This Honeywell Home room stat must be the most installed ever, why in the UK we get it wrong?

  Рет қаралды 14,685

Mr Combi

Mr Combi

Жыл бұрын

This Honeywell Home room stat must be the most installed ever, why in the UK we get it so wrong? Often no earth or separate neutral as required, even worse fitted and specified in a COLD hall?? Contrary to the instructions and drawing.
The best way to fix this rubbish and expensive installation is RF (Radio Frequency) a simple 4 wire receiver and ‘walk-about’ table top stat.
No internet or APP required. Low cost and easy to upgrade, saves money.
Even better go WiFI via an APP the lowest running cost are always boiler manufactures own controls, next “Smart controls” from Danfoss, Drayton, Honeywell Home, then Nest & Hive.
Remember the older the 230vAC analog stat is the higher the over shoot which is a waste of MONEY. Our APPs and orange book has diagrams in colour and are easy to follow
Watch the video to the end for extra tips then link to www.mrcombi.com to
Order both books + CO2 chart order value £45.00 no vat
For more info: please use the link below
Our APPs are all one price £4.99 no vat
www.mrcombi.com/apps/
Apple iOS download: apps.apple.com/gb/developer/m...
Google Play download: play.google.com/store/search?...
BOOKS: www.mrcombi.com/shop/
KZbin Videos: www.youtube.com/@mrcombiBedfo...
Music: Friendly Dance - Nico Staf

Пікірлер: 59
@andrewcannon3195
@andrewcannon3195 3 ай бұрын
We're quite happy with our thermostat in the hall, when we're active during the day we use it to switch the heating on and off depending what we're doing, it would be a nuisance having to go into the sitting room (and we'd have to take outdoor shoes off). In the evening the hall thermostat sits at 12-13 and the living room is just right. If it gets too hot in the sitting room we go into the hall and turn it down. Can't see your problem with thermostats in halls really.
@mrcombiBedford
@mrcombiBedford 3 ай бұрын
Dear Andrew, Thanks for the comment, as you see on the box, the firm calls it a ROOM stat, install instructions show a LOUNGE, not a hall. Please ask your installer why they ignored this and canceled your guarantee. As we sit in the lounge for 5 hours most of us want the stat there not in a cold hall. As you point out that 247 your system overheats and you over pay, most people find that expensive. Hope that helps, George Staszak. 👍😍
@andrewcannon3195
@andrewcannon3195 3 ай бұрын
Well it never overheats George as we have it set between 12 and 15, and it goes off overnight on the timer at nine pm until 8 am anyway, tbh our heating is hardly ever on ;) If we want the living room to be, say 18, we just set the thermostat in the hall to about 15, works fine. We have to go into the hall to go to the loo or whatever anyway so it's zero inconvenience to adjust it. If someone had put our stat in the living room I'd move it to the hall ;))
@mrcombiBedford
@mrcombiBedford 3 ай бұрын
I pass on the message from the controls firms, very glad you happy with your controls, take care, george @@andrewcannon3195
@Noaxe_Tegrinde
@Noaxe_Tegrinde Жыл бұрын
I've spent ages on my beloved KZbin looking for info on my faulty system so thanks again for a brilliantly produced video. You're very knowledgeable and good at presenting!👍
@mrcombiBedford
@mrcombiBedford Жыл бұрын
Hi Again, glad to help, regards, George Staszak👍
@mrcombiBedford
@mrcombiBedford 7 ай бұрын
Look out for a new Vid. about changing a ROOM stat in a hall to RF 👍
@richardclarke9966
@richardclarke9966 2 ай бұрын
"In my wife's house" 🤣. So true...
