Taco Zone Valve Relay Control! Explained, Thermostat Wiring, Zone Valve Wiring, Circulator Control!

  Рет қаралды 141,697

AC Service Tech LLC

AC Service Tech LLC

8 жыл бұрын

This is how a Zone Control System for a Boiler Works, what the functions are, how to wire it, and what the signal voltages and relays do!
Tool List- www.amazon.com/shop/acservice...
Support- / acservicetech
Our Inverter Mini Split Resources:
Mini Split Book on Our Website- www.acservicetech.com/mini-sp...
Mini Split Paperback on Amazon- amzn.to/3ytHJSs
Mini Split Paperback on TruTech Tools- www.trutechtools.com/BooksGui...
Mini Split E-Book on Google- play.google.com/store/books/d...
Mini Split E-Book on Apple- books.apple.com/us/book/id644...
Our Single Speed and Two Speed Air Conditioning Resources:
My Paperback and E-Book: www.acservicetech.com/the-book
My Paperback: www.amazon.com/shop/acservice...
Read the book reviews on Amazon!
Check out our new Articles at www.acservicetech.com/articles
Support the Channel by purchasing tools through Tru Tech Tools!
Use this link www.trutechtools.com/?Aff=8
Save 8% at checkout using code "acservicetech"
Supervision is needed by a licensed HVAC Tech while doing this as Experience and Apprenticeship garners Wisdom and Safety.
All of the ACSERVICETECH Playlists- / @acservicetechchannel
If you want to support the ACSERVICETECH Channel and receive more HVAC content, check out www.Patreon.com/acservicetech
ACSERVICETECH is a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to Amazon.com.
You can enter Amazon through this amzn.to/2aenwTq
The above link happens to be the Gauge Set that I use in my refrigerant videos but you can search from there.
Here is a link to the Taco Zone Valve used in this video amzn.to/2cGktI1
Here is a link to the Taco 6 Zone Valve Control with Priority hot water amzn.to/2dGQ2Av
Here is a link to the UEI DL389 Multimeter used in the video amzn.to/2xAdaJf
Here is the link to the Fieldpiece SDMN6 Dual Pressure Testing Manometer with Pump-amzn.to/2jyK5Ka
Here is a link for the Supco Magnet Jumpers amzn.to/2gS4h6z
Here is a link to Refrigerant hoses with valves used in the videos amzn.to/2aBumVI
Here is the Link for the Yellow Jacket Refrigerant Manifold Gauge Set used in the videos amzn.to/2aenwTq
Here is a link to the Digital Refrigerant Scale used in the video
amzn.to/2b9oXYl
Here is a link to the Imperial 535-C Kwik Charge Vaporizer for Charging Refrigerant- amzn.to/2oge0u9
Here is a link to the thermostat 3/32 screwdriver -- amzn.to/2hxt7uK
Here is a link to the C&D core removal tool amzn.to/2bFpobQ
Here is a link to the JB 6 CFM Vacuum Pump amzn.to/2nqbvo8
Here is a link to the JB Platinum 5 CFM Vacuum Pump with Valve
amzn.to/2mGKcSh
Here is a link to 1 gallon of JB Vacuum Pump Oil amzn.to/2mGrlXy
Here is a link to the Supco Vacuum Micron Gauge amzn.to/2bH98bO
Here is a link to the 1/4" by 1/4" female coupler from Supco - amzn.to/2kFrbU9
Here is a link to the Hilmor 4 port Aluminum Manifold Gauge Set-
amzn.to/2m4QLik
Here is a link to the Supco core removal tool amzn.to/2brEJco
Here is a link the Nitrogen Regulator amzn.to/2bXdR5f
Here is a link to the Nitrogen Flow Meter amzn.to/2brvoBg
Here is a link to the General Tools digital Psychrometer
amzn.to/2cSHsi1
Here is a link to the Amprobe Digital Psychrometer amzn.to/2d7cGkW
Here is a link to the Fieldpiece SDP2 Digital Psychrometer- amzn.to/2nniMVR
Here is the UEI Digital Manometer used in the videos amzn.to/2c1XkiT
Here is the link for the Ratcheting Service Wrench amzn.to/2dGV4Nh
Here is a link to the Appion G5 Twin Recovery Pump amzn.to/2dGSEyr
Here is a link for RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn
Here is a link to the air acetylene torch setup- amzn.to/2aQalsb
Here is a link to the Malco Snap Lock Punch amzn.to/2cY53Ag
Here is a link to the Wiss 3 Pack Tin Snips amzn.to/2bHWhWO
Here is a link to the Wiss 5 Blade Crimper amzn.to/2bwTlsW
Here is a link to the Wiss Hand Seamers amzn.to/2dRk83v
Here is the link for the Hitachi Lithium Ion Drill and Flashlight kit amzn.to/2dzNgkL
Here is the link for the Irwin Wire Stripper/Cutter/Crimper amzn.to/2dGTj2V
Here is the link for the Hilmor 12" folding tool amzn.to/2d9VTPR
Here is the link for the Malco 3" Blade Combination Snips amzn.to/2dz7Ejc
