I love this guy's videos. I was chasing intermittent lockout (once every couple days) on a beckett AFG for over 2 years. Did all the stuff, filter, screen, nozzle, electrodes, transformer. Motor replacement finally resolved the issue. I think someone with more experience than me would have gone to the motor quicker, because it was making a funny buzzing sound when it started up. New one doesn't do that and the burner starts up a lot quicker too.
@carlosumana91929 жыл бұрын
Steve - you were right. I checked the pump again by jumping out the FF and verifying the flow. My flow was ok for a few seconds and then dropped significantly. I proceeded to take the filter apart and check the flow at the shut off valve, it was minimal. I used a CO2 gun to blast air back toured the tank. I reopen the shut off valve and found the flow to be a lot stronger. I put everything back together and bled the pump. The system has been running fine since about 3:45pm today. Thanks again for your help, I truly enjoy your videos and learn a lot.
@stevenlavimoniere9 жыл бұрын
+Carlos Umana a good oil flow in important with oil very important
@elmerkreisel3967 жыл бұрын
Thanks Steve.i have the intermittent problem. Runs for a day or two and than it stops. Elmer
@chief20362 жыл бұрын
I just fixed my boiler thanks to this video. You saved me a bundle. Thank you so much.
@jerrysmith63482 жыл бұрын
Had 4 or 5 service calls because boiler would shut down every few days. We finally realized that if you hit the motor with a wrench, it would kick right on. Thanks to this video, I changed the motor, squirrel cage & coupler myself. Cost about $125. Thanks Steve!
@django2513 жыл бұрын
Thanks, I learn a lot from your vids and you have a quirky sense of humor that I appreciate. Mine was a damper getting hung up- used some sandpaper to clean around the bottom of the damper vent and then it worked fine. The damper was getting hung up on rust or debris. Over time the hinge pins of the damper wore down the holes on each side because of movement of the damper plate ,it touched the bottom of the vent pipe. I sanded the bottom edge of the plate a little too with some 80 grit paper so it moved freely. There's enough clearance now and it's running fine. I'm sure this isn't always the case, but it may help someone if that's what's causing it to shut down.
@lh982 жыл бұрын
The barometric damper caused a repeated fail to start or off on safety? 😳
@meganmcguinness92063 жыл бұрын
I have a similar system and am trying to learn as much as I can so I can troubleshoot small issues. THANK YOU for making these!!
@jeffreydunlap63825 жыл бұрын
Had the same issue with my burner. Replaced the screen which was all sludged up. While I was there replace the motor. Thank you for your help sir!
@markf350s6 жыл бұрын
Thanks for sharing Steve some of your knowledge Steve helps a lot of us out here with less knowledge about oil burners
@johnerway72552 жыл бұрын
Great job Steve, I do so much enjoy your videos. You sure put things in order and easy to follow alone as you do your magic. Keep safe my friend.
@sherrykoch34516 жыл бұрын
Video is very informative. Saved me untold hours. I wish all videos were this good. Thank you so much.
@dwaynes59832 жыл бұрын
Thank you for video. I came across lose wires. No springs in wire caps. Replaced them all and ran like a charm
@j.r.ferrerio99403 жыл бұрын
Hey Steve, I have a Gilbert &Barco oil fired hot air furnace that has been in operation since 1952. Same old burner assy. I rebuilt the fire pot once and rewelded parts of the rear a few years ago.. but it's still running.
@JeffreyJones-om6fx4 жыл бұрын
Very informative thank you for taking the time to do these. Wished I lived closer to you, you would be my HVAC guy.
@larryg71096 жыл бұрын
Ugh, I hate intermittent problems. They are so hard to fix!! Good job!!
@jamesfortier93943 жыл бұрын
STEVEN THANKS FOR WAHT YOU DOYOUR DOING A GOOD THING HERE. I have a basic af-10 beckett's oil burner with the same issue. I get oil from the pump, have changed out the controller and the cad cell. Ignighter looks good and electrodes also look good. I ordered a new motor to try next. I am in Maine retired from the military grew up in new bedford MA> Seen some familiar sights from you windshield in the videos. Thanks Bud
@johnthorpe45102 жыл бұрын
I've been a hvac service tech for 20 years now. 95% of the time when the burner trips out once a day or so at random times, change the transformer/ igniter & electrodes and takes care of it every single time. Except that tiny 5% lol. But that aside, I do like the videos you've done, at least someone on here seems like a real service tech. Thank you again.
