Hello , if I am installing a Temporary Main 100amp Outdoor Electrical Service Panel with 2 ground rods 6 feet apart within 3 feet of a Shed Sub Panel . Will I be required to add two more ground rods at the Shed Sub Panel? Even; if, I have Main and Sub Panel bonded to same two Ground Rods ?
@MasterTheNEC2 жыл бұрын
If you have a remote distribution panel in the detached structure, in your case a shed, you would indeed be required to establish a grounding electrode system at the shed. Now, if the main panel and shed with remote panel are that close, nothing says you can't use the same ground rods if you wish.
@davem53922 жыл бұрын
how are you testing 25 ohms or less
@MasterTheNEC2 жыл бұрын
You invest in a 3-point fall of potential meter or an Ground Resistance Meter which are expensive. Here is the cheaper option - www.fluke.com/en-us/learn/blog/grounding/earth-ground-fall-potential But, its probably easier to just put in (2) ground rods.
@davem53922 жыл бұрын
@@MasterTheNEC thank you that’s what I figured. It would be interesting to have one to experiment with. I never used one
@JustWatkins562 Жыл бұрын
Just ran into this with an inspector, couldn't understand how to accomplish this so I just threw in two rods 😂 thank you very much for the info!!!
@BBQPitmaster6263 жыл бұрын
So the ground rods must practice Social Distancing as well?
@MasterTheNEC3 жыл бұрын
LOL......
@JustWatkins562 Жыл бұрын
That was funny 😂
@robertvillalpando52503 жыл бұрын
👍 instructed
@capoconstruction19613 жыл бұрын
I am researching a question. 200 Amp panel. Need to run underground service conductors to two spots in rear of property. How to calculate all this? 1. Determine distance? 2. Determine future potential load? 3. Go to two tables in NEC correct?
@MasterTheNEC3 жыл бұрын
We do not answer questions here. If you have a technical question please visit www.PaulAbernathy.com and post on our portal.