Thank You,
ACSERVICETECH

Пікірлер: 75
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Our Inverter Mini Split Resources: Mini Split Book on Our Website- www.acservicetech.com/mini-split-book Mini Split Paperback on Amazon- amzn.to/3ytHJSs Mini Split Paperback on TruTech Tools- www.trutechtools.com/BooksGuides?aff=8 Mini Split E-Book on Google- play.google.com/store/books/details?id=HN-iEAAAQBAJ Mini Split E-Book on Apple- books.apple.com/us/book/id6445178399 Our Single Speed and Two Speed Air Conditioning Resources: My Paperback and E-Book: www.acservicetech.com/the-book My Paperback: www.amazon.com/shop/acservicetech Read the book reviews on Amazon! Check out our new Articles at www.acservicetech.com/articles Support the Channel by purchasing tools through Tru Tech Tools! Use this link www.trutechtools.com/?Aff=8 Save 8% at checkout using code "acservicetech" Tool List- www.amazon.com/shop/acservicetech Support- www.patreon.com/acservicetech For those that are looking for the tools used in the videos: (Linked Below) Here is a link to the Taco Zone Valve used in this video amzn.to/2cGktI1 Here is a link to the Taco 6 Zone Valve Control with Priority hot water amzn.to/2dGQ2Av Here is a link to the UEI DL389 Multimeter used in the videos- amzn.to/2av8s3q Here is the link to the Fieldpiece SDMN6 Dual Pressure Testing Manometer with Pump-amzn.to/2jyK5Ka Here is a link for the Supco Magnet Jumpers amzn.to/2gS4h6z Here is the link for the Irwin Wire Stripper/Cutter/Crimper amzn.to/2dGTj2V Other tool links can be found in the video description section. ACSERVICETECH is a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to Amazon.com.
@JavierGarciajaviercobito
@JavierGarciajaviercobito 4 жыл бұрын
God bless you my friend for teach us I really appreciate it your time
@ziaulhassan8171
@ziaulhassan8171 6 жыл бұрын
dear sir your way of teching is outstanding thank you so much
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks Zia!
@johngnipper1454
@johngnipper1454 4 жыл бұрын
Nicely done, great tutorial
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thanks John!
@fb1313
@fb1313 3 жыл бұрын
Thanks for the helpful video. I have an SR504, which looks similar to the one in the video, but mine keeps ticking quite often lately and am wondering why and where it can be coming from since this just looks like a circuit board? it ticks when none of my 3 zones are calling for heat.
@jimbola77
@jimbola77 8 жыл бұрын
sweet nice explanation!!!!
@acservicetechchannel
@acservicetechchannel 8 жыл бұрын
Thank you!
@georgeEPC
@georgeEPC 5 жыл бұрын
By the way great info as always
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks
@FrostyMaine
@FrostyMaine 3 жыл бұрын
Disclaimer: I am not a licensed electrician or boiler technician but, I simply hope this helps. If using Aquastat to control boiler temperature (typically back of the boiler) with the new Taco 406-4, you will need to take the white wire of the burner and the white wire of the aquastat and tie them together with a wire nut. Then, put the red of the burner into one side of the ISOLATED END SWITCH and the red of the Aquastat into the other side of the ISOLATED END SWITCH. This allows the aquastat to disable the burner if furnace is at temperature or, if not at temperature, fire the burner.
@bnappi22
@bnappi22 2 жыл бұрын
Very helpful video as I needed this today. I have an indirect water heater with the priority switch on, and notice thermostats lights not calling for heat when the were. I turned off the priority switch and all of a sudden my other 4 zones starting calling for heat. Can you please help me understand why this can happen? Bad ZCS? I tried jumping the zones but the only way to get it to work is by turning off the priority switch. TY
@acturus1697
@acturus1697 Жыл бұрын
Thank you so much for this video! How do you wire a double pole zone valve actuator? I'm stuck on a double pole sharkbite zone valve actuator that I just can't get instructions on how to wire it to a taco zone valve relay control. I understand the difference is that it has the ability for an offsetting on the thermostat. I'm about to give up on that option and return them and go with the taco. They cost more but it will work. Thanks again!