@Beautyfull-t2s2 жыл бұрын
Thank you Steven for your generosity!!
@paullesogor20789 жыл бұрын
Thanks for sharing. I had an intermittent problem like this, and it kept tripping out. I checked the spark and it had decent spark at the transformer. But ultimately it was one of the newer digital style transformers that would work on and off. Also I had my thermostat programmed so temps went down at night, burner wouldn't fire much until morning, and it would lockout over night. Sometimes it would happen in a few days, weeks, and months. I replaced with an iron core / non-solid state style transformer as I think steve has suggested in other videos.
@BoilerTeardown9 жыл бұрын
Paul Lesogor Yeah the intermittent spark cant blaze through small inconstancy in oil flow. Might have a small vac leak or other crud. A tiger loop is a fine addition when converting to an intermittent spark.
@stevenlavimoniere9 жыл бұрын
Paul Lesogor i have a lot of problems with them electronic transformer i will not buy them anymore
@wackpackxj2 жыл бұрын
Oddly comforting to listen to you breath through your nose while you’re working. Reminds me of being beside my FATHA when I was a kid while he was fixing something or OTHA.
@chopdig882 жыл бұрын
Te
@garyg68202 жыл бұрын
😂😂😂
@garysgarage.28412 жыл бұрын
You should hear the noises he makes dropping a Deuce.
@slashmetaldetecting7 жыл бұрын
I have gotten the same issue going on and it's like below zero all this week up here in Maine and it looks like my furnace needs a motor to hopefully it's not too costly thanks for the video this to help me a lot now I know what the issue is I've taken apart my furnace before and cleaned it it might be the tip but by looking at my motor it looks like it's really old
@bigdog45745 жыл бұрын
any updates on solution?
@adamcraig15682 жыл бұрын
Thanks Steve for the helpful videos
@chrismemphis80625 жыл бұрын
This past week, my snowbird in-laws 1996 Miller hot air unit with Beckett was tripping out when no one was around. They had 'a guy' come and clean it. He seemed knowledgeable. Same problem came back, so he said the motor was making noise and was too buys to come back soon. I looked at it and figured I could change it, and the oil pump was definitely squealing, so I changed that instead along with the filters and nozzle. Squealing went away, but same problem shutting off, so I changed both the motor and primary- I put on a Carlin- very nice unit, and also new transformer and electrodes. I even put 2 bottles of hotshot in and recirculated the oil in the tank with a pump. The primary would flash green for a little bit, then go solid and run. But the same problem came back, would run all night the off again in the morning. Turns out the f*cking guy who cleaned it opened the air setting way to far- almost all the way, and was blowing out the fire. I had no Idea as to how much that made a difference. What a f*cking $nightmare$. But I sure learned a lot- try the free adjustment stuff first!!
@dklucas19 жыл бұрын
Great Job Steven That's why i like your videos,you are very professional
@stevenlavimoniere9 жыл бұрын
dklucas1 thanks for the connent
@v2danfo Жыл бұрын
Steve ... would a bad themastat cause such issues ... intermitent ? .. had service callls .. replaced pump nossle etc .. last thing they replaced was the digital themastat... no issue after that ...
@bobisthebuilder39827 жыл бұрын
Im not sure if anyone said this yet but when checking the spark make absolutely certain the handle doesn't have any cracks. I got blasted by a transformer due to a hairline crack. There is more than enough voltage to kill you dead right there. Luckily for me i was using a screwdriver intended for high voltage work.
@aaronnel83647 жыл бұрын
Hi Steven, I certainly appreciate what your doing with your videos. I have learned how to check a transformer and have replaced that. My parents have an old Heil oil burner that I am trying to get running for them. The have been space heating for the past few years and with a large house that just not enough. When I turn on the breaker the Furnace will fire right up and run a whole cycle bringing the house up to temperature. When the thermostat triggers it to start again it will turn on the blower for the burn chamber and fuel but no ignition. Every time I allow the heater to go 20 mins or so without any electric and then turn the breaker back on it fires perfect. What should I look at next
@robertdimeglio71555 жыл бұрын
Bet your OIL Supply line was partially clogged! The time you waited allowed the line to fill back up!