@mrcombiBedford
@mrcombiBedford 2 ай бұрын
Hi Richard, that's 2 of us, take care, George 🤩👍
@gasservenw1369
@gasservenw1369 Ай бұрын
Hi George. Just sidetracking slightly but I have a customer who upgraded their Landis & Gyr roomstat to an RF EPH stat but didn't want the old stat removed. The installer set the old stat to max and told them not to use it but use new RF stat. This is correct as far as I'm aware but I think they have been moving stat probably due to habit. So, going to link wires behind stat just wanted to confirm which ones to link out. Thanks
@mrcombiBedford
@mrcombiBedford Ай бұрын
Dear Gas NW, Thanks for asking, yes you are correct the old stat MUST be disconnected, I understand they don't want to remove the old one before decorating. Power OFF and remove the wires from the boiler end and make safe (don't cut them OFF, someone may want to reconnect them later). Hope that helps, George Staszak 🤩👍
@gasservenw1369
@gasservenw1369 Ай бұрын
@@mrcombiBedford Hi George. Many thanks for the information. Its an old heat only boiler so will I need to put a link back in on the boiler end so that the EPH twin channel programmer controls the switch live to the boiler? Thanks
@mrcombiBedford
@mrcombiBedford Ай бұрын
@@gasservenw1369 Glad to help, it's only the feed to the old stat that needs removing at the boiler end as you say.👍
@MarkJones-gt2qd
@MarkJones-gt2qd 5 ай бұрын
Funny enough, someone cut the blue wire on my thermostat, so it "works" with two wires, but I know the blue wire IS connected at the wiring box, and goes to neutral. I'm tempted to reconnect the blue wire by extending it, otherwise I wonder if the signal "floats" when the thermostat is off. I noticed because I was taking Mr Combis advice and changing it for a digital one. A tado, fwiw, which allows for each rad to have a individual temperature, AND call for heat. How cool is that. Mind you, at 70 quid a pop, it would need to be.
@mrcombiBedford
@mrcombiBedford 5 ай бұрын
Hi Mark, looks like the blue neutral was cut at the stat but not the wiring centre which you should do. Most Digital stats don't have neutral. I cannot afford £70 a stat, I will not live long enough for the payback. Like solar and air source you have to wait at least 12 years but that's when it needs to be replaced thus not many installs make any money. MPs give very good heating advice, there goes my knighthood.
@MarkJones-gt2qd
@MarkJones-gt2qd 5 ай бұрын
@@mrcombiBedford thanks for reply. I got them in a sale... Just a few. It's more of a gadget thing for me! Turning on the heating from my bed is quite appealing. My wife puts on the electric heater if she's cold. So the cost is high then! The bill is already epic.
@mrcombiBedford
@mrcombiBedford 5 ай бұрын
We have to accept the fact that women are always feeling colder than men, that's why they control the room stat, the good news is I will soon be making a video about bluetooth stats just for them and peace and love to your home. 🥰🤩 @@MarkJones-gt2qd
@GundamGir1
@GundamGir1 7 ай бұрын
My thermostat is sitting on the (outside) inside Hall wall right beside the front door. Theres hall stair n wee top landing. There's the front door the pvc door surround and then the thermostat sits againt the pvc surround. I said to them not to put it in the hall or against that wall, as it gets hit with rain n wind, and the hall us always cold. Council told me it's even better there keep everything nice n warm. No use having the thermostat as it doesn't matter what it's sitting at it doesn't turn the heating off n on, it's always on as the hall is always cold. I now just keep it off and hit advance.
@mrcombiBedford
@mrcombiBedford 7 ай бұрын
Dear Heather, thanks for asking, I sympathies with you, unfortunately you are not alone, I get the impression that these organisations do not employ staff that can read install instructions which is a shame. I am making a video about changing a rubbish room stat to RF (radio frequency ) which is very easy to do, no smart complicated APP needed. Your choice is disconnect (not remove) the stat, find a qualified person to fit RF or Smart. As per video the best is from the boiler firm next is Open Therm any boiler under 6 years, next from Danfoss Drayton or Resideo. Hope that helps. 😍👍
@1stevew
@1stevew Жыл бұрын
Are yes..... Happy wife = Happy life !!!! ....top video again.... thank you
@mrcombiBedford
@mrcombiBedford Жыл бұрын
Hi Steve, correct if Mrs Combi is happy I am really happy, take care, George😃
@anujitchatterjee1736
@anujitchatterjee1736 5 ай бұрын
In my new place I have an old Drayton thermostat unlike a digital one. Not sure what settings to put to optimise usage. Note 'timed' setting is there in boiler settings
@mrcombiBedford
@mrcombiBedford 5 ай бұрын
Dear Anujit, thanks for asking, room stats should be 18c over night or when you go out, when you are home 20 21 22c which is most comfortable for you. Please remember ALL stats will over shoot the target temp. set by 2 to 6 degrees to stop the boiler (hunting) going ON and OFF lots of times per hour which will damage and wear it out. Please find my VID how to test a stat. Hope that helps, George 👍
@availablerooms-wortingroad4587
@availablerooms-wortingroad4587 3 ай бұрын
Thanks for this helpful video but in the places (8 mins 35 seconds onwards) where you talk about the blue wire, we can't see the wiring mistake you are referring to in the video and the discussion about the blue wire is not clear. Could you please show the wiring of the old thermostat that has been done incorrectly and the new correct way for a digital thermostat. I have just installed a digital one(Siemens RDH100) and I used only the yellow and red cable because those were used in the old Honeywell I was replacing. The blue wire was already cut off but not sleeved or taped up. I replaced the Honeywell because I was suspicious that it was not turning the heating off in time. So potentially overshooting and strangely it was also not turning on the heating early enough either.
