACAdventures 14 күн бұрын
Weird right…
@woodystokes1543
@woodystokes1543 25 күн бұрын
Great job 😊in the pickup
@JeffsHVACAdventures
@JeffsHVACAdventures 25 күн бұрын
Thanks brother
@lahoucinelamlih3214
@lahoucinelamlih3214 18 күн бұрын
You are a pro brother
@JeffsHVACAdventures
@JeffsHVACAdventures 17 күн бұрын
Thanks man.
@justinpisarski412
@justinpisarski412 27 күн бұрын
My fieldpiece pump trips them too and I've always wondered why. Great video and keep up the good work
@JeffsHVACAdventures
@JeffsHVACAdventures 27 күн бұрын
Certainly weird. Thanks
@christopherdelon3026
@christopherdelon3026 26 күн бұрын
I have to use a widow maker for my field piece pump. Just got used to it now after 1 yr of use
@llampallas66
@llampallas66 24 күн бұрын
My fieldpiece vacuum pump does the exact same thing with the GFCI
@Xiable
@Xiable 7 күн бұрын
It's the ramp up of the motor. Gfci react to increases in electrical draw that cause it to trip
@ccthepope
@ccthepope 27 күн бұрын
great video!
@JeffsHVACAdventures
@JeffsHVACAdventures 27 күн бұрын
Thanks
@Shawn_RHVAC
@Shawn_RHVAC 26 күн бұрын
Have the same issue with mine. Returned it for replacement
@JeffsHVACAdventures
@JeffsHVACAdventures 25 күн бұрын
I’ve had mine a couple years. Kinda just deal with it at this point
@gabrielstern4992
@gabrielstern4992 27 күн бұрын
Nice video Jeff for future reference In case you come across another one of those situations and need to flush the evaporator or linesets from a txv or compressor failure you may want to go to auto zone or advance auto and Pick up one or 2 cans of ac pro system flush then run the nitrogen but then you have to vac out the system for 40 minutes and ac pro does offer them I. Big gallon sizes too and you would just need a flushing gun too add solution to as I think it's a good idea as a precaution to flush the linesets out also before installing the new compressor and filter dryer as a precaution I know on cars if a compressor fails or an evaporator you always do a ac system flush. But with new cars you can't flush the new condensers you Just have to replace them but I can get replacements from spectra for around 100 dollars evaporators around the same slightly less And 4 seasons makes automotive compressors wish residenrial hvac had more of those options for older units. So those r 22 and older 410 a units can keep going as for your blueon video I need to do my research to see if it will work with poe oil as well and if it can work as a replacement for 410 a
@JeffsHVACAdventures
@JeffsHVACAdventures 27 күн бұрын
Good Advice.
@gabrielstern4992
@gabrielstern4992 27 күн бұрын
​@@JeffsHVACAdventuresjust did some research on the blueon stuff it looks like thats the one for a replacement for R 22 it does say it has lower pressures than r 22 to help preserve system components from your blueon video and that you can put more I. For a charge VS r 22 and that it reduces the power draw VS r 22. And here is what's messed up 15 years later they finally come up with a better refrigerent VS R 22 and better than 410 a that's not flammable and has a even lower gdp VS 410 a but the same crap that started with r 22 replacement refrigerents is now happening with 410a and Jeff I think part of the reason so many evap coils and condenser micro channels are going bad and all these system problems are is because of the higher pressures from the low and high side it's tougher on the compressors coils and txv valves VS the older systems so if their was a, way to just make blueon the standard and come up with switches to change for 410 a systems that would help along with the inverter technology. I have Been looking at the so called 410 a refrigerents replacements and the only one that shows promise to me is r466a but it is not available here yet and is not approved yet but has been tested in a trane rooftop unit that is intended for 410a. Butvthe question concerning blueon is can you use it with a, system for which the compressor was replaced with poe oil because from what I understand 407c is getting phazed out too. Anyway Jeff if you have older r 22 systems it's better to keep em going at this point and repair em and use blueon VS all this crap going on unless the system is totally dead it's best to keep em going.
@gabrielstern4992
@gabrielstern4992 27 күн бұрын
Just checked blueon is compatable with both poe and mineral oil so why the heck are they just not coming up with sensors that can be put on 410a systems to allow them to run optimally at lower pressures and that just be the refrigerant for both r 22 replacement and 410 a replacement. And then the American companies can kick butt again and stop the forcing of everything needing to be made in Japan or China.