@snailsalad2 жыл бұрын
I can’t get my copper fuel line from the pump to the burner to stop leaking fuel at the burner, where it screws into the igniter. Tried tightening it leak got better but still there, think I need to replace the copper line?
@redpine8665 Жыл бұрын
Had a similar issue. It has an oil heater on the nozzle assembly unit. The wires for it were partially obscuring the view of the photocell that looks for fire.
@robertmattison12826 жыл бұрын
Excellent video you posted on KZbin on know it 2018 but just found. Thanks
@kingcreo27609 жыл бұрын
Those streams looked pretty good Steve. Sort of like me after a night of drinking. Lol. Nice job as usual.
@stevenlavimoniere9 жыл бұрын
Kyran Speiser thanks for the comment
@heyitsantman4 жыл бұрын
Im sericing mine own heater and the money I save just trying to figure it out. So far switch and nozzle and it ran fine for 24 hours now it shit off faster. Motor looks easy enough plus my brother does this kind of work and I just have him on what's app t see what I'm doing. Great video I have been telling him that the motor sounds like the fins are worn.
@TheCleaner6969 Жыл бұрын
I just had my furnace cleaned. Told the guy it tripped once. He tested the transformer with a screwdriver said it was good. That was a few weeks ago. Now it tripped 2 more times & he wants another service call. I have a relay on the pump the control is a Honeywell R8184G4009 which is old. When I press the reset button it clicks fast the furnace will run & stay running for weeks. The motor is 11 years old. Any ideas?
@777wrench Жыл бұрын
Enjoy watching your videos. I have a question to ask you. Can a fuel pressure gauge be installed permanently on the the fuel pump? One could simply tell a glance as to the output pressure anytime.
@soving4 жыл бұрын
I only know enough to be dangerous but wouldn't checking the flame sensor and igniter control box be before changing the motor? I would have guessed a flame sensor or fouled probes..
@richardcarver53562 жыл бұрын
My fuel oil is coming out frothy. Pump is a year old. Tank is above boiler. Can't figure out why fuel is doing this. Checked flare nut at tank appears good( out of top of tank). Would sludge do this? Wondering if I should blow the line back to tank.
@torreshondaguy3 жыл бұрын
where would you start if you oil flow has air in it it seems like my oil flow has air in it boiler runs but trips and restarts itself right away
@whommee9 жыл бұрын
good video,, sort of like when you take your car with a squeak to the mechanic and when you get it there it dont squeak no more. hope you got it ,, good job good vid bet you like the challenge of diagnosing those "hidden problems"
@stevenlavimoniere9 жыл бұрын
nate its fixed i call the guy a few days later all is good
@twistedambitionz4 жыл бұрын
steven lavimoniere let’s be honest, it was because of the replaced coupler and not the motor. Motor had a manual reset overload. If that were intermittently overheating like you suspected. That would trip. Not the primary control
@abdulrabah22795 жыл бұрын
I have the same issue with my oil burner. it trips frequently ( 2 to 3 times a day). my service guy replaced oil filter, nozzle, motor and the trip relay box and cleaned the fuel line. nothing changed the furnace still tripping. i am tired of calling this service guy and i am thinking to change him. and advice to why i have this issue. According to the service man the flame looks good no black smoke bump is good. so what the heck is wrong with my furnace help please
@notajp5 жыл бұрын
Could be weak transformer, dirty or weak cad cell, dirty/misadjusted electrodes, or low fuel pressure. Time to find a better service guy.....
@chuckerroo59775 жыл бұрын
My furance didnt trip and came down to forty gallon oil on the floor any idea why this would happen?
@jpz60725 жыл бұрын
air in the fuel line? does your fuel line goes up then down to the furnace? Replace the transformer and electrodes first.
@bigdog45745 жыл бұрын
Ever figure out what the issue was?
@croyal42405 жыл бұрын
Did he replace the ignition transformer,it could be weak and causing it to shutdown every couple days.Burner might start with delay ignition sometimes
@YouBetterPreachАй бұрын
Another great video Steve! My HVAC guy Cleaned my Boiler/Furnace 2-3 days ago, but now its shutting of after about a day. I hit the reset button and same thing works for about 1 day. Could it be something as simple as the Cad Cell? I have a Beckett oil burner also. Thanks!