@jimmyung3212
@jimmyung3212 7 жыл бұрын
Nice!!!
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Thanks again!
@rico1074
@rico1074 Жыл бұрын
Can you please tell me it this taco controller works with white rogers 3 wire zone valve? Thanks
@jackhammond23
@jackhammond23 2 жыл бұрын
Dealing with a 25 year old radiant floor heating system. The board is wired for two separate zones: Zone 4 and Zone 3. Zone 4 works perfectly, but though Zone 3 receives the signal from the thermostat, it does not appear that the signal moves across the board and out to the valve. Could it be the board is damaged? Can I move the zone 3 connection to zone 2 without issue?
@drdr140
@drdr140 2 жыл бұрын
What about when 2 of the zone valves are on a separate circulator pump?
@vincentcarroll2142
@vincentcarroll2142 6 жыл бұрын
thanks for the info. Question... on the taco 3 wire zone valve (as shown in your video). When 2 and 3 connect to trigger the circulator , is that when the Isolated end switch triggers the boiler ?
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
It closes the end pump switch on the bottom left on this zone control board. It is where the 120v black input comes in and the other black wire will be the hot for the circulator. Using a control like this, the boiler would already be up to temp and ready, thanks
@JCC1256
@JCC1256 5 жыл бұрын
How can I wire a buffer tank that has a 4006 Aqua. That is powered by end switch. The aqua then decides to power the buffer circulator or fire gas boiler.
@hobson3724
@hobson3724 2 жыл бұрын
what about the high and low limit switch and the 24v ac to the combination gas valve?
@Forge5894
@Forge5894 7 жыл бұрын
I enjoyed watching your video thank you for posting it!
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Glad to hear you enjoyed the video, thanks!
@ncooty
@ncooty 5 ай бұрын
I was hoping you'd show how you deal with the common wires from both the A/C air handler and the hydronic system. They're likely on different circuits, but, whereas there are separate 24V hots, there's only one C terminal per thermostat. If you wire the Cs together, then you could have a shock hazard with one circuit off and the other on. Alternatively, you could use the C from just one of the systems, but then the thermostats would run only with that circuit on.
@hankespinosa9474
@hankespinosa9474 4 жыл бұрын
What’s the benefit of having this v wiring the zone valves directly with the transformer and boiler?
@jeffschoen4009
@jeffschoen4009 2 жыл бұрын
Does this zone value just control 1 circulator pump or multiple pumps?
@jamescecil4629
@jamescecil4629 2 жыл бұрын
So on my hydronic board when zone one calls for heat It will fire off the zone one circulator but the end switch will also be able to fire off the primary circulator on my hydronic board that supply’s the heat to the primary loop…?….
@jrainmaker19
@jrainmaker19 7 жыл бұрын
Great explanation Jason. If you only had 2 wire actuators and you jumped 3 and 4, does the pump still wait until the actuator is fully open or do you have to accommodate the flow of water another way until the actuator fully opens? Such as a differential bypass valve? Thank you
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Usually on the four wire units 3 and 4 will close when the valve is completely open. On the 3 wire valves 2 and 3 will close when the valve is completely open. Thanks
@jsanti1000
@jsanti1000 3 жыл бұрын
I wired a three zone Taco control panel and 3 taco zone valves. I accidentally mis-wire zone valve terminal 1 and 3 to the zone control on zone 1. Did it fry that zone control on the zone control board? I was exhausted and accidentally wired blue white red instead of red white blue. Now that zone refuses to open even after it was corrected. I tried another zone valve head and no difference, I can only imagine it is the board. Is it repairable? the other 2 zones are working fine.
@bbrewer609
@bbrewer609 4 жыл бұрын
I the Taco unit, just wired it up to a 2007 Burnham Series 2 gas boiler with 5 Zones. Problem is the safety train from the boiler is only tied into Zone 5 so when any other Zone except Zone 5 calls for heat the Zone valves will open but boiler safety checks do not get completed. The only way I can get Zones 1,2,3,4 to get heat is to also fire Zone 5 and the safety train varifies and boiler fires. I tried putting jumpers across all 5 valve modules on the Taco but no joy. Any ideas on how to get the boiler to fire when Zone 1,2,3,4 call for heat without Zone 5 calling for heat?
@slawek14
@slawek14 2 жыл бұрын
I have a question how to control and connect circulating pumps with zone valve relay controller
@QuangNguyen-lr4cm
@QuangNguyen-lr4cm 5 жыл бұрын
Thanks for the video! Is it possible to share one circulator pump across all zone valves? How would you wire the pump to support that?
