Heat pump 13 stuck check valve

  Рет қаралды 5,027

Love2HVAC with Ty Branaman

Love2HVAC with Ty Branaman

Күн бұрын

Heat pump with a stuck check valve.
Indoor vs outdoor, stuck open vs stuck closed.
From taking a test to diagnosing a live systems lets explore a variety of stuck bypass check valves in a heat pump application.
Some of these will be be more applicable than others but the idea is to get you thinking about the heat pump cycle.
Outdoor check valve stuck open in AC mode
Outdoor check valve stuck open in Heat Pump mode
Outdoor check valve stuck closed in Heat Pump mode
Outdoor check valve stuck closed in AC mode.
Indoor check valve stuck closed in AC mode
Indoor check valve stuck closed in Heat Pump mode
Indoor check valve stuck open in Heat pump mode
Indoor check valve stuck open in AC mode
Special thanks to JD Kelly student of HVAC for the awesome graphics!

Пікірлер: 34
@JasonKurtz-uc2xy
@JasonKurtz-uc2xy 10 ай бұрын
Hello Ty. I always dreamed of being a student of yours. You have a wonderful personality and I love the way you break things down. We’re probably around the same age, but I’m just starting out in the field. It’s been overwhelming and daunting at times, but I presume it’s going to be like this for awhile. You are a great teacher and a great man. I love the inner joy that you bring when you surround people. You are like a beacon of light. Even though we don’t know each other personally, it an honor and a pleasure knowing you from the social media platform. Take care.
@kentuckyhillbilly455
@kentuckyhillbilly455 2 ай бұрын
Thanks for still being around. You are a valued member of the HVAC community. I have definitely learned a lot from your videos. This isn’t my line of work but a lot of it applies
@benefits941
@benefits941 2 ай бұрын
currently in school for hvac you are great help
@RATCHETMAN1001
@RATCHETMAN1001 7 ай бұрын
tom lech sent me to watch you, i do automotive ac i thought because the way we are taught we were doing ac correct( boy was i wrong) in my industry is so far behind. i love what you are teaching. not every thing applies to us but most of it does. i thank you and tom so much. wow wow wow
@love2hvac
@love2hvac 7 ай бұрын
Awesome!! Tom is great. We have lots of people on the HVAC side that don't know either. It's about learning and sharpening our skills. I love it when people want to learn!
@RATCHETMAN1001
@RATCHETMAN1001 7 ай бұрын
@@love2hvac im 67 and most of my life i love to learn new things.i dont no if i would want to be a teacher cause so many dont want to learn and that would disappoint me i think.but watching and learning from u guys gets me excited like a kid with a new toy. i ll keep watching till i get the info i need ,many thanks
@chesstime356
@chesstime356 Жыл бұрын
Another good video as always I like your videos. I think I will be watching this video few times again to get more out of it. I do most of the time residential maintenance work… heading towards fully service technician…
@love2hvac
@love2hvac Жыл бұрын
Thank you! I am so glad they are helping!!!
@JanosHoyos
@JanosHoyos 4 ай бұрын
Hi Ty 2 months ago i asked you about doing combustion analysis and you responded remind me closer to heating season which is now. If you do decide to do a session on combustion could you please address troubleshooting, diagnosis and adjustments. Thanks and have a great day. Best regards Victor
@nakiapringley5391
@nakiapringley5391 Жыл бұрын
Great video.
@jimmylanders2175
@jimmylanders2175 Жыл бұрын
Happy New Year Ty! Love your teaching and videos. Other than gauge pressure and temps and SH and SC, can you also do a temp across the metering device to prove prior to change out?
@love2hvac
@love2hvac Жыл бұрын
A temperature reading across an open check valve is a great way to check. It should be the same temperature, if not it's likely restricted If the metering device is engaged there will be a temperature drop but there is in value in what it should be
@mtbbiker6401
@mtbbiker6401 Жыл бұрын
Hi Ty. I have a Trane Heat Pump. There is a bypass check valve at the outdoor unit which I believe is a ball type check valve that allows refrigerant to bypass the outdoor TXV. There is no such bypass valve in the indoor unit. This means the indoor TXV must have a built in bypass when operating in heat mode. Is this the case? My mom also has two similar Trane Heat Pumps. One has a similar bypass on the outdoor TXV but the other unit does not have this extra bypass routing, only the outdoor TXV. I guess there are TXVs designed to allow flow of refrigerant in both directions. My outdoor unit was making a chattering noise while running and pretty loud after the compressor shut down for a few minutes (in cooling mode). I diagnosed the noise coming from the outdoor check valve. Apparently this is a known issue with older Tranes (2010). Trane released a clip on magnet part to help eliminate the noise. I suspect that after the compressor shuts down, refrigerant is flowing back through the valve which causes the noise after shutdown. Hopefully it won't harm any other components. I have posted a video of the noise on my channel.
@love2hvac
@love2hvac Жыл бұрын
The Trane check valve rattle is a known issue for sure. I likely to damage anything and the magnet kit helps with the noise. The indoor TXV is usually built with an internal bypass check valve. Some Trane TAM models use an electronic expansion valve inside. They are programmed so the stepper motor of the EXV opens all the way for bypass. Excellent question!