@lh982 жыл бұрын
Did the motor swap actually fix this issue? I don’t see an update. Was it off on safety or just fail to start? Primary control with intermittent issues can be a challenging cause to diagnose too
@bigdog45745 жыл бұрын
Hi folks, had same issue, reset would trip once or twice per day. When I press the reset, the transformer would whine, def had the spark, felt the motor and noticed it was getting hot on one side. Next time this happened, I spun the blade then pressed the reset, no more whine and motor starter spinning. So no I knew the motor was the problem (original motor). Of course, I already changed all the filters, screen filter in the pump, checked flow, cleaned electrodes and spray nozzle.
@jjjohn59142 жыл бұрын
Steve..as a follow-up....did it solve the problem...no callback to fix again?
@donnierobertson30883 жыл бұрын
Great job and video like always
@DeanQLQPasa3 жыл бұрын
I too have a similar system. My tank is outside and i believe that because there is a lot of sludge in my tank and my tank is under the ground. Is there any cleaning solution that i can use perhaps once a month that i can pour into my tank outside?
@maulrat5883 жыл бұрын
How is the motor bad if it's running? From getting warm? Diagnosis by replacement??
@paulgraham63535 жыл бұрын
You are the best...and your little dog too !
@egold10062 жыл бұрын
I notice you do not use the gasket provided with the Allanson transformer, I once forgot to install it and lived with a low level hum for a few days. It actually resonated through the house.
@OLLIM505 жыл бұрын
Hi Steve I've been without heat for several days, I have a Beckett similar to this one on the video. My oil furnace trips out every 1-4 minutes. I have had done a tune up, new pump, in 2017 got a new tranformer, nozzle system have been cleaned, cad cell looks clean and reads well, lines have been bleed, it come out good and red I even placed a new reset box, but still trips out. The only thing I see that is left it's my motor. My motor starts and burner flames right away. My motor reset button popped out once but continued to start after I pressed the reset. However seeing this video it seemed like the motor started aswell and still the motor was bad. I need help not sure what to do, I even hard wired the motor for approx 2 min, to see if it tripped out and it didn't dont know if I should of hard wired for longer, but however I NEED HELP!!! Love your videos Steve il wait your response. Thanks God bless!!
@stevevinas5 жыл бұрын
Update?
@genecurrivan2799 Жыл бұрын
And? What was it?
@OLLIM50 Жыл бұрын
@@genecurrivan2799 well after all that, can't believe it has been 4yrs already, thanks for your response 🤣, but a tigerloop fixed all my problems 🙋♂️
@StreetSceneLive3 жыл бұрын
My system was just tuned up a month ago. The last couple days I have to hit the reset button to get it to fire up... It runs fine... Later when it cools back down it doesn't kick on automatically like it should via the thermostat... So I gotta go hit the button again... Again, runs fine after this... What is my problem??
@stevenlavimoniere3 жыл бұрын
call back the guy that just did the service
@harrydickson45759 жыл бұрын
Another fine job Steve thanks for sharing!!!
@stevenlavimoniere9 жыл бұрын
Harry Dickson thanks harry my friend
@garynair5143 Жыл бұрын
Mine tripped b/c the start/run capacitor blew so when the burner started , the load line set temperatures kicked in and told the unit to shut off, as the main fan wasnt running. I could start the fan by hand when a load line run temp allowed it. Was a beast to troubleshoot, the oil tech company set out changed filter, cad cell, oil nozzle, ait filter, was starting to look like parts cannon fixing. So after watching some videos it was the blown capacitor.
@kathyfish71453 жыл бұрын
We have same oil burner type unit. It works when the tech is here then after he leaves and temperature gets up then it shuts off after it tries coming back on it won’t light. What could be the problem
@garyg68202 жыл бұрын
You’re the best on KZbin!!!!! Thank you
@michaelpadovani95669 жыл бұрын
What's the difference between the AF and the AFG Becketts? And which do you prefer?
