Trane Chiller Centrifugal Refrigeration Cycle

  Рет қаралды 52,804

HVACTIME

HVACTIME

Күн бұрын

Пікірлер: 97
@HVACTIME
@HVACTIME 4 ай бұрын
chilleracademy.com/p/intro-to-chillers Get support today.
@millsdevan
@millsdevan 4 ай бұрын
I checked out your web site and I am very interested in it the intro to chillers, but I noticed a good portion remains under construction? How often do you plan on adding material?
@HVACTIME
@HVACTIME 4 ай бұрын
Awesome, would be great to have you a part of the community. Great question, I am adding a new lesson daily on average. At first I was trying to release full modules at a time but have found it much more consistent releasing daily. They will typically post before lunch except for Saturday.
@juliocastaneda2398
@juliocastaneda2398 2 жыл бұрын
I'm a chiller and boiler mechanic and I cant say I've ever heard some one dumb it down for me as well as you have. This makes a lot more sense, Aces
@jorgejaimes3147
@jorgejaimes3147 2 жыл бұрын
Good afternoon, I have a question, what does the opening of the IGV depend on?
@juliocastaneda9864
@juliocastaneda9864 2 жыл бұрын
@@jorgejaimes3147 igv is moved by the algorithm in the controller to keep leaving water temp at or very close to set point . Other things can influence how the far or locked in placed for the igv movement if a condition exists that exceeds the machines limits that would keep the IGV from moving to the desired position but that's protection for the machine we don't move those manually
@bunnyman6321
@bunnyman6321 Жыл бұрын
​@@juliocastaneda9864 What's igv?
@juliocastaneda9864
@juliocastaneda9864 Жыл бұрын
@@bunnyman6321 it's an abbreviation for inlet guide vanes. It's the vanes that control capacity on a machine like this. It can go up and down to modulate capacity. They open wide for machine to go to 100 capacity when the water temperature is far from the setpoint this makes the machine work harder when it reaches near the setpoint it closes somewhat the IGV to reduce capacity and stay close to the setpoint . It's capacity control of the unit. Kind of an unloader on a recip compressor or multi stage cooling and heating
@bunnyman6321
@bunnyman6321 Жыл бұрын
@@juliocastaneda9864 Thanks! Do commercial hvac techs deal with plc?
@xelusional9892
@xelusional9892 5 ай бұрын
1st year apprentice here, working for a commercial/industrial company. Today I punched tubes for the first time, on a carrier. One thing I like todo at the end of the day is search for educational content on what I did that day. And today I found your video, thanks for the knowledge my friend 🙏 🤑
@HVACTIME
@HVACTIME 5 ай бұрын
intro to chillers course launching at chilleracademy.com on Monday! welcome to the industrial side!
@vickiesrag
@vickiesrag 5 ай бұрын
Can you explain why we loose capacity with the Economizer? I brought it up some I was told I was wrong but didn’t have enough info to explain it. Somebody help lol
@kevinmithnick9993
@kevinmithnick9993 2 ай бұрын
Maybe because you are using compressor power to cool The refrigerant, not the water the chiller is intended to. The term "less capacity" refers to total cooling capacity available to chill the water Like in a car for example, you use engine power to run auxiliaries like alternator, coolant pump...
@jorgitomarquez
@jorgitomarquez 2 жыл бұрын
I am a mechanical engineer and this is a great explanation full of practical tips. Thank you!
@MR-backup
@MR-backup 9 ай бұрын
Definitely a good video. Why is it the Engineering world is so full of "geniuses", but almost all of them can't even teach a pet rock to sit?
@Fitzyfitta
@Fitzyfitta 3 жыл бұрын
Awesome video. You are killing it man!!
@kevinrooney5722
@kevinrooney5722 3 ай бұрын
Great Video, We are having an oil migration issue one of our CVHH-SVX001A units and assistance on how to get it to migrate back would be fantastic
@kevinmithnick9993
@kevinmithnick9993 2 ай бұрын
11:30 also because greater lift requirements for other refrigerants like r134a found in YK 's
@jamesmobley4762
@jamesmobley4762 3 жыл бұрын
Come and work for Google datacenters...apply, won't regret it
@jasonjohnsonHVAC
@jasonjohnsonHVAC Ай бұрын
513 and 514 is the new flavor of juices being used
@brandonwalker4842
@brandonwalker4842 10 ай бұрын
One thing. . Oil don’t sit on the bottom of the evap it floats on top of the refrigerant. Which is why under light loads we don’t get oil return back because there is no aggressive boiling breaking the oil out of the refrigerant. I would be interested to know actually how far that secondary oil return line goes up into evap?
