24V vs 48 volt 15kw inverters. What are the differences?

  Рет қаралды 56,416

Genetry Solar

Genetry Solar

Күн бұрын

Пікірлер: 73
@bjtaudio
@bjtaudio 3 жыл бұрын
That transformer in that 15kW inverter is about the same size as my 5kW unit, I noticed with all off the shelf inverters is the transformers are way undersized. Yes it will do the 15KW but with poor efficiency dropping below 93% 7% is a whopping 1050Watts of heat in that case, it will not last long. Also those little TO-220 mosfets irfb4110 all up 32 4 groups of 8 switching 300Amps at 50V, just a matter of time before it goes pop, or be sure to keep load at a few KW max no more, it will last then.
@IanTester
@IanTester 3 жыл бұрын
Note that this is an old style of inverter and is not as efficient as newer designs. The newer ones first use a DC-DC converter to get up to the required voltage, and then switch that with mosfets. I can't remember what these two types of inverters are called and some googling mostly turns up solar power websites.
@bjtaudio
@bjtaudio 3 жыл бұрын
Power Jack's definition of continuous power is full load for 10minutes or less, mine is full load + 10% for years. It really simple if anything gets hot and fans a running at full power then in not true continuous. My inverter only gets warm may be 15 degrees above room temperature, no fans needed.
@coreybabcock2023
@coreybabcock2023 Жыл бұрын
The thicker wire is to handle the amp draw without much voltage drop
@bobstockwell3911
@bobstockwell3911 5 жыл бұрын
the best Controller to use on this Inverter is the 100 amp Bluetooth Victron for $900
@joseperniarombos8679
@joseperniarombos8679 3 жыл бұрын
Muy bueno tu canal, lastima que no lo das en español, la traducción de youtube no es la correcta. Pregunto lo siguiente, el equipo tiene entrada de alimentación en fase dividida ( 240/120 V) ?. Si es así cuenta con cargador de Baterías ?. Has realizado pruebas de cargas con un banco de resistencias, para determinar su potencia real que describe el fabricante ?. Saludos desde el estado de Barinas Venezuela. Soy ingeniero electrónico, técnico superior en Electrónica y técnico en Telecomunicaciones. Mi especialidad son los sistemas de Energía. Me gusta tu canal amigo.
@repairman1808
@repairman1808 4 жыл бұрын
How this thing may be 15Kw if the power transformer is not more then 5Kw. A Triad Magnetic 5Kw transformer is 11 inches OD but this one is smaller as I can see. Do the China engineers brake physics low?
@graceho99
@graceho99 4 жыл бұрын
Nice video and precious info one can rarely find. One question: when you say that in the 24v inverter, the 24v DC input is turned into 18v AC before it enters the transformer, is the 18v in terms of RMS (i.e. voltage one reads from a volt meter)? Or you are talking about peak voltage?
@fabriziobrutti1205
@fabriziobrutti1205 3 жыл бұрын
It's RMS
@awade7622
@awade7622 5 жыл бұрын
Great video !
@geocha1962
@geocha1962 5 жыл бұрын
Do you know the current limit on the DC site for each ? Thanks George
@Rafaeljotiar
@Rafaeljotiar 4 жыл бұрын
48VDC input with how much wattage input to get high wattage ?
@tonyolomu11
@tonyolomu11 4 жыл бұрын
Hi morning I just wanted to know so if you can on couple a Sunny Boy 2000 W Solar PV grid tied Inverter 2000HF SMA SB2000HF-30 2KW. To a 15kw 48v power jack inverter, running the AC output from the inverter into to the AC input of the power jack inverter so that it can charge the batteries and also so run back into the power panel of the house please let me know and it is for the UK market thanks
