Why we need to transform the impedance of the line but the impedance of the grid is no considered?
@jaykesapalaran54342 жыл бұрын
Thank you for sharing your knowledge ❤️ very much informative and easy to understand 💌 THANK YOU...
@aljml6828Ай бұрын
how do you caclulate the 4000 mva in the first place?
@madhuvimal883 жыл бұрын
Hai.. Can you please validate with etap value.. What inputs have taken in etap and that particular input how to use in manual calculation..
@sandipkumarprajapati31892 жыл бұрын
Thank you Professor!
@DebjitDas934 жыл бұрын
In grid impedence calculation and Numerator in KV & denominator in MVA? How? If KV, then bring MVA into KVA
@Grx-z1b4 жыл бұрын
Very good explanation, but I have a question. Since both of the grid's and the 110KV line's impedences are behind the transformator, why did you only multiply the line impedence in square of "the transformation ratio" but not the grid impedence. I meant by transformation ratio U2/U1. Thank you.
@jfsimon19813 жыл бұрын
Hi, He calculated the grid impedence seen from 20 kV (20kV^2/4000MVA). Yes the units match in this case since kV^2=MVA. Jean-François
@jfsimon19813 жыл бұрын
Good day, Is ths is mistake at 4'04" Isc,3P = (20000/1.732)/33.47 = 345 A (not 605A) ? After calculating I found out different results: Short circuit level at 20 kV: 605 A -> 345 A Short circuit level at 400 V: 30 kA -> 17.25 kA Thank you, Jean-François
@willgould44172 жыл бұрын
I got the same result as you, think its a mistake
@sambathbunkh Жыл бұрын
Good explanation
@shabeerahamed15014 жыл бұрын
If we use cable which is connected to the transformers, we need to add those impedences in the SCC.
@noobzgamer43582 жыл бұрын
How if fault on bus 110kv before Transformator?
@arijitmahanta235 Жыл бұрын
I think there is calculation mistake during calculation of fault current at 20 kV side for fault at B. It is coming 345 amps not 605 ams
@mahmoud71424 жыл бұрын
Thankfully for highclass explain
@lythous4 жыл бұрын
Hi. I think you made a mistake in your calculations. I_FB = (20000 / sqrt(3)) / 33.47 = 345 A @ 20kV :: 17.25 kA @ 400V
@tomaszpiwowar76574 жыл бұрын
You right!
@atmsc4nd4l4 жыл бұрын
agree.
@Brandlead8 ай бұрын
605A at 110kV right not the primary of the 20kV,0.8MVA transformer?