EEV/EVX leaking by causing low superheat alarms on chiller

  Рет қаралды 9,887

Ulises Palacios

Ulises Palacios

Күн бұрын

A look at Sporlan SERI electronic expansion valve

Пікірлер: 61
@rookierefrigeration4357
@rookierefrigeration4357 4 жыл бұрын
Good video. Funny how the seat was worn enough to bleed by. Nice find 💪🏼💪🏼
@bradmironik6137
@bradmironik6137 4 жыл бұрын
Thanks for sharing. Interesting how that works.
@philltafolla
@philltafolla 4 жыл бұрын
Welcome back Ulises 😬😁
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Felipe Tafolla haha this one was interesting and kicked my butt for a bit. Figured I would make a video so hopefully it could help out someone in the future.
@philltafolla
@philltafolla 4 жыл бұрын
Ulises Palacios nice . So even with the pin closed , refrigerant would still leaked by ? I’ve seen it on liquid solenoid valves , few times , since I work on smaller stuff . Good shit shout out from SoCal 😎
@ismackherbiehind
@ismackherbiehind 4 жыл бұрын
Those Veto bags are very nice. I own one and I love it.
@JuanTodoli
@JuanTodoli 4 жыл бұрын
Good find Ulises 👍
@sterlingarcher46
@sterlingarcher46 4 жыл бұрын
Very interesting, mate 👍 Hey who's the make of that EEV ? I'm only used to Carel and some Sporlan ones ?
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Sterling Archer thanks. It’s a sporlan seri-j
@sterlingarcher46
@sterlingarcher46 4 жыл бұрын
@@UlisesPalacios cheers , mate , love your vids , man , fantastic job !👍👍👍
@bmillwood6666
@bmillwood6666 4 жыл бұрын
Those exv come a part. When I installed one of those, I took them apart during welding
@HVACRVIDEOS
@HVACRVIDEOS 4 жыл бұрын
Really interesting, it seems like it would take some serious effort to damage that seat......
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
HVACR VIDEOS yeah. I wondered that myself. They are pretty strong motors and I didn’t see any visual damage on the seat surface
@19thcenturyfuture
@19thcenturyfuture 4 жыл бұрын
Ulises Palacios the needle is stainless and the seat is soft brass, after time and many hard close off’s.....there ya go
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Jake Crockett makes sense.
@19thcenturyfuture
@19thcenturyfuture 4 жыл бұрын
Ulises Palacios thanks for the vids, always enjoy
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Jake Crockett thanks 🙏
@whitesheatingairappliancer7101
@whitesheatingairappliancer7101 4 жыл бұрын
What voltage are you using to control the motor, 200 vdc? Great video thanks
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
12-14vdc
@whitesheatingairappliancer7101
@whitesheatingairappliancer7101 4 жыл бұрын
Thank you
@yl923
@yl923 2 жыл бұрын
this speed 200 steps/second
@norikghoorchian5128
@norikghoorchian5128 3 жыл бұрын
I think I have same problem whit carrier 40 ton chiller. Any way thanks a lot for sharing this video.
@UlisesPalacios
@UlisesPalacios 3 жыл бұрын
Thanks for watching. I’ve had this issue on 2 trane chillers.
@creativetradesman6833
@creativetradesman6833 4 жыл бұрын
I’m having the exact same issue with a 09’ cgam120. I looked on 360 for parts but there is 3 different part numbers for modules and motors. Do you remember the part numbers for the angle valve and the stepper motor?
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Creative Tradesman what’s the serial number. I just replaced one on a 70 ton yesterday. You will need to order the part number that starts with Val and it’s a good idea to replace the module as well
@creativetradesman6833
@creativetradesman6833 4 жыл бұрын
Ulises Palacios is the stepper motor a MOT or an MOD?
@yl923
@yl923 2 жыл бұрын
where can I see the pinout of the valve connector? what pins do colored wires come to on it?