@JeffsHVACAdventures
@JeffsHVACAdventures 27 күн бұрын
@gabrielstern4992 good stuff brother. Blueon says they are working on a 410a replacement for what it’s worth.
@gabrielstern4992
@gabrielstern4992 27 күн бұрын
​@@JeffsHVACAdventures I hope so it needs to have lower head pressures and work better than 410 it needs to be the equivalent of the r 22 replacement or better. The closest thing I have seen is r 466a that honeywell has been testing with trane but that's still not good enough and is getting a lot of push back and I gave looked at the r 454 b or whatever and I don't like it at all and I defenetely don't like r 32 by itself it's too flammable and too much risk even with sensors that supposedly shuts off the system but here's the problem what if someone accidentally sets a match off or something or an electric spark happens from a bad wire connection that could trigger an explosion like with propane or natural gas. Because that's what r 32 is. To a degree it has way more propane in it VS 410 a which does contain r 32 but it also has r 134 a which is what my car uses too.
@racegrubb2152
@racegrubb2152 23 күн бұрын
In what way did the compressor fail. Was it a short to ground, lost compression, won't start? Was it noisy and on the way out? I am assuming compressor was running and pumping because I don't know how a txv can be condemned if there is no compression or compressor doesn't run at all unless the bulb line is visually broken. A lot of oilt in that dang thing for sure. I have had few oil logged evaporator coils that jad to he replaced, could never get it all on a few
@JeffsHVACAdventures
@JeffsHVACAdventures 23 күн бұрын
The compressor was changed because we didn’t know how long it ran with no oil and in a vacuum with a clogged TXV
@racegrubb2152
@racegrubb2152 22 күн бұрын
@@JeffsHVACAdventures I got ya, so it was more of a recommendation to prevent future headache. Got ya. Thanks for the reply back
@Joshuatimmons1783
@Joshuatimmons1783 12 күн бұрын
I don’t know why Carrier switched to LG compressors you should have asked for a Copeland and paid extra for it for a better quality compressor and went away with LG LG should just stick to tv’s and stop making compressors and a suction line trap isn’t actually a bad thing on the evaporator since that happened it’s probably better to have one than to not have one on it
@chrissipple1018
@chrissipple1018 25 күн бұрын
It's not that your pump dislikes GFI's, the GFI's don't like your pump. Call Fieldpiece
@JeffsHVACAdventures
@JeffsHVACAdventures 25 күн бұрын
lol. Yea I was thinking that.
A Full Day Of HVAC Calls! | Condenser Motor | Breakers | No Heat And More!!
33:44
Jeff’s HVAC Adventures
Рет қаралды 2,4 М.
5 Calls, One Sunday!  THEY JUST KEPT COMING!
29:20
Jeff’s HVAC Adventures
Рет қаралды 3,4 М.
The child was abused by the clown#Short #Officer Rabbit #angel
00:55
兔子警官
Рет қаралды 14 МЛН
Alat Seru Penolong untuk Mimpi Indah Bayi!
00:31
Let's GLOW! Indonesian
Рет қаралды 8 МЛН
Can You Draw A PERFECTLY Dotted Line?
00:55
Stokes Twins
Рет қаралды 64 МЛН
Overheated Compressor
24:56
Nor-Cal Refrigeration & H.V.A.C
Рет қаралды 3,7 М.
Compressor Literally BUSTED APART!
20:55
Jeff’s HVAC Adventures
Рет қаралды 2,1 М.
FAILED Repair Turns Into Replacing Condenser Coil On 10 Ton York RTU!
20:47
Jeff’s HVAC Adventures
Рет қаралды 1,7 М.
Goodman A/C NOT COOLING!  More Than Just The Obvious!
14:47
Jeff’s HVAC Adventures
Рет қаралды 6 М.
Customer Says AC Is Making The Water Heater Leak!  Plus Other HVAC Calls!
15:56
Jeff’s HVAC Adventures
Рет қаралды 987
2 Bad Compressors In Weeks WHY? Freezer Down
29:40
HVACR Survival
Рет қаралды 13 М.
An Unusual No Cooling Call
22:56
HVAC GUY
Рет қаралды 138 М.
Helping Apprentice Diagnose a Heat Pump Condenser | HVAC
25:04