Connecting a power logger to a LIVE 600A 3 phase fuse board | REC004

  Рет қаралды 12,944

Residual Electrical

Residual Electrical

Күн бұрын

Пікірлер: 46
@petehiggins33
@petehiggins33 Ай бұрын
A reactive load of -3.5kVAR corresponds to a capacitance of about 200uF hanging directly on the mains. It's a big capacitance and I can't think of anything that would do that, so I suspect that there might be a faulty grid tie inverter connected which is failing to match the phase of the supply. It might be an idea to repeat this measurement at night when there's no solar power.
@residualelectrical
@residualelectrical Ай бұрын
Check the latest video, it looks like you’re correct!
@we-are-electric1445
@we-are-electric1445 Ай бұрын
Unless there is a lot of electronics connected you would expect (on balance) the load to be more inductive rather than capacitive.
@three-phase562
@three-phase562 Ай бұрын
Interesting that the VAr reading on the first PEL was negative indicating a capacitive load rather than inductive. The second PEL to the plant room was showing inductive VAr, 0.9 pf is pretty respectable for motor plant. Would be interesting to see what the pf closer to the intake is, as the capacitive loading should counteract the inductive loading. For connections into boards like this I have a set of fly leads made up with 4mm safety sockets on them that connect direct into the leads to save taping the crocodile clips in place. For Red Spot fuses, I have a set with the 4mm sockets built into the fuse carrier.
@residualelectrical
@residualelectrical Ай бұрын
Nice, can you send me some pics of those? They sound great!
@retozaugg3775
@retozaugg3775 Ай бұрын
You said that there is a bit of PV connected to the board with the bad power factor. One time we had a case, where the inverter was faulty. It produced a huge apparent power and was tripping the 25 A fuses, but the meter only read a few amps active power.
@tangojango44
@tangojango44 Ай бұрын
If the load and generation are closely matched, then irregular power factors are quite common. It would be worth turning off the solar and re-checking those readings. Though at 5pm you wouldn't expect much of an influence.
@gokugeorge011
@gokugeorge011 Ай бұрын
I will be very glad if you can make me your apprentice 🙏🙏 ..i have a electrical backround.
@gokugeorge011
@gokugeorge011 Ай бұрын
I will be very glad if you can make me your apprentice 🙏🙏 ..i have a electrical backround.
@001Elan
@001Elan Ай бұрын
Hey Mike great vid mate followed since you started , so thought I’d kindly point out …. Wearing your arc flash is a good example to the majority who don’t, but without your balaclava it’s fairly irrelevant, your head is well within the theoretical arc flash zone which means second degree burns if all goes up ! On hands that’s a problem , on your neck and face ??!!! Please take care , keep safe
@residualelectrical
@residualelectrical Ай бұрын
Thanks elan!
@Ash-gw2bk
@Ash-gw2bk Ай бұрын
We love to see it I told you I’d be back 👌
@John_Faultless
@John_Faultless Ай бұрын
Great video mate. It's really good to see someone explaining the potential losses due to low power factor. Look forward to the results 🫡
@residualelectrical
@residualelectrical Ай бұрын
Thanks John!
@russellslater4037
@russellslater4037 Ай бұрын
Fantastic, I've finally got my head around PF. Thank you, thank you, thank you.
@residualelectrical
@residualelectrical Ай бұрын
Glad it’s helped!
@Ronny86_
@Ronny86_ Ай бұрын
Nice video Mike! Looking forward to the next one
@residualelectrical
@residualelectrical Ай бұрын
Thanks Ronny!
@rcoombs100
@rcoombs100 Ай бұрын
Hi there, thanks for the vid. What size fuses did you replace the originals with when you powered up?
@lewisbrand
@lewisbrand Ай бұрын
Most LED luminaires are around 0.8 power factor or less.
@_eusty
@_eusty Ай бұрын
5:53 made you jump!
@0liver0verson9
@0liver0verson9 Ай бұрын
huh?
@ShalomBrother
@ShalomBrother Ай бұрын
Your shaping like your disarming a 💣
@residualelectrical
@residualelectrical Ай бұрын
Search and destroy 🪖
@Fishfingersarnie
@Fishfingersarnie Ай бұрын
Any plans for a BMS? would save all of the confusion in the future and allow for live readings at any point.
@residualelectrical
@residualelectrical Ай бұрын
Sure would, I don’t think they would install one though.
@0liver0verson9
@0liver0verson9 Ай бұрын
Very interesting stuff. So it's possible a supply can alter the cost of electricity? Or is the "power factor" related to something else? I work with meters and obviously some customers dispute meter reads and bills. This usually results in a 2nd check meter being installed to run concurrently. I wasn't aware of other factors on the supply side that alter bills, if that's what you're investigating.
@Ronny86_
@Ronny86_ Ай бұрын
It’s to do with real power and apparent power. Basically the property is wasting