Troubleshooting Trane EEV and EVC Board

  Рет қаралды 82,132

Zack Talks Shop | B-Side

Zack Talks Shop | B-Side

Күн бұрын

Do not try this at home! HVAC training is required!
profile.php?...

Пікірлер: 52
@francolezzi6948
@francolezzi6948 2 жыл бұрын
*Used to supplement the up stairs when it gets hot outside this works very well and **Fastly.Cool** Also works good when the upstairs gets too hot in the Winter from the heater.*
@trickyanims7852
@trickyanims7852 5 жыл бұрын
Had a TAM7 with the 10 red flash (superheat) fault. Great video! Read a interesting article suggesting the "SH" fault can sometimes be due to a dirty filter or evap coil.
@Powlashvac
@Powlashvac 8 жыл бұрын
Holy crap that PSI dropped like a brick. Great video Zack
@zacktalksshopbside
@zacktalksshopbside 8 жыл бұрын
I was so sure it was a txv
@jimmartinez8977
@jimmartinez8977 5 жыл бұрын
Really appreciated the vid! Thank you.
@johnisraeljr5623
@johnisraeljr5623 8 жыл бұрын
Great troubleshooting Zack!! Really enjoyed this video!!
@zacktalksshopbside
@zacktalksshopbside 8 жыл бұрын
Thanks John, I wad glad I ran into this one
@ComfortPlusHeatingandCooling
@ComfortPlusHeatingandCooling 8 жыл бұрын
Good video Zack! That boy brazes copper the way I weld steel lol.
@zacktalksshopbside
@zacktalksshopbside 8 жыл бұрын
It wasn't pretty
@joshmassaro7333
@joshmassaro7333 4 жыл бұрын
Honestly I can't find any literature for trane. It is driving me nuts. They tell me to go online but all I find online is installation manuals.
@arthurhartwick7974
@arthurhartwick7974 Жыл бұрын
Great video. I was working on one today. What are those round things you're using to read pressure?
@10rninjariderzx
@10rninjariderzx 5 жыл бұрын
How much energy does an eev save you vs the replacement and service calls to fix it?
@mrgreen9086
@mrgreen9086 3 ай бұрын
Worked on of these the day Had 3 green flashes (stage 2 cooling) and 7 red flashes (high superheat) put a jumper on open and test and pressures did not change. Going to be replacing the exv 😅
@chinopaiz1708
@chinopaiz1708 3 жыл бұрын
Do you have the E-manual for the control board and electronic tapper motor ..??
@geekincognito
@geekincognito Жыл бұрын
I have the same unit. Getting 6 green and 4 red flashes while cooling. Any idea?
@achevalier111
@achevalier111 6 жыл бұрын
Hey where can I find gauges like that? I don't know what to call them, pocket gauges?
@adamspears3819
@adamspears3819 4 жыл бұрын
Thanks for the video. Do you know what 7 red fault flashes mean on that EEV control board?
@ryanscanlon2450
@ryanscanlon2450 2 жыл бұрын
High superheat
@mistyflorist5455
@mistyflorist5455 6 жыл бұрын
good day sir. may i know how to get the app for checking the reading from a tablet and where to get the service handbook? i am a apprentice in air con and will be doing a presentation by year end and our guys wish to monitor the system wirelessly. pls advicr
@jamesrothwell1738
@jamesrothwell1738 Ай бұрын
What’s the name of that book?
@Bill_CBR
@Bill_CBR Жыл бұрын
I'm curious, where did you find the leak? Did you ever go back for that?
@joeschneider67
@joeschneider67 4 жыл бұрын
No way that EEV and circuit board fail at same time. That's easy fix by replacing everything. Am sure the problem was the EEV...more likely, if that unit has air flow problems ( low air flow ), the valve will be working hard to maintain refrigerant flow till collapse. I have see that issue very often.
@380Banshee
@380Banshee 2 жыл бұрын
That stepper motor tho, dip switches trane famous for those, program to the air handler type, weeeee, lol!!
@Chris-zo9yy
@Chris-zo9yy 4 жыл бұрын
I’m just wondering but if you couldn’t jump out the stepper motor and then determined the step motors resistance was off point, what led you to condemn the board? You shouldn’t be able to jump out a bad motor.
@Papasquatch73
@Papasquatch73 3 жыл бұрын
He said why 4:51
@jonathanhale8388
@jonathanhale8388 3 жыл бұрын
If you ohm it out and it ohms bad, it's a bad step motor in my experience.
@camronconlee944
@camronconlee944 8 жыл бұрын
I actually really like eev's.... for refrigeration, not for a/c. I mean if you already have an automation system I figure why not, but for one split system it seems like overkill.
@zacktalksshopbside
@zacktalksshopbside 8 жыл бұрын
I don't see too many problems with them either. Just a little overkill like you said.
@wesjarrett7295
@wesjarrett7295 3 жыл бұрын
What will you charge me for a copy of your service book. My boss just threw me into this role and I habe no information available