@mtbbiker6401
@mtbbiker6401 Жыл бұрын
@@love2hvac Thanks for the reply. I was a little perplexed when I didn't see external bypass piping on the indoor TXV like it has on the outdoor unit.
@oscarguillen1729
@oscarguillen1729 9 ай бұрын
Are there any cases where the reversing valve or compressor will be the issue in a high suction pressure scenario? If so, would it be possible to make a video on how to troubleshoot such issue? Thank you for the videos you make and all you do for HVAC community!
@jpechacek80
@jpechacek80 Жыл бұрын
3 ton residential package unit 410A . Compressor trips on over pressure in Heat Mode (>500psi). I blocked the outdoor fan with a cardboard so it wouldn't trip. (temporarily to measure) LO side P=110, T=38.6 (suction) Tsat=35.5 => 3.1deg superheat. HI side P=350, T=80 Tsat=105 (25deg subcool!) (Downstream from the TXV bypass ) After watching this video, I need to recheck upstream from the TXV bypass And look for a temperature difference across the TXV that is supposed to be bypassed in Heat Mode. If stuck, is there a way to get it unstuck without opening up the system?
@love2hvac
@love2hvac 11 ай бұрын
Sometimes a magnet works, some times tapping it but those are often temporary.
@bernardocisneros4402
@bernardocisneros4402 3 ай бұрын
Thanks for the video. Do you prefer using a manual (analog) or digital manometer?
@VERYEASYTOLEARNHVAC
@VERYEASYTOLEARNHVAC Жыл бұрын
thanks ty,,,, when you make electrical & control wiring related videos??
@love2hvac
@love2hvac Жыл бұрын
It's coming! Work and bills keep getting in the way
@mikev.1034
@mikev.1034 Жыл бұрын
👍👍
@AngelRodriguez-qg5zq
@AngelRodriguez-qg5zq Жыл бұрын
Thanks Ty and happy new year!
@love2hvac
@love2hvac Жыл бұрын
HAPPY New Year!
@NizarOkab
@NizarOkab 11 ай бұрын
On a previous 410a charging video, you charged the unit through the low side. Is it safe to add liquid knowing that’s it going to the compressor?
@love2hvac
@love2hvac 11 ай бұрын
Throttling it in, very short burts allowing to to expand to a vapor before reaching the compressor.
@ddcws1
@ddcws1 14 күн бұрын
I'm following you so can an internal txv check valve fail?
@love2hvac
@love2hvac 14 күн бұрын
Yes
@ddcws1
@ddcws1 4 күн бұрын
Reason I am asking is because we have had an issue with a trane package heat pump. Last March It was locking out on a in-timed defrost 8 and 9 fault. When testing we found the tech determined it to be on the cooling side. The indoor txv was restricting when going into defrost he replaced it. It happened again. I go out there and looks to be that there is a restriction on the cooling side. We just replaced a txv so I called Trane and they said indoor coil was plugged with the readings I gave them. Replaced coil w/new txv and tested and everything looked okay. Tested defrost numerous times and no issues. 9 months later (Dec) issue is happening again. Same thing in timed defrost. I tested it and no issues. Forced defrost things looked okay. Forced again and when it came out suction pressure fell below the low pressure switch cut out. Switch opens up at 35psi and I was near 30psi. Granted I had bypassed low pressure switch while currently testing thinking maybe it was the issue but it was good. Had no significant temperature drop across filter drier so Determined outdoor txv was issue. Replaced and no issues. I have a picture of the filter screen at old txv and you can see its plugged. Wondering if that was the actual issue the whole time. If the screen is restricted wouldn't that also affect it bypassing correctly?
@ddcws1
@ddcws1 4 күн бұрын
@@love2hvac When I did the indoor coil repair I flowed nitrogen. I always flow it anytime I do a repair. Just wanted to let you know.
@love2hvac
@love2hvac 3 күн бұрын
@@ddcws1 yes if the screen is clicked it would affect bypassing. Most of the Trane units have an external check valve outside
@ddcws1
@ddcws1 3 күн бұрын
@ it's a residential package unit. I don't believe there is an external check valve.
@salvatoregiovanni8967
@salvatoregiovanni8967 Ай бұрын
Great content and scenarios, but for this content to be geared toward students, your presentation speed is waaay too fast. Slow down!
@JanosHoyos
@JanosHoyos 4 ай бұрын
Please
Heat Pump 11 Gauges
16:17
Love2HVAC with Ty Branaman
Рет қаралды 14 М.
Heat Pump 03 Reversing valve
21:04
Love2HVAC with Ty Branaman
Рет қаралды 37 М.
1% vs 100% #beatbox #tiktok
01:10
BeatboxJCOP
Рет қаралды 67 МЛН
СИНИЙ ИНЕЙ УЖЕ ВЫШЕЛ!❄️
01:01
DO$HIK
Рет қаралды 3,3 МЛН
HVAC 106 Scenario Restriction and non-condensable
14:02
Love2HVAC with Ty Branaman
Рет қаралды 31 М.
Heat Pump 12 Hight Pressure trips only in Heating
12:51
Love2HVAC with Ty Branaman
Рет қаралды 12 М.
Temperature Rise How to Measure it and Why it's Important
7:54
TAS Academy HVAC Training Videos
Рет қаралды 7 М.
HVAC 102 Scenario Low Evaporator Airflow effects on the refrigeration cycle
9:54
Love2HVAC with Ty Branaman
Рет қаралды 11 М.
MASTER the Thermostatic Expansion Valve in the HVAC Industry!
25:03
Heat Pump 02 Refrigeration cycle step by step AC-HP
28:16
Love2HVAC with Ty Branaman
Рет қаралды 13 М.
Heat Pump 06 Fixed orifice metering device
11:11
Love2HVAC with Ty Branaman
Рет қаралды 14 М.
Troubleshooting With Sat Temps, Superheat, & Subcooling! 5 Possible Problems!!
18:48
Heat Pump Reversing Valve Troubleshooting Tips (Switchover Valve)
10:43
Fox Family Heating and Air Conditioning
Рет қаралды 164 М.
1% vs 100% #beatbox #tiktok
01:10
BeatboxJCOP
Рет қаралды 67 МЛН