@gordonrockafellow1211
@gordonrockafellow1211 11 ай бұрын
The reason that the oil tank is heated is to keep liquid refrigerant from draining or condensing into the oil tank. Liquid refrigerant is heavier than oil and would cover the electric oil pump intake, feed refrigerant instead of oil on start up, destroying the bearings. The oil pressure control doesn't know difference in liquid refrigerant from oil.
@josezavalazavala7864
@josezavalazavala7864 Жыл бұрын
Hello what are the symptoms of a overcharged chiller?
@MR-backup
@MR-backup 9 ай бұрын
Good question.
@kevinmithnick9993
@kevinmithnick9993 2 ай бұрын
I think it depends of the type of compressor, expansion device.... In general higher than normal condenser pressures followed by high current possibly tripping alarms for those reasons Particularities in each machine, for example, chillers using exv's you could see control tendency to close the valve more than normal (rthd, rtwd, ylaa, cgam, 30rap) Yk,s you could see control trying to close orifice beyond setpoint Others like ycav fill valve fighting with high subcooling.... If that's the case a good idea is to recover refrigerant in vapor fase only...
@Faketaxie
@Faketaxie 20 күн бұрын
Thank you for explaining it like a tech to tech 😂
@christophermerritt6436
@christophermerritt6436 Жыл бұрын
I like the detail that you give us I am up-and-coming certified Universal and wanting to service and have great knowledge of chillers so you helped me a lot thank you
@markbell6864
@markbell6864 3 жыл бұрын
That’s what I thought just wasn’t 100% positive. Thanks for the reply and thank you for what you do. Great job and love your vids.👍
@HVACTIME
@HVACTIME 3 жыл бұрын
Thank you!
@genegonzalez4713
@genegonzalez4713 2 жыл бұрын
Daikin has developed a system that practically eliminates surging, one of the things they,ve added is a checkvalve on de discharge of the compressor, this counteracts the reverse flow that comes from the condenser back towards the compressor discharge. as we all know surge is when the condenser pressure is greater than discharge pressure this phenomenon is synonimous with surge
@CryptoAbe
@CryptoAbe 2 жыл бұрын
Daikin is about to go bankrupt... pile of junk
@OramWerd
@OramWerd 2 жыл бұрын
@@CryptoAbe “about to go bankrupt”…..you do realize Daikin is the largest HVAC manufacturer in the world right? Do you even know what you’re talking about?
@americafirst6016
@americafirst6016 9 ай бұрын
@@CryptoAbe lmao dude. No clue what you are talking about
@PrabashMilinda
@PrabashMilinda 4 ай бұрын
i want to know why this trane chiller shut down with afd hi temp alam , what is the problem and how to fix it..because i have big knowledge abut chiller ..please explain
@HVACTIME
@HVACTIME 4 ай бұрын
Have you verified your cooling system for the afd? If you'd like in-depth Chiller support I have a chiller community to discuss troubleshooting help for everyone enrolled at chilleracademy.com
@romancavalrycomfort
@romancavalrycomfort 2 жыл бұрын
Very easy to understand explanation thanks
@dodgerblue182able
@dodgerblue182able 3 жыл бұрын
Thanks for the video, great explanation of the centrifugal unit!
@rajeshtiwari-kb7nb
@rajeshtiwari-kb7nb 5 ай бұрын
Ek videoHindi me bhi translet karke banaye sir
@aircooledchilleralltypes4938
@aircooledchilleralltypes4938 3 жыл бұрын
Sir trane rtaf techview software is free
@andyreyes6464
@andyreyes6464 16 күн бұрын
Amazing man just amazing
@genegonzalez4713
@genegonzalez4713 2 жыл бұрын
Usually surge is agravated by two things; a poor cooling tower performance [tower effectiveness, not adequate] meaning that the tower is undersized for that given moment and time, tower operating outside of the design approach. Also a deficit or lower then normal flow within the condenser shell. This increase in pressure within the condenser shell, overcomes compressor discharge pressure / Surge
@MelonBopper
@MelonBopper Жыл бұрын
There is definitely more things that could cause a surge, especially on these chillers. All depends on if you're talking about a high end surge or a low end surge.