@chrisd3399
@chrisd3399 3 жыл бұрын
This is literally what happen too me today !
@THEMFORMATION
@THEMFORMATION 4 жыл бұрын
How did you fit your meter leads in there to test the stepper motor? Mine wont fit
@amann910
@amann910 4 жыл бұрын
you can use small piece of thermostat wire in a pinch or get back probe kit for your leads
@frankcloskey7789
@frankcloskey7789 Жыл бұрын
Note : Trouble shooting is very important so is your sub cooling.8/7/2022yr
@Bluecollarworkingman
@Bluecollarworkingman 6 жыл бұрын
This is good.
@Bluecollarworkingman
@Bluecollarworkingman 6 жыл бұрын
Changing the dipswitch to the wrong refrigerant and back, got mine going temporarily until i could get a new one.
@Jimddddd1981
@Jimddddd1981 8 жыл бұрын
Electronic expansion valve? Is that shit really necessary? I'm sure the salesman who sold that system talked about all the "benefits" of the Trane system. What I'm sure he did not mention is that the cost of repairing the system negates the energy savings. I would never recommend this type of system.
@zacktalksshopbside
@zacktalksshopbside 8 жыл бұрын
It does not appear it was needed. I don't really do these type either.
@321marshman
@321marshman 6 жыл бұрын
Jim D they are kind of in the new inverter technology
@jonathanhale8388
@jonathanhale8388 3 жыл бұрын
They're great for efficiency. They're really not bad to diagnose or work on. The motor can fail but the valve itself is rated for practically the life of the unit. EEV and ECM all the way!
@NotOurRemedy
@NotOurRemedy 2 жыл бұрын
More reliable and efficient.
@Wisdomoftheair
@Wisdomoftheair 8 жыл бұрын
High-dollar equipment but not a lot of quality in the installation. That strikes me as, odd.
@dirtydave2315
@dirtydave2315 4 жыл бұрын
That little sticker in the corner says the unit should not be taped up like that
@RobHVAC
@RobHVAC 8 жыл бұрын
Nice trouble shooting.
@zacktalksshopbside
@zacktalksshopbside 8 жыл бұрын
Thanks Rob
@mns.gh6432
@mns.gh6432 3 жыл бұрын
From Iraq so thnxs
@joeshearer1247
@joeshearer1247 8 жыл бұрын
That suction line was horrible! Were you lucky enough to have that literature left for you?
@zacktalksshopbside
@zacktalksshopbside 8 жыл бұрын
Yep it was on the unit. My phone was ready if not.
@video-wt6de
@video-wt6de 6 жыл бұрын
Hello how are you
@john7017
@john7017 5 жыл бұрын
You can pull a Trane...
@tomwardzala4240
@tomwardzala4240 6 жыл бұрын
Piece of shit hyperion series units
@usahoangsatruongsa
@usahoangsatruongsa 4 жыл бұрын
Sssooo the bottom line here is you misdiagnosed it. You blamed it on Trane EEV and control board ?? When you first check the standing pressure 50 psi didn't ring a bell ? When you test run in cooling mode (3:32) the highside pressure only 214 psi for a r410a system did not ring a bell ? and You blamed it on EEV and control board ? have ever heard of low charge? I know a heat pump equipped with EEV is not popular and not easy to diagnose it but atleast when you look at the gauge The high side pressure only214 psi did not tell you anything?? If you suspect a bad EEV (not open,stuck closed) then when you run the cooling mode the high side pressure should be MUCH HIGHER not 214 psi as shown in your video.
@adamcraig1568
@adamcraig1568 3 жыл бұрын
So before you attack Zack know your shit. System was running 100/300 in heating mode which in NC is very possible. In cooling mode we could obviously see a restriction. If your running cool mode in winter (November) than obviously in cooling your head pressure will be that low. Come on man. Hvac 101
EEV Valves and Power Heads
8:01
HVAC is WIN
Рет қаралды 10 М.
ROCK PAPER SCISSOR! (55 MLN SUBS!) feat @PANDAGIRLOFFICIAL #shorts
00:31
🌊Насколько Глубокий Океан ? #shorts
00:42
100❤️
00:19
MY💝No War🤝
Рет қаралды 8 МЛН
Electronic expansion valve
13:10
What would Dennis do
Рет қаралды 12 М.
KEEP THESE ON YOUR TRUCK... Solenoid & EEV Magnets
3:16
Johnstone Supply Balsan Group
Рет қаралды 25 М.
Electronic Expansion Valve - How it works ETS 5M HVAC
13:41
The Engineering Mindset
Рет қаралды 361 М.
trane unit with bad RTRM board
14:30
Anthony Reardon hvacr
Рет қаралды 33 М.
System not cooling |TRANE TAM7 AFC board | HVAC
7:35
Koolin’ with Krauss HVAC
Рет қаралды 12 М.
Electronic Expansion Valve Tutorial
6:01
Temperzone Climate Innovations
Рет қаралды 4,6 М.
Testing an EEV
3:15
Samsung HVAC America
Рет қаралды 29 М.
HOW TO TEST DAIKIN EEV COIL.
12:23
Mitch Attwood
Рет қаралды 12 М.
ROCK PAPER SCISSOR! (55 MLN SUBS!) feat @PANDAGIRLOFFICIAL #shorts
00:31