@BonitaCreekWaterGuy
@BonitaCreekWaterGuy 6 жыл бұрын
I have a Aims 10kw 48v split phase that was working for the last 3 years. Three in the morning lighting hit somewhere close and took out the inverter. Does the Power Jack have surge protection? The Aims 10kw needs a 15kw generation and I have a 7.5 kw so I never hooked it up. What does the Power Jack require for a generator connection?
@GenetrySolar
@GenetrySolar 6 жыл бұрын
I can tell you that I accidentally sent the grid through my inverter and it roasted the breaker but the inverter was fine. They use 70 amp push button reset fuses that seem to work great.
@nsacrooks
@nsacrooks 5 жыл бұрын
What happened to the inverter carcass? I am an electronic technician. Might be interested in your blown inverter as a project.
@GenetrySolar
@GenetrySolar 5 жыл бұрын
Inverter carcass?
@nsacrooks
@nsacrooks 5 жыл бұрын
Did you repair your inverter? If not I'd like to attempt repair of it.@@GenetrySolar
@alexysortiz9683
@alexysortiz9683 5 жыл бұрын
What is the fan voltage rated on 5000w 24v powerjack? 24v? I can only took 3100w out of it before the fuse blow, upgrade the fuse??
@GenetrySolar
@GenetrySolar 5 жыл бұрын
Do you have a split phase version?
@alexysortiz9683
@alexysortiz9683 5 жыл бұрын
@@GenetrySolar nop, just 1 phase at 110v
@paywaldo2103
@paywaldo2103 5 жыл бұрын
I don't know much about these inverters, so take this with a grain of salt..... Do you know if the 5kw rating is peak or RMS? 5k/sqrt(2) = 3.5k which is close to where your fuse is blowing. Some companies boast a little on wattage (at least with speakers and amps), I have no idea about your inverter company. Still seems like you shouldn't be blowing a fuse though. I would contact the manufacturer and also see what they think. It's hard to say increase the fuse size, because something else inside could get damaged by the current that is blowing your fuses. some appliances draw in a large inrush of current initially and then average out much lower. not sure if that could be a cause. Good luck!
@SuperVstech
@SuperVstech 5 жыл бұрын
Alexys Ortiz my understanding of the 110v models is limited single circuit wattage . The fuse is likely seeing far beyond amperage due to induction surge. Motors pull much more watts than resistance loads.
@michaelbatchelder
@michaelbatchelder 4 жыл бұрын
Is Power Jack the brand? Can't find them listed, maybe out of business since this is a 2018 video
@faidularcs
@faidularcs 5 жыл бұрын
It's reviews!
@Migueldeservantes
@Migueldeservantes 5 жыл бұрын
Does the 2019 models have a higher voltage AC on the input?? I mean I would love to use the 48 but that would put me on a purchase of an extra set of 12 batteries of 2V "1100" amp batteries.. and that my friend is in the order of the 5K..... your advice will be greatly appreciated.
@BonitaCreekWaterGuy
@BonitaCreekWaterGuy 6 жыл бұрын
Is the 48v. split phase a pure sine wave? Have you tested the sine wave? I need 60 Hz and the Aims was a steady 59.7 Hz and no adjustment. Does the Power Jack have an adjustment? Does this have a bonded neutral or a floating neutral?
@GenetrySolar
@GenetrySolar 6 жыл бұрын
It is a perfect 60hz. It also has a floating neutral, however when connected to the breaker neutral it will share the bond. Floating neutral only applies to the outlets on the front.
@MMA.Indonesia
@MMA.Indonesia 2 жыл бұрын
where to buy it
@user-bi5sd4ct3s
@user-bi5sd4ct3s 4 жыл бұрын
This is a question from Japan Where is the product purchased from, for example, a website? Please tell me the site address. Please tell me the price Thank you.
