Rinnai RL series interior and exterior fan removal and replacement.

  Рет қаралды 5,079

That Tankless Guy

That Tankless Guy

Күн бұрын

Пікірлер: 33
@cturtle97
@cturtle97 9 ай бұрын
Thank you. I had replaced burner rods and igniter and still did not clear the code 11. Took the fan out and spun it a bit. No debris or obstructions. Unit is working again. I had already cleaned the burner, orifices and previous flame rods to no avail. Wife and kids think I’m a hero now.
@scottseideman5384
@scottseideman5384 Жыл бұрын
Thanks Mike, you saved the day today! Texas has geikos, too. Two in the fan and it sounded like a bass guitar with a big amp! When I opened it up this morning and saw all those wires with the fan buried underneath, I closed it right up. Took maybe 15 minutes to fix after seeing your high quality video. Thanks again!
@davehunkele
@davehunkele 6 ай бұрын
Thank you -- had a code 10 on an RL75 interior unit and had the problem of hot water running cold after a few minutes. Cleaned out blower that was full of dead stuff. Saw a bit of debris in the exhaust line as well and cleared it. I couldn't figure out how to disconnect the blower, but was able to clean it out without disconnecting (with power off). So far, hot showers. A local plumber wanted $850 to clean the unit with no guarantee it would solve the problem or $4200 for a new unit. I had descaled a few times and cleaned out the water filter, but the blower cleanup seems like it's solved the problem. THANK YOU!
@bill2penn
@bill2penn 3 жыл бұрын
Thanks a lot for this video. I cleaned out my fan which had stopped because of debris and now it works again. You saved me a service call.
@ThatTanklessGuy
@ThatTanklessGuy 3 жыл бұрын
Glad I could help
@MARKE911
@MARKE911 4 жыл бұрын
Thank you for making these videos
@TheBuddylab
@TheBuddylab 4 жыл бұрын
Your very welcome
@ryanwalters9412
@ryanwalters9412 Жыл бұрын
This is great Mike. I wish I had found it sooner! I watched someone do it once and have since cleaned mine out 20+ times (lots of trees covering, in Central Texas, and thus lots of roaches getting into the unit). I'm amazed at how little of an obstruction causes faults. I have a new fan assembly that I'm going to put in this weekend, as it's clean now but still throwing code 10's. I've had the cover off for a bit to try to get better airflow, and it seemed to help for a while. I think that motor just might be tired after the obstructions and crud around the blower fan, which I have thoroughly brushed, but the additional friction might have taken its toll.. Also want to mention- I have no idea what I'm talking about and just cowboying this thing into working with a wire brush. Biggest reason for the new $90 blower assembly besides the motor potentially crapping out is the screw holes are no longer biting from my repeated use of them- have been performing this procedure regularly for years now and I'd imagine they're not meant for that.
@ryanwalters9412
@ryanwalters9412 Жыл бұрын
FWIW, the time I 'watched someone do it' was a plumber I paid $180 to do this process, not long after it was installed.
@bradhall4125
@bradhall4125 3 жыл бұрын
Thanks for the video! Helped me clean the moths out of the fan super quick.I can now sleep in later because the closet is right next to my master bedroom and holy hell was it loud.
@555mouser
@555mouser 3 жыл бұрын
Quality video. Great help and great job on the description. Big thanks from up here in Canada.
@ThatTanklessGuy
@ThatTanklessGuy 3 жыл бұрын
Glad it helped
@tomrippeto122
@tomrippeto122 2 жыл бұрын
This video was an absolute lifesaver. Thank you for posting it. God bless.
@sarfaraz572
@sarfaraz572 2 жыл бұрын
thank you sir, this video helped me today
@michaelmurray7874
@michaelmurray7874 4 жыл бұрын
Mike great video as always keep up the great work on both channels. Congratulations on your new video gear it makes a big difference. Happy Thanksgiving to your family.
@robhinkle3681
@robhinkle3681 2 жыл бұрын
Much thanks, Mike! You saved me a service call!
@markharrison5712
@markharrison5712 2 жыл бұрын
thank u ! I was going out to the shed to get the plasma cuter .
@ryanwalters9412
@ryanwalters9412 Жыл бұрын
Got my assembly swapped today. MAN that fan box (the part the fan and motor came out of in this video) is tough to get out. Is only 4 screws but they're in tough spots. If anyone's going down that road, I suggest putting the screws in on the 'tab' side first when putting in the new one, as it's next to impossible without a second set of hands to get the fan box lined up for the screws going into the burner housing if you don't. I ended up having a small, more flexible extension attached to a beefier extension on my impact driver, manipulating the head with a hook and fingers back through the weeds of the harnesses and pipes. Am not an expert, and there could be a less painful way! EDIT: repeat code 10's, have roaches getting into the blower unit. Thinking blower motor is shot so I ordered a new unit. Shot some air into the burner unit when I had the fan box off and vacuumed, through the fan hole, repeating a few times and definitely got some crud. Probably will have to pull the burner one of these days. Am hesitant as it looks like they can be tough to get free, but will give it a whirl if I need to now that I've found this channel.