@mrcombiBedford
@mrcombiBedford 3 ай бұрын
Dear AR, thanks for asking, I have lots of drawings in other vids APPs and book, that shows what you are asking. The old 230vAC room stat has to have 3 wires, the neutral we don't need in digital stats so we make it safe and use the other two as they are Com and SW.L. Hope that helps, George 👍
@availablerooms-wortingroad4587
@availablerooms-wortingroad4587 26 күн бұрын
@@mrcombiBedford Thank you very much George. I managed to get the thermostat installed using the 2 wires. I am experiencing that under the stairs location problem though. Even in June, the temperature under the stairs is dropping to 18 degrees, causing the heating to turn on. I think I need to configure it for a 2 degree differential so that it only switches the heating on when there is a 2 degrees difference. Thanks again.
@mrcombiBedford
@mrcombiBedford 26 күн бұрын
Thanks for asking the blue wire is with the black wire that’s wrong All the blue wires should be together and never with others Hope that explains George
@stefanotattifrongia3612
@stefanotattifrongia3612 3 ай бұрын
Hello there, I have the same set up that you show with the Honeywell thermostat with the wheel and the ST9100C. I want to replace with a smart system, if I choose the Honeywell T6 Wired smart, I need to put the thermostat with the display instead of the one with the wheel and the receiver box instead of the ST9100C module correct? Thank you for your answer.
@mrcombiBedford
@mrcombiBedford 3 ай бұрын
Hi Stefano, thanks for asking, No the wheel is too old, replace with Drayton RF 902 2 channel about £117 from Toolstation, this will save you money and easy to use Take care, George Staszak, next week I will have a video on changing rubbish Combi controls system to to RF901 single channel, just what you need except one channel. 🤩👍
@karenteasdale7341
@karenteasdale7341 6 ай бұрын
Mine is in a garage in the coldest place. By the draughty up and over door. Comes on all the time in winter ..so high up i cant reach it.
@mrcombiBedford
@mrcombiBedford 6 ай бұрын
Dear Karen, Sounds like a FROST stat, there must be another somewhere in the house. Get someone to find it, if you want "Smart" on your phone that's very good, if you don't want that, ask for RF, that's one you can move the stat around the house and cheaper to buy. take care, George Staszak. 🤩👍
@jdk1515
@jdk1515 5 ай бұрын
Can i change the old one with a digital one without a boiler?
@mrcombiBedford
@mrcombiBedford 5 ай бұрын
Dear J DK, yes no problem, always take fotos of the old stat and where it's connected to, read the new instructions because may only need 2 wires, Com and SW.L replace the new digital stat and enjoy. 😍👍
@DragonXDrei
@DragonXDrei Ай бұрын
I wish you showed how to replace that old thermostat to the new o, and if we have to connect the same wiring, 2 live 1 neutral plus sensor.