@marijoprugovecki2205
@marijoprugovecki2205 3 жыл бұрын
Hay do you work whit sporlan seri .. KS EV
@Bluecollarrebel
@Bluecollarrebel 4 жыл бұрын
Nice👍
@adnanqamar4398
@adnanqamar4398 3 жыл бұрын
hi ULises i have the same issue with cgam 70 machine ,chiller loading alarm of loss of charge.even the parameters are ok. some time chiller load alarm after 24 hours some time 16 hours.i had replaced suction sensor and transducer.still same issue.
@davemaldonado2496
@davemaldonado2496 2 жыл бұрын
have you come up with a solution? having low super heat issue w/ cgam 30
@SombraLocs
@SombraLocs 4 жыл бұрын
I’m thinking of getting that SM-12.
@Oz_is_on_fire
@Oz_is_on_fire 4 жыл бұрын
Cool. Nice share homie!
@robertmason4334
@robertmason4334 Жыл бұрын
What is that tool called to power exv
@SombraLocs
@SombraLocs 2 жыл бұрын
What did you use to take the valve apart?
@UlisesPalacios
@UlisesPalacios 2 жыл бұрын
I used a Klein skinny jaw adjusted wrench to Hold the valve on the flat spots and a dang pipe wrench to loosen the motorized part of the valve. I heard a crows foot works also
@SombraLocs
@SombraLocs 2 жыл бұрын
@@UlisesPalacios Thanks!
@UlisesPalacios
@UlisesPalacios 2 жыл бұрын
For sure. They are one there pretty tight.
@UlisesPalacios
@UlisesPalacios 2 жыл бұрын
When you reassemble it. It doesn’t have to be super tight.
@Randylazz
@Randylazz 4 жыл бұрын
Good stuff.......
@anthonymastello1573
@anthonymastello1573 4 жыл бұрын
There were some software issues with those LLIDS/Controller early on. All you have to do is unbind the EXV and then rebind and download new software to LLID.
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Anthony Mastello yup. . I have the bulletin. This chiller didn’t fall into those years but I went ahead and updated the software. It’s a 2017. Have you come across this issue?
@anthonymastello1573
@anthonymastello1573 4 жыл бұрын
@@UlisesPalacios I haven't. Do you know if someone changed the EXV recalibration time in the feature settings?
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Anthony Mastello no. It doesn’t look like it. It’s set to every 24 hours.
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Anthony Mastello it’s a 2017 CGAM
@anthonymastello1573
@anthonymastello1573 4 жыл бұрын
@@UlisesPalacios okay, yeah default is 24 hours. I'd be worried if someone changed it to a shorter time. Does the chiller short cycle?
@izharraza7995
@izharraza7995 2 жыл бұрын
SIR TARN CHILLER MODEL RTAF WHAT THIS PASWAD LLID BINDING SETTING ON DISPLAY
@SombraLocs
@SombraLocs 4 жыл бұрын
What type of chiller was it?
@UlisesPalacios
@UlisesPalacios 4 жыл бұрын
Familia Sanchez HVAC a 2017 CGAm
Electronic expansion valve
13:10
What would Dennis do
Рет қаралды 12 М.
Миллионер | 2 - серия
16:04
Million Show
Рет қаралды 1,2 МЛН
哈哈大家为了进去也是想尽办法!#火影忍者 #佐助 #家庭
00:33
火影忍者一家
Рет қаралды 124 МЛН
REAL 3D brush can draw grass Life Hack #shorts #lifehacks
00:42
MrMaximus
Рет қаралды 8 МЛН
EEV Valves and Power Heads
8:01
HVAC is WIN
Рет қаралды 11 М.
Troubleshooting No Evap Flow On Dakin AGZ Chiller
9:40
THE CHILLER GUYS HUB
Рет қаралды 2,8 М.
Electronic Expansion Valve - How it works ETS 5M HVAC
13:41
The Engineering Mindset
Рет қаралды 368 М.
Quick Ammonia leak search With A Sulfur Stick
7:28
Ulises Palacios
Рет қаралды 12 М.
Troubleshooting Trane EEV and EVC Board
7:49
Zack’s in the Shop
Рет қаралды 84 М.
Electronic Expansion Valve Tutorial
6:01
Temperzone Climate Innovations
Рет қаралды 7 М.
Chiller carrier 30gx.Alarm 60 الالارم. low discharge superheat
5:21
عالم التكييف المركزي والشيلرات samir salah
Рет қаралды 796
Loss Of Charge TRANE CHILLER CGAM070F … Leaks or Something Else
12:39
Миллионер | 2 - серия
16:04
Million Show
Рет қаралды 1,2 МЛН