@gaminidissanayake5465
@gaminidissanayake5465 3 жыл бұрын
Bless u. Valuble infos.keep up the good work
@LudwiggBalili
@LudwiggBalili 7 күн бұрын
Great video
@americafirst6016
@americafirst6016 Жыл бұрын
Worked on a CVHF570 this week, pulled the rear bearings. Good video.
@MR-backup
@MR-backup 9 ай бұрын
How to video?
@rupertstaana3382
@rupertstaana3382 3 жыл бұрын
Another great content! Is my understanding correct for how lowering CHWS set point causes a drop in chiller cooling capacity. For AFD controlled compressor, - chws set point is lowered, - compressor speed increases - increased refrigerant discharge volume to condenser - Liquid refrigerant builds up in condenser - Head pressure increases on first flash plate - Increased subcooling and increased flashed ref gas. - Decreased volume of liquid refrigerant returning to evaporator and increased flashed gas to economiser. Am I getting it right? Thanks!
@HVACTIME
@HVACTIME 3 жыл бұрын
Correct. Lower the setpoint the less total capacity it will carry. And become more inefficient.
@rupertstaana3382
@rupertstaana3382 3 жыл бұрын
@@HVACTIME im amazed how you reply so quickly! Thanks again 💪🏽
@HVACTIME
@HVACTIME 3 жыл бұрын
@@rupertstaana3382 here to help
@OTHG6v
@OTHG6v 2 жыл бұрын
Liquid decreases in the condenser due to density at colder temps, speed increase to compensate for the volume available. On a normal machine that has a txv sub cooling will decrease.
@OTHG6v
@OTHG6v 2 жыл бұрын
Compression ratios matter. Orifice doesn’t care….. txv, exv or float all is related to lift.
@Zane-qd3ri
@Zane-qd3ri 6 ай бұрын
Very helpful
@MAMED100
@MAMED100 11 ай бұрын
Good afternoon, I would like to know the measurement of the condenser sealing ring? I will be very grateful for your help
@jeremyparo9117
@jeremyparo9117 7 ай бұрын
Great video, man! We appreciate your time!
@hvacengineeringbyvladimirpaul
@hvacengineeringbyvladimirpaul 7 ай бұрын
Great
@mathewkurian7521
@mathewkurian7521 Жыл бұрын
Awesome explanation!! Even Trane couldn't explain this much!!! Thank you Sir!!♥️
@MR-backup
@MR-backup 9 ай бұрын
An in depth video, even if it is a short one, on the CVHF/E motor refer cooling cycle would be nice.
@midovlogofficiel
@midovlogofficiel 2 жыл бұрын
Hello my brother I have a problem on the Trane RTAD165 group I have an alarm (Temp winding -comp A)
@arunmehera1976
@arunmehera1976 Жыл бұрын
Will you please help me out about carrier 19XR centrifugal water cooled chiller.
@franciscocobill5513
@franciscocobill5513 2 жыл бұрын
Work w/ R-11 & R-12 Trane Centravac chillers a very nice reliable machine.
@neilvestervictor180
@neilvestervictor180 3 жыл бұрын
the ones we have is from g group five of them 160,137(2) two 50 tons
@PTISUPPORTERS786
@PTISUPPORTERS786 Жыл бұрын
Great job sir I am really saying I clear all my doubts in your video very well done 👏
@arshedkhan9470
@arshedkhan9470 2 жыл бұрын
this model chiller High current Alam rejoin?
@tarpontime7562
@tarpontime7562 2 жыл бұрын
What is the oil line that’s right next to the tang operator?
@neilvestervictor180
@neilvestervictor180 3 жыл бұрын
Mitsubishi bought the company now
@_Padma_TausikHasan
@_Padma_TausikHasan 2 жыл бұрын
Dear, Thanks with lots of love.
@peterszczepaniak1893
@peterszczepaniak1893 Жыл бұрын
Thank you for the videos please keep it up
@danielpsky9596
@danielpsky9596 3 жыл бұрын
very good content. Can you make a video about TurboCore compressors. I personally have been seeing more and more Daikin Maglev and Multistack using Danfoss TurboCore compressors.
@HVACTIME
@HVACTIME 3 жыл бұрын
Sure can, that would be a great one to do!
@neilvestervictor180
@neilvestervictor180 3 жыл бұрын
I work ministry of health
@OTHG6v
@OTHG6v 2 жыл бұрын
Tip speeds the same. Geared or not.
@stlbrian33
@stlbrian33 3 жыл бұрын
Another Great video. Thanks.