@mrcombiBedford
@mrcombiBedford Ай бұрын
Dear Gixxer, thanks for asking, I cannot show you how to wire a digital stat because each firm has different terminals, you would not change to the same type, 2L +N, all digital. have COM and SW.Live same goes for Open Therm. some will be 230vAC or 24vDC or Volt Free it depends on the one you buy, as in other Vids. if your boiler has O.T. that's the lowest running cost after that VF then 24vDC avoid 230vAC. hope that explains. Our Wiring book and APP has more info. take care, George Staszak 👍
@Bari_Khan_CEng_CMarEng
@Bari_Khan_CEng_CMarEng 8 ай бұрын
The blue conductor has a yellow or black to indicate line or switched voltage - in a three wire setup? Can I kindly ask where this is stated in the regulations or any codes or is it actually even stated in UK version of boiler installation manuals? Cheers
@mrcombiBedford
@mrcombiBedford 8 ай бұрын
Hi Bari, thanks for asking, if a blue wire has voltage it MUST be sleeved to show current, must installers don't bother, these Codes of Practice are found in Building Control we get from either Viper or NICEIC publications, hope that helps, George Staszak 👍
@Bari_Khan_CEng_CMarEng
@Bari_Khan_CEng_CMarEng 8 ай бұрын
@@mrcombiBedford cheers for the update. I was under the impression the sleeving colours should ideally be BROWN to indicate that it is a Switched Live - but it can also be Yellow or Black to indicate switched live?
@mrcombiBedford
@mrcombiBedford 8 ай бұрын
You are correct any colour except Earth (yellow / green) is also not allowed @@Bari_Khan_CEng_CMarEng
@41jimmymac1
@41jimmymac1 8 ай бұрын
Can you tell me if the upgrade Honeywell digital thermostat you show to replace the old analog Honeywell thermostat if it will work on 3 wire setup ?? As in your vid l see 4wires from the old thermostat?? If so which way is it wired please or do l need a different Honeywell thermostat?? Mac
@mrcombiBedford
@mrcombiBedford 8 ай бұрын
Hi James, thanks for asking, all digital stats only need 2 wires, Com the wire from the programmer and SW.L switched live (combi) either to the CH Com or a motorised valve (white mid poz. or brown if zone) to move the motor. The old stat would have 4: E / N / Com / SW.L. Digital only need 2 as above, make safe the others. I am doing a video soon about Analog to RF which has a bit in this video. Honeywell now RESIDEO have just launched a new range buy that stat. Hope that helps, George staszak 😀👍
@scooby536
@scooby536 5 ай бұрын
Sure my analogue dial doesn't work I can wack it right up to 30 and doesn't feel one bit warmer located on my stairs front door at bottom
@mrcombiBedford
@mrcombiBedford 5 ай бұрын
Dear Sharon, thanks for comment, unfortunately you are not alone, specifiers know it's wrong but don't care. As my relpy to another video please hang on to see my Bluetooth control which will solve yours and many peoples problem, take care 😇👍
@manofweed1
@manofweed1 8 ай бұрын
Probably install in the hall because it's usually closest to the boiler in the kitchen ?
@mrcombiBedford
@mrcombiBedford 8 ай бұрын
I have met some of these installers, the answer is the ignorant boss told them, specifiers who can't read install instructions, sparkies who also don't read and some don't care about running cost and they can charge more (rip off) customers. Hope that explains.🤠👍
@Swwils
@Swwils Жыл бұрын
Because for whatever reason gas engineers / plumbers in the UK accept a certain culture and rather than lift each other up and improve, simply race to the bottom.
@mrcombiBedford
@mrcombiBedford Жыл бұрын
Dear Swills thanks for reply, it's sad to see so many hall installs, even had installers on my course openly said they did it wrong but would not change and fit smart because too much work. all the best, George
@bungler1000
@bungler1000 Жыл бұрын
I had an old Honeywell mechanical stat, located in living room, it only has 2 wires, Red which is live and a Black, the heating never switched off, so assumed the stat was faulty, replaced with a Drayton RTS8, because it states suitable for 2 wire set up, its still the same, never switches off, thermostat only switches heating off if i turn it manually. I currently have the Red (live) to L and Black to 3, as per wiring diagram supplied. Any advice appreciated. Can i connect a digital stat with the existing Red (live) and Black wire???
@mrcombiBedford
@mrcombiBedford Жыл бұрын
Dear B 1K, thanks for asking, The RTS8 is a very good choice the leaflet shows your RED goes to L and Black to 2. should work. Test the stat in 230vAC (programmer to ON) Turn stat to lowest temp10C?, put meter RED lead to L BLACK to 2 should be 0vAC. DANGER LIVE terminals!!! slowly turn up the stat until you get 230vAC or more, check the boiler has fired. return to stat leads back in then slowly turn down to 10C or until goes to zero AC. that's the way all 230vAC stats are tested. hope that helps, regards, George Staszak, 👍
@bungler1000
@bungler1000 Жыл бұрын
Hi George, thanks for quick reply, I will do the test later, but, I have the Black in 3, as the leaflet says, that's for most gas/wet heating systems, should it be in 2??, Would a digital stat be better for me? Really bugging me that the stat wont switch the heating on and off as it should, when room temp is reached. (other than turning it manually) Any advice much appreciated, Mark.