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Yes you would. In this video of the control, the contacts close at the bottom left on any call for heat. It is called the end pump switch. Just put power to one side of the switch and the power coming out goes to the circulating pump, thanks
@georgeEPC
@georgeEPC 5 жыл бұрын
When the zone I’m calling for heat and the taco valve is open do terminals 2 & 3 have voltage or continuity??
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Without wires, they will have continuity when the valve is mechanically open, thanks!
@l.a.m7645
@l.a.m7645 3 жыл бұрын
Can you do a video on white Rogers zone valve
@Purp-yf7tp
@Purp-yf7tp 5 жыл бұрын
How do you connect a honey well aquastat. Upgraded to the taco 6 zone ( I have 5). Not sure what to do with the aquastat
@marklaux4637
@marklaux4637 2 жыл бұрын
That's exactly my question too.
@BelleRiverHeating
@BelleRiverHeating 2 жыл бұрын
Now how do I wire this to my honeywell aquastat relay to fire my burners?
@victornicasio5260
@victornicasio5260 7 жыл бұрын
I have a Taco SR506-4 6 zone switching relay and my dilemma is that I have one zone continuously running although the setting at the thermostat is at a low setting. Another zone functions as is required and another zone does not kick on at all. I can't figure out my problem. Can you help me?
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
You would have to check for voltage at numbers 1 and 2 at your taco zone valves and see if they have power when they are not supposed to and don't have power when they are supposed to. From there you work your way back to the switching relay. If you have the thermostat set higher than it is in the room then the r power would touch the signal wire W going back to the switching relay and you would have 24v power from 24v common to the w when read with a multimeter inside the switching relay. Thanks
@alittlebitofeverything5090
@alittlebitofeverything5090 6 жыл бұрын
Thank you for the explanation, it was easy to understand. What gauge and type of wire would you use to connect the zone valve to the switch relay. Also, what gauge and wire would you run from the relay to the circulator pump if it was a Taco 007? Thanks in advance.
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
control for zone valve is 18 gauge and circ pump is same as rated max amps for boiler. 20 amp-12 gauge, 15 amp-14 gauge
@alittlebitofeverything5090
@alittlebitofeverything5090 6 жыл бұрын
acservicetech Thank you for the quick response. Stranded copper wire for the zone valve is ok?
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Stranded would work but we typically use solid under the screw terminals, thanks
@alittlebitofeverything5090
@alittlebitofeverything5090 6 жыл бұрын
acservicetech Thanks!
@roberthernandez1985
@roberthernandez1985 2 жыл бұрын
Hey Craig doesn’t 3 and 4 need a jumper when using a 3 wire head?
@mramnauth0
@mramnauth0 8 ай бұрын
no I don't think so, only if it was two wire then jumper required
@seanjmichel
@seanjmichel 6 жыл бұрын
My heat started coming on at 6pm every day. It continues to stay on even after pulling the t-stat off the wall. The online tech said it was the switching relay (taco sr501), but I have my suspicions. What else could cause the relay to come on the past 3 days at 6pm?
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Are your thermostats programmable and is the hold button on instead of a program. Do you have wifi tstats and program sees you coming home?
@seanjmichel
@seanjmichel 6 жыл бұрын
Thermostat is a programmable honeywell, it is not wireless. We use it for ac and heat. Hold button is not on, thermostat is selected to off.
@fjskowron
@fjskowron 7 жыл бұрын
I had a Taco Zone Bad go bad, well, it worked but somehow #2 and #3 kept continuity so the boiler had a constant call for heat. The circulation pump would run all the time even though all four zone pumps on this system were closed it would just spin in place and hum. When the boiler Aquastat Relay sensed that the boiler internal temp was low it caused the boiler to kick back on and heat it back to the set boiler temp. This went on for months before it was noticed. Very inefficient but all still worked (sort of) so the homeowner never knew except they wanted to know why the boiler was always hot, even in Summer! Something to possibly look for, I never knew a Taco Zone Valve can malfunction in such a way.
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Oh man! Nice, well glad to hear you caught the problem. In this video I show the guts to the valve like you were saying in reference to the switch at the end of the video. ----kzbin.info/www/bejne/bnbWoppphct9sKdh-----Thanks for the comment!
@davesingh8085
@davesingh8085 3 жыл бұрын
how to connect honeywell L8141E to ZVC404-4 Zone Valve Control
@diogoleviske6554
@diogoleviske6554 3 жыл бұрын
my zone valve relay control only have H and N spots its done not have common wire spot. how can i install a wifi thermostat without it?