@stevenlavimoniere9 жыл бұрын
Michael Padovani the fan is different af has a wide fan . afg as a small fan buy plastic housing to help with air flow
@k2blah-blah-blahski6 жыл бұрын
@@oharedwa7792 some times the ohms and amp draw is normal. But a bearing starting to go bad can heat up and cause drag on the motor. Once that happens, amps will rise, but you need to be there to catch it. That will cause the motor to over heat and shut down. Once everything cools down and the OL resets, all is normal again for a little while. Although I agree checking amperage draw and ohms is standard procedure, it won't ALWAYS reveal an intermittent problem.
@twistedambitionz4 жыл бұрын
If the motor has a manual reset overload. Why would you think it’s the motor without that overload being tripped?
@jandk1987 жыл бұрын
Very helpful videos. Did you use Carb cleaner on the electrodes?
@suziejohnson98637 жыл бұрын
I am taking the tank out of the ground, the new tank will be a gravity flow system to the burner, should I have a one way valve between the tank and the burner in case I have a leak so it won't drain all the fuel out of the tank in my garage? If I do what kind of valve and where are they sold?
@ShyboyMike Жыл бұрын
so was it the motor or what?
@cnn940013 жыл бұрын
my blast tube get oil and it drips down to bottom of the burner and motor. I did all, replaced the nozzle, set the electrode, but keep seeing oil at the beginning of blast tube. I can't really tell where the oil's come from, but I do see it. Any suggestion?
@garrettjay64148 ай бұрын
I have the same problem right now, good oil flow, cleaned the screen in the pump, checked cumtomers replacement of fuel filter.. power to transformer but no spark and no psi on water, feed and backflow dead. 1st visit new transformer, nozzel, and water feed, fixed the customers' shotty install of new electrodes. Second visit replaced the controller to new smart controller from old. 3rd visit to be seen but I'm going flipping crazy over hear. Already eating 170.00... 😢
@joepiol51054 жыл бұрын
Igniters also can quit when they heat up, then start working again when they are cool. That igniter seemed to be an old one.
@arniegrote3199 жыл бұрын
Hope you got it Steve, Intermittent problems SUCK..
@stevenlavimoniere9 жыл бұрын
Arnie Grote this fixed the problem i was right about the old motor
@killingsworthjeffrey3 жыл бұрын
What's that red button on the blower motor?
@adamantvermont Жыл бұрын
How much is the motor?
@albahroe129 жыл бұрын
Did you install a used motor and blade it looked old
@stevenlavimoniere9 жыл бұрын
albahroe12 it was a new motor with a blade on it . i installed on another job i didn't need but it was new .
@carlosreis46264 жыл бұрын
steven lavimoniere so was it the motor that was bad did you ever get a call from the customer again
@kennyplay59824 жыл бұрын
What was it then? Was it the motor? Thx
@JohnDoe-ne9oc6 жыл бұрын
Rite under Neath that box rite there mines leaking any suggestions
@superdutyscaler68236 жыл бұрын
Why didnt you use a control or flame detector tester?
@gundamrx7925 жыл бұрын
Did the motor repair solve the issue?
@tamalodg1963 жыл бұрын
Yeah the newer style "solid state" ignition transformers are a pain in the ass because they get intermittent... Like they work then they dont and usually 95% of the time it's a intermittent transformer. We have a F3 Beckette model with the 51771U ignition transformers get intermittent with our furnace. We have had to replace them every 5-10 years. We have gotten now so we always keep a spare on hand since they go up so frequently.
@byron25213 жыл бұрын
I saw someone ask the same question I was going to. "can you use carb cleaner to clean those electrodes?" Don't see why not.
@keithrichards68169 жыл бұрын
Enjoyed the video.. my question is can the motor run outside the boiler and check amperes?
@danielebbeling66485 жыл бұрын
Was the turbulator crusted ?
@keithsheppard5107 жыл бұрын
I'm here trying to get my boiler back on. I'm locked out, reset button stays yellow, it's a new motor and reset. need help thank you
@braidensunday10757 жыл бұрын
Keith Sheppard hold reset for 45 seconds
@kjhnsn7296 Жыл бұрын
I had this issue. Turns out it was caused by my burners power vent system. An overgrown shrub was interferring with the vent exhaust flow and intermittently tripping the safety and shutting down the burner. Trimming back the bush fixed the issue.