@ImpalaSSRulz21
@ImpalaSSRulz21 4 жыл бұрын
EBay. Power jack inverter
@user-bi5sd4ct3s
@user-bi5sd4ct3s 4 жыл бұрын
This is a question from a Japanese. Where can I buy this product?
@huuqua8945
@huuqua8945 4 жыл бұрын
Please buy that inverter link
@harnamchand
@harnamchand 5 жыл бұрын
I want a 15 Killo Watt Inverter input 24 Volt DC To AC 220-240, 15000 Watts. How much Price US Dollars
@anazmy
@anazmy 4 жыл бұрын
Where can I buy inverters
@fredschreffler4869
@fredschreffler4869 5 жыл бұрын
How much does a 48 volt inverter cost
@daythunder1
@daythunder1 2 жыл бұрын
Seems like I bought my 12 volt power jack inverter for nothing. No way to upgrade my 12 volt to 24volt or 48volt... ☹️🙄😢 $$$ down the drain
@timturner6548
@timturner6548 4 жыл бұрын
Can carry amp better
@greatogbuagu1370
@greatogbuagu1370 5 жыл бұрын
Which is better, 48 volts or 24 volts and why?
@GenetrySolar
@GenetrySolar 5 жыл бұрын
48 volts will always be better. Less heat because fewer amps to get to 120 volts. Less strain on the inverter.
@gottamodify7756
@gottamodify7756 5 жыл бұрын
Is this a true 15kw inverter, and is it 7.5kw per side.
@GenetrySolar
@GenetrySolar 5 жыл бұрын
Yes true. At it's Max. I would stay closer to 6k per side max if you want it to run continuously.
@troy5007
@troy5007 5 жыл бұрын
Can you run the powerjack inverters in parallel? Thanks for your help.
@jec_ecart
@jec_ecart 4 жыл бұрын
Who the heck makes 15kwa in 24v???? They must be atleast 96v
@bernardotabaranzajr7652
@bernardotabaranzajr7652 5 жыл бұрын
What is the best brand of pure sine wave inverters that you can recommend to be used to light up the off grid house?
@elijahhannigan1475
@elijahhannigan1475 4 жыл бұрын
out back
@africantech5
@africantech5 2 жыл бұрын
Famicare
@victorrinz3753
@victorrinz3753 5 жыл бұрын
15000/48 presque 400amp les batterie vent exploser
@rynoopperman5010
@rynoopperman5010 4 жыл бұрын
I don’t understand the vid Spend all this time explaining why gas powered engine can’t be converted to a diesel engine... Why spend time on this?
@elixier33
@elixier33 5 жыл бұрын
Its clearly 220v not 240v! Its written on the front!
@mdnazmul-mianazmul1401
@mdnazmul-mianazmul1401 5 жыл бұрын
12v & 24v good..! 48v no good. How to make device 12v & 24v inverter system power supply. & 24 hour.! it's very important. I want this device to be make.!this Device 24 hour backup...? & full load.? Thank you guys. for this your watching.
@pogpogcasino
@pogpogcasino 5 жыл бұрын
Lol. The higher the voltage the lesser the current drawn. 48 or higher is best. 12 volt & 24 volt will be drained faster than 48 volts.
The New 8000W Inverter Much Better!
15:34
Going Off Grid
Рет қаралды 42 М.
Cute kitty gadgets 💛
00:24
TheSoul Music Family
Рет қаралды 21 МЛН
这三姐弟太会藏了!#小丑#天使#路飞#家庭#搞笑
00:24
家庭搞笑日记
Рет қаралды 119 МЛН
Power Jack 6000 Watt LF Inverter detailed look and load test
38:28
Genetry Solar
Рет қаралды 10 М.
Genetry Solar Company Update video.
25:01
Genetry Solar
Рет қаралды 497
Inverter Upgrade! Reliable to Aims in Off-Grid System
17:10
DavidPoz
Рет қаралды 757 М.
Let's talk about cheap inverters (48 volts)
38:18
HalenTech
Рет қаралды 17 М.
12 volts VS. 24 volts for Off-grid Solar Power Systems
12:42
DIY Solar Power with Will Prowse
Рет қаралды 1,2 МЛН
Exploring Low and High Frequency Inverters
11:40
Penn State Solar Center
Рет қаралды 96 М.
12V, 24V, or 48V Battery for Off-Grid Solar Power
9:41
Cleversolarpower by Nick
Рет қаралды 179 М.
Cute kitty gadgets 💛
00:24
TheSoul Music Family
Рет қаралды 21 МЛН