@mrcombiBedford
@mrcombiBedford Жыл бұрын
Hi again, It is a digital stat, no need to change, you look at the middle drawing, www.draytoncontrols.co.uk/sites/default/files/Combistat%20%28I.%20Guide%29.pdf George
@MarkTyrrell-nu6sh
@MarkTyrrell-nu6sh Жыл бұрын
Hi George the RTS8 I have is a mechanical stat, have done the test you suggested, programmer on, stat on 10, L & 2 show 240v, turn the stat up, boiler starts up, L & 2 then show 0v, very confused.
@mrcombiBedford
@mrcombiBedford Жыл бұрын
@@MarkTyrrell-nu6sh with the stat on10c should be 0vAC, you say when you turned it up the boiler fried up=OK what happened when you turned back to 10c did it go off? try swapping the wires as see, could be the BLACK in COM, try in 2 and 3 which works OK,
@johnward5006
@johnward5006 Жыл бұрын
I definitely disagree, there is no way my 70year old wife can control our heating more accurately than our programmable, opentherm stat! With regard to wiring in Honeywell type stats, the neutral connection is fundamental to it's accurate operation, as are the positioning in the MAIN sitting area, 1.5m above floor level, not the 1.2 some electricians insist on. Neutral connections are more common than not in wireless and or hardwired controls!
@mrcombiBedford
@mrcombiBedford Жыл бұрын
Hi John, thanks for your I agree with you, regards👍
@johnward5006
@johnward5006 Жыл бұрын
@@mrcombiBedford It's sad that too many installers don't make the effort to promote energy efficient anything! Maybe it's a money thing, but installers need to up their game and consumers have to take their share of responsibility and be prepared to pay a more realistic price for the RIGHT job!
@Noaxe_Tegrinde
@Noaxe_Tegrinde Жыл бұрын
@@johnward5006 It is a cost thing plus a competition thing (between tradesmen.....lower price and most customers don't know zilch so they think they're getting 'like for like' systems with different prices. Key thing is to put the roomstats out of reach of the womenfolk and hide the kitchen steps!! 😀😀
@craigsmith8495
@craigsmith8495 7 ай бұрын
😀😀😀😀😀😀👍although you are now in trouble with her indoors lol@@Noaxe_Tegrinde
@MarkJones-gt2qd
@MarkJones-gt2qd 5 ай бұрын
Interested to understand what the neutral does that is essential, since mine is disconnected. I suspect it leads to some vague behavioral problems from my mid valve honeywell. It has been like that for 20 years though.
БОЛЬШОЙ ПЕТУШОК #shorts
00:21
Паша Осадчий
Рет қаралды 8 МЛН
Vivaan  Tanya once again pranked Papa 🤣😇🤣
00:10
seema lamba
Рет қаралды 32 МЛН
RV Water Heater Maintenance & Mistakes Every RV Owner Should Know!
18:15
EnjoyTheJourney.Life
Рет қаралды 958 М.
How to wire a room stat
6:01
CP Utility Solutions
Рет қаралды 7 М.
Honeywell 9400C Programmer user video
10:42
AdvantageSW
Рет қаралды 186 М.
Honeywell 6000 Walkthough
8:15
Excellent Air Heating and Cooling
Рет қаралды 153 М.
My Smart Home is Stupid - HVAC Update
17:44
Linus Tech Tips
Рет қаралды 3,1 МЛН
Surprised 😳🤩🤩❤️🔥🥳
0:35
Okanutie
Рет қаралды 35 МЛН
ПРИДУМАЛИ НОВЫЙ МЕТОД ПРОВЕРКИ ТКАНИ
0:21
Как дешево😱  #рекомендации #юмор #новости
0:17
Шок Контент
Рет қаралды 3,2 МЛН
Tiny motor, big power
0:25
Rob Rides EMTB
Рет қаралды 15 МЛН
berenang lagi #viral #shorts
0:12
Kakek Endo Family
Рет қаралды 45 МЛН