@LTVoyager
@LTVoyager 5 жыл бұрын
Since the t-stat is wired to the Taco controller, what sends the signal to the boiler to fire?
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
The boiler will typically keep itself at 180 or whatever the aquastat is set at by itself or it can be done through the end switch wire, thanks
@luiscardenas51
@luiscardenas51 7 жыл бұрын
i have argo arm switch relay for two zones.. i just found out that i need to install zone valve.. i bought honeywell v8043. the zone valve has 2 red and 2 yellow wires... can i some one help me... conecting the zone valve and the argo switch relay
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
On the zone valve the yellow wires power the motor and the red wires close when the zone valve is fully open so water can flow through but switching relays such as ARM2P are normally for when you zone off a system with multiple circulator pumps and not zone valves. s3.supplyhouse.com/product_files/ARM2P-install.pdf
@chuckAWD
@chuckAWD 7 жыл бұрын
Probably a silly question but how does a thermostat know when to turn the system off ie: how does it know it's reached the set temperature? is there an inline temperature sensor on a hydronic system or something else?
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Great Question! When the thermostat on the wall for that zone reaches temp, it stops the 24v signal to the control board which in this case is the taco zone control system. Then the zone controller will shut that zone valve off and if there are no other zones calling for heat, it will shuit off the circulating pump. Here is a playlist of thermostat videos and what each of the wire colors and terminals do. Thanks------- kzbin.info/aero/PLxnHR5_D2ojzDfU1IjPpzdhi_mUGe3F7W
@chuckAWD
@chuckAWD 7 жыл бұрын
Thanks a bunch! The temperature sensor is in the physical thermostat itself the and when it sees that it's reached the desired temperature in a give room, it shuts off which, in turn, sets things in motion with the Taco ZVC. I have been racking my brain for days trying to figure that out. Thank you kindly.
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Exactly, glad to help!
@jasonfrv
@jasonfrv 8 жыл бұрын
Can u let me know the part number of this product thanks
@knighthvac4876
@knighthvac4876 8 жыл бұрын
Taco zvc 406
@mikepelletier1399
@mikepelletier1399 7 жыл бұрын
those 2 transformers do not have the VAs to run 6 of those zone valves at .9A ea
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
You are right, one would have to use lower draw zone valves. Those sentries are nice! Thanks putting the note there Mike Pelletier!
@hughjazzole2037
@hughjazzole2037 Жыл бұрын
Sr503 not working
@ziaulhassan8171
@ziaulhassan8171 6 жыл бұрын
dear sir please tech us auto car AC wiring diagram thank you much
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
I just do residential commercial building units, thanks
@ricardopinedo2337
@ricardopinedo2337 6 жыл бұрын
"
@Purp-yf7tp
@Purp-yf7tp 5 жыл бұрын
How do you connect a honeywell aquastat?
Testing, Wiring, Taco Sentry Zone Valve! How it Works, Comparison, Explained!
10:56
Thermostat Wiring at Control Boards
14:53
Jersey Mike HVAC
Рет қаралды 52 М.
Final muy increíble 😱
00:46
Juan De Dios Pantoja 2
Рет қаралды 52 МЛН
버블티로 체감되는 요즘 물가
00:16
진영민yeongmin
Рет қаралды 113 МЛН
Smart Sigma Kid #funny #sigma #comedy
00:25
CRAZY GREAPA
Рет қаралды 17 МЛН
Crucial Knowledge To Heat Pump Troubleshooting
14:15
Jersey Mike HVAC
Рет қаралды 19 М.
TACO 6 ZONE CIRCULATOR RELAY INSTALLED
22:13
steven lavimoniere
Рет қаралды 15 М.
Thermostat Wiring Explained!
10:35
Benjamin Sahlstrom
Рет қаралды 955 М.
NO HEAT. SERVICE CALL # 5  3 WIRE TACO VALVE FAILED. TROUBLESHOOTING
7:55
Alex The Handyman
Рет қаралды 10 М.
Pre-Built Combi Boiler System with  VT2218 and Zone valves
12:16
Jim Speranza
Рет қаралды 29 М.
Hydrotherm Gas Boiler No Heat Bad Zone Switching Relay Replaced Taco SR501 Installed
15:12
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 14 М.
How To Wire a System Circulator to a Taco Zone Valve Control (ZVC)
12:24
Taco Comfort Solutions
Рет қаралды 297 М.
WHY CAPACITORS FAIL in Air Conditioners! Watch it Break!
9:45
AC Service Tech LLC
Рет қаралды 1,4 МЛН
Final muy increíble 😱
00:46
Juan De Dios Pantoja 2
Рет қаралды 52 МЛН