Ron Pecina Jr. is a licensed electrical contractor. This allows him to pull permits and schedule inspections required to do this work. If you are planning to do this work yourself check with your local building department for the required permits in your area. Also, contact your electrical utility company for any further specifications required on your area. The work shown in this video was done in an area serviced Public Service Electric & Gas Company (PSEG).
The PSEG utility company requires a special metering device commonly referred to as the “5th Jaw.” This fifth jaws measures utility grounded neutral current. The work WILL NOT PASS INSPECTION if the “5th jaw” is not present in the meter enclosure at the time of inspection.
A grounding electrode system is required and consists #2 aluminum attached to the copper water main on both sides of the water meter. The supplemental portion of this grounding system consists of #6 AWG copper attached to two ground rods driven into the earth. The grounding electrode system is BONDED to the system grounded neutral conductor at the main disconnect to complete a SOLIDLY GROUNDED SYSTEM.
200 amp upgrade:
200 amp meter enclosure
2” PVC and various fittings and connectors
2/0AWG copper conductors
#2 AWG aluminum conductor
#6 AWG copper conductor
Galvanized ground rods and clamps
Water ground clamps
Exterior grounding bus
Pressure Treated 2x4
3/4” painted plywood
200 amp main breaker 40-circuit panel
All new circuit breakers
Individual wire connectors
Call 732-770-1437
Point Pleasant, NJ Licensed Electrical Contractor | New Jersey Electrical License & Business Permit Number: 16557
Want to see more? Another 200A Upgrade can be seen here: • 200 AMP SERVICE UPGRAD...
Like Us on Facebook:
/ classic-electric-llc-1...
Classic Electric, LLC
Point Pleasant, New Jersey
08742-5406
#Licensedelectrician #jerseyshoreelectrician
#7043Generac