@ziaarnie3694
@ziaarnie3694 3 жыл бұрын
Amazing as always bro . thank you
@morrismashike8330
@morrismashike8330 3 жыл бұрын
Nice well explained thanks man!
@bobparrott8130
@bobparrott8130 3 жыл бұрын
👍 great info Thank U
@kyler_720
@kyler_720 2 жыл бұрын
K8 ubbbv
@joseramos2719
@joseramos2719 2 жыл бұрын
Love it bro 👍🏽
@thisaranilupul904
@thisaranilupul904 3 жыл бұрын
nice
@brianmillion-osborne6747
@brianmillion-osborne6747 3 жыл бұрын
York has a new low pressure magnetic bearing machine called YZ .I had the chance to see it after it was commissioned at the start of this summer. It was for a condo. Beautiful piece of equipment.
@HVACTIME
@HVACTIME 3 жыл бұрын
Yes it is! What I find intriguing is they have fixed IGV.
@MR-backup
@MR-backup 9 ай бұрын
Until you have to fix it.
@kevinmithnick9993
@kevinmithnick9993 2 ай бұрын
To my understanding the first generation of ymc2's came with all the load control strategies available: prv, vgd (yes, also used for load control), vsd. Then they decide to skip some of those Maybe they found that vsd+Vgd is enough for load and surge control
@frankies1717
@frankies1717 2 жыл бұрын
Keep em coming ! Are you from NY?
@HVACTIME
@HVACTIME 2 жыл бұрын
East Texas
@Noypihvac
@Noypihvac 3 жыл бұрын
Have you work with TRANE RTAF OR RTAE?
@HVACTIME
@HVACTIME 3 жыл бұрын
Yes
@Noypihvac
@Noypihvac 3 жыл бұрын
@@HVACTIME what the difference of rtac and rtae in terms of design.
@markbell6864
@markbell6864 3 жыл бұрын
How do you gain subcooling from flashing?
@HVACTIME
@HVACTIME 3 жыл бұрын
In the same way sweat takes heat from your body by evaporating. When the flash happens the gas pulls heat from the liquid dropping the subcool temp.
@trachooyansucon3806
@trachooyansucon3806 2 жыл бұрын
@@HVACTIME Great VDO, thank you.
@MrEdwin1026
@MrEdwin1026 11 ай бұрын
Thanks!
@HVACTIME
@HVACTIME 11 ай бұрын
Thank you!
@politiciansthrowstones
@politiciansthrowstones Жыл бұрын
These are a absolute work horse! I love these machines. Even though I work for jci.
@spikester
@spikester Жыл бұрын
Its okay, its mission critical, your stuff has to just work & keeping a fine healthy relationship with the techs working on it for a living gives full sense of comfort, unlike those simply shilling for products on YT, this is a major indication of trust when it comes to equipment like this and word gets around very fast in the trades.
CVH & CDH Refrigerant Cycle Trane Chiller
12:26
HVACTIME
Рет қаралды 2,1 М.
когда не обедаешь в школе // EVA mash
00:57
EVA mash
Рет қаралды 3,6 МЛН
Will A Guitar Boat Hold My Weight?
00:20
MrBeast
Рет қаралды 256 МЛН
iPhone or Chocolate??
00:16
Hungry FAM
Рет қаралды 41 МЛН
HVAC Chiller Approach Explained
15:21
HVACTIME
Рет қаралды 49 М.
I used to hate QR codes. But they're actually genius
35:13
Veritasium
Рет қаралды 1,5 МЛН
Startup Issues with Trane Chiller
7:23
HVACTIME
Рет қаралды 7 М.
Chiller Training: Water Cooled Chillers Mechanical
1:47:10
HVACTIME
Рет қаралды 18 М.
Cooling Tower Setpoint For Chiller
19:24
HVACTIME
Рет қаралды 37 М.
DIY Vapor Compression Refrigeration System
28:06
Hyperspace Pirate
Рет қаралды 1,1 МЛН
HVAC Tech School: Understanding Chiller Surge
10:08
ControlTrends Smart Buildings
Рет қаралды 307 М.
Refrigeration Basics with Elliot and Bert Part 1
47:24
HVAC School
Рет қаралды 58 М.
Chiller Shaft Seal Repair on York YK Centrifugal
15:50
HVACTIME
Рет қаралды 33 М.
когда не обедаешь в школе // EVA mash
00:57
EVA mash
Рет қаралды 3,6 МЛН