@remichal
@remichal Жыл бұрын
I have a Rinnai E110EN combi boiler that's about 10 years old. It's started making a loud squeal (like loud brakes) on startup. It lasts about 2 to 3 seconds and goes away. The unit works fine other than that. I'm in Maine, BTW
@stevengambrell2199
@stevengambrell2199 Жыл бұрын
Do you have a video on the rur160ip fan replacement? I'm told it's a 15 min fix. Got 1 to put on next week. Thanks
@beachesaerialphotography2550
@beachesaerialphotography2550 11 күн бұрын
Thanks for the video, sure enough it was a gecko in there throwing mine out of balance
@bunlerssak
@bunlerssak 4 жыл бұрын
Hi Mike: my Rinnai RL75iP has the problem as you described on your video which is very helpful, it's 12 years old now. What if I want or have the professional replace the V65iP model which has the lower price. Is it as simple as remove the old RL and replace with V65 with the same piping and connectors.. Thank you
@TheBuddylab
@TheBuddylab 4 жыл бұрын
With the V6.5 you need to buy a valve kit I would not recommend using the old valve kit. So the price difference is only about $150.00 plus the RL7.5 is a better unit. There would be some piping you would have to do and changing the vent but it not that hard. Mike
@chrislambiase4640
@chrislambiase4640 11 ай бұрын
Hi Mike great videos they always help me maintain my R75-LSi . I'm having a difficult time finding replacement fan they say it's discontinued I have been given options but the connecter is different. Mine is the 4 pin that plugs directly to motor housing no harness. All I see is harness ones. Any help would be appreciated. Keep posting great content.
@uscfsu2008
@uscfsu2008 2 ай бұрын
When replacing the fan on a internal unit do I need to turn the gas off as well as unpluggin the power? Thanks!
@Jeff_Engineer
@Jeff_Engineer 2 жыл бұрын
Our tankless is mounted to the garage side of our guest bedroom wall and it's really loud inside the bedroom. Seems the fan is louder than it ought to be. I just had it out to address the moths + dust + code 10 error and the fan had a tiny clip on one vane. It looked like they put it there for balancing the cage so I left it. I'm just wondering if there's a better quality fan I could put in there that's not so loud. I'm sure I could pull the unit off the wall and mount it on vibration dampers, but that's a lot of plumbing and these things are supposed to be quiet.
@victorlopez7096
@victorlopez7096 4 жыл бұрын
Thanks god bless you very helpful
@juliocesaranez3853
@juliocesaranez3853 Ай бұрын
Mr Mike , I used your video a few years ago to fix my water heater, I found 7 dead little lizards I cleaned it, vacuum it and it worked. Now the have the same problem but this time I found one lizard cleaned it put it back together and still doesn’t work the water heater doesn’t make sound like it usually does I felt like the fan was not spinning . So I took the fan out again but this time while the fan was out I connected all the wires to see if it spins and it does spins so I put it back on and still doesn’t work while it’s fully mounted the fan doesn’t sound like it’s spinning while it’s mounted . Any advice ?
@gasman7558
@gasman7558 10 ай бұрын
Thanks Mike for this video! what if i DID NOT make a Reference Mark? i took mine apart and now i have issues with hot/cold water at the shower no codes. But the fan is the only thing i toched.Thank you very much for your HELP
@George_us
@George_us 4 жыл бұрын
Hey, Are you in Saint Augustine, FL? I want to install a Rinnai myself but I don't know if St John's allows a home owner to do it himself. I will find out on Monday, if they would give me a permit. Anyway, I could always use your help. Thanks...
@YumboYack2521
@YumboYack2521 2 жыл бұрын
I hate these models, if you have to replace the blower housing it’s a nightmare since the there’s two screws that screw in from the side left, only 2 inches of room. The bottom right screws are just as bad as you have to access them from 6 o clock with the copper pipes in the way. Thank you for these informative videos.
@lawrenceisrael7418
@lawrenceisrael7418 9 ай бұрын
Thanks guy
Removal and cleaning of Rinnai's water flow turbine
23:18
That Tankless Guy
Рет қаралды 59 М.
Code 11 on a Rinnai RL series unit
29:32
That Tankless Guy
Рет қаралды 75 М.
Beat Ronaldo, Win $1,000,000
22:45
MrBeast
Рет қаралды 158 МЛН
Сестра обхитрила!
00:17
Victoria Portfolio
Рет қаралды 958 М.
Мен атып көрмегенмін ! | Qalam | 5 серия
25:41
Правильный подход к детям
00:18
Beatrise
Рет қаралды 11 МЛН
S3:E04 - Rinnai R94LSi Fan Replacement
6:04
Get To It!
Рет қаралды 16 М.
Proper venting of a Rinnai RUR series unit.
19:20
That Tankless Guy
Рет қаралды 39 М.
TANKLESS WATER HEATER. Replacing a Rinnai heat exchanger
10:54
Sick Kids Entertainment
Рет қаралды 3,5 М.
How to fix a humming sound in your tankless water heater//Maintenance Part 1
14:52
Code 12 on a Rinnai tankless checking the flame rods
8:02
That Tankless Guy
Рет қаралды 164 М.
MC91 2 Controller Instructional Use Video
9:43
Rinnai America Corporation
Рет қаралды 181 М.
BLOCKED Heat Exchanger On Rinnai Tankless Water Heater!  Cleaned And Flushed!
18:33
Jeff’s HVAC Adventures
Рет қаралды 5 М.
Beat Ronaldo, Win $1,000,000
22:45
MrBeast
Рет қаралды 158 МЛН