@kennyplay59824 жыл бұрын
How much is a replacement motor cost? Thanks
@drcajundan3 жыл бұрын
~$80
@carlfowler3151 Жыл бұрын
My furnace won't come on unless I tap the ignition coil primary
@Nomadahtous5 жыл бұрын
just had a brand new beckett installed and something not quite right...bled it and it fires up nice then runs a long cycle and shuts off...wont start back up unless its bled again...been going on all week. I am getting white fuzzy air in line...bleed it clean fire it up same thing...runs a full cycle shuts off wont fire back up unless bled. all new filters and gaskets on tank end. acts like its getting air from somewhere or a pump issue . I also bled filter at tank so its not that end of things. like pump not holding prime.only thing i havent bled is that short line at pump.
@Nomadahtous5 жыл бұрын
blows great heat while its running. but appears to run to long before cycle quits is another observation
@andygold5 жыл бұрын
I'm having the same exact problem, except possibly for the overrunning issue. This all started after the hot water heater was replaced. Trips daily. Reset either lights and then times out and shuts off, or it won't light until I bleed the line (lots of foam at first). After a bleed, it seems to stay on I believe 100% of the time. I see no leaks which I figure would show where air is entering the lines. Plumber says there's no nozzle shut off on my system (heard another video talk about some form of nozzle shut off that prevents air from being sucked in at the nozzle when the system shuts off), but I don't have that. Can't figure where air is entering the system.
@Nomadahtous5 жыл бұрын
I replaced the re-set box with red button and that resolved the problem... it was mind boggling up until that point
@Nomadahtous5 жыл бұрын
I’m learning that this boxes are sensitive and any major work jostles it around you might as well replace it because it’s going to act up
@TheSpo964 жыл бұрын
I’m watching this with a problem of my own. My burner runs fine. Then when it’s calling for heat, it circulates, gets the water jacket up to temperature and then turns off the burner. Then it goes to turn the burner on again, but the water is still hot enough so it shuts the burner off again. Then it times out. Is it a bad (sticking) relay or aquastat?
@stevenlavimoniere4 жыл бұрын
its call a high limit thats the way it should run . boiler only need to be so hot .when the boiler shuts of on high limit the circulator will keep working till t stat is happy
@TheSpo964 жыл бұрын
@@stevenlavimoniere so the high limit seems to be working correctly. I’m having the issue where when the burner turns on but is then shut off almost immediately because of the high limit. Then the relay light kicks on after 45 seconds. It seems that the eye is still looking for the fire but the motor isn’t even running. Bad relay? It never happens for domestic hot water. Only for heat from zones.
@stevenlavimoniere4 жыл бұрын
@@TheSpo96 best to call a local service tech to look over your issue . i can not tell what your issue is over a email ..
@drakkorvladimir40125 жыл бұрын
Turn on closed captions and tell me what it says at 5:54.
@colleenoloughlin39705 жыл бұрын
"Check the drawer assembly " said with a Massachusetts accent.
@jeffreyperrigo25184 жыл бұрын
steve I want to change over to anew AF#9 can't find one will a #10 work?
@craft01455 жыл бұрын
The first motor had no capacitor dome on it. The new motor had a capacitor dome. Why? Which one is better?
@erikj.20664 жыл бұрын
Old motor uses a start capacitor with a set of contacts that open, dropping the cap out once it gets up to speed. New motor is the revised PSC style that’s supposed to be more efficient, and doesn’t have contacts to jam, or wear out.
@Chane91719576 жыл бұрын
squirrel cage keeps sticking...how do I know if it's the motor or the pump?
@paulg4446 жыл бұрын
He just seems to know what he is doing ! It is as if he has been doing this for a long while!
@lisalambert16897 жыл бұрын
how do I buy Beckett parts? wholesalers and contractors Will not sell to me.
@rutherglen72265 жыл бұрын
I found some on Amazon..
@Yatsevitch6 жыл бұрын
I don't understand why the motor is bad yet still runs. My burner flames on and burns well, but after about 30 minutes the reset button pops out. If I wait a few minutes, it restarts and then runs for less time and then the button pops out again. I changed out a faulty oil pump and now that works well. The spark is strong and there is a new nozzle. So it comes down to three issues: the motor, the reset controller or maybe the aquastat attached to the boiler. Any ideas?
@bigdog45745 жыл бұрын
If oil filter and screen filter in oil pump are clean, check/change electrodes, clean/ change nozzel, clean/change eye cell, if all that fails --> change out reset controller, I would do motor last.
@bigdog45745 жыл бұрын
did you ever figure out what the issue was?
@QUIETMONEYPRODUCTIONS7 жыл бұрын
Steve was it the motor? I am going through the same thing but every day.i have changed everything except the motor?
@fernandoledesma27806 жыл бұрын
QUIET MONEY PRODUCTIONS technicians couldn’t figured it out,in the end it was a bad motor!!!
@hugoariaslivia16897 жыл бұрын
sera de gran utilidad esta demostración. en lo cotidiano.
@carlosumana91929 жыл бұрын
Hi Steve, my burner is tripping out every ten minutes. The pump is working (plenty of flow), I replaced the transformer, nozzle and electrodes along with doing the annual cleaning this summer. What do you think is kicking out the the burner? From this video it seems like it might be the motor...
@stevenlavimoniere9 жыл бұрын
+Carlos Umana what it and see what it does could be a pump. sometimes its running to lean can do that . every 10 minites i would have to be there looking at it to make a ruling on it
@lfdvidinc7 жыл бұрын
Just curious , I’ve noticed in a few videos , do you like to clean off the brass and the area under the nozzle adapter??
@char05077 жыл бұрын
always great video and appreciated
@howardiko71565 жыл бұрын
Where does the air come from. The loovers are closed all the way.?
@erikj.20664 жыл бұрын
Shutter under the pump is also adjustable for air. Band is used for larger nozzles.
@MegaCyberleader2 жыл бұрын
when it works when you are there and not work when you are gone, is called Technicians syndrome. Goodness knows I know . I feel your pain :P
@dansweeney109 жыл бұрын
Good job Steve! What would a cracked porcelain do to the operation?
@stevenlavimoniere9 жыл бұрын
dansweeney10 affect the spark from getting to fire the oil
@chipper4425 жыл бұрын
Hello Steve. Quick question. I was told by my tech, that the transformer continues to arc throughout the burn cycle. I said I didn’t think so, but figured I’d ask the pro. Wouldn’t that transformer overheat running all that amperage constantly? Doesn’t the CAD cell recognize flame and A.) keep the pump on, and B.) stop the “arc” needed to ignite the fuel? Thanks for the informative videos, I’m late to your channel but slowly catching up on the content.
@blackmanops37494 жыл бұрын
The newer "Intermittent Primary Oil Ignition" (aka. relay box) have the arc cut-out capability (marked by separate wires to the motor, valve, transformer). The older relay boxes like the Honeywell R8184 that have only three wires (black, white orange) are always on (easily confirmed by the fact there is only one wire (orange) that powers the motor, transformer and valve). Just went through that exercise 2 weeks ago.
@lh982 жыл бұрын
Transformer puts out high voltage 10,000 volts to 14k depending on model but they aren’t high amperage which would create a lot of heat. They don’t get hot like you’re thinking..
@richmurphy209 жыл бұрын
Great job Steve. I've been reading the comments here and people blame the electronic igniters. the older callin electronic igniters had a built in thermal overload that would trip than it would reset itself.
@stevenlavimoniere9 жыл бұрын
RICH Murphy i do not buy or use electronic transformers any more .had a lot of problems with them
@mr.b96509 жыл бұрын
Nice video Steve! You the man..
@stevenlavimoniere9 жыл бұрын
***** this one was a bad motor
@gmoneyga849 жыл бұрын
steven lavimoniere was the homeowner hitting the reset when it would trip out? what about the reset on the motor? was it overheating?
@stevenlavimoniere9 жыл бұрын
gmoneyga84 no the rest on the motor did not trip just the protector relay and yes the homeowner did reset it
@TheBergy329 жыл бұрын
Looks good, see what happens...
@stevenlavimoniere9 жыл бұрын
Jordan Berghaus nothing surprices me
@susieh21006 жыл бұрын
I'm looking at this Video because my Boiler has been trying to fire up for the past 30 minutes without staying lit. What is going on!?
@bobobyfour7 жыл бұрын
Thanks Steve, great video, what is the orange piece you put over the nozzle to check the position of the burner called?
@scottunknown42446 жыл бұрын
Its a z gauge for checking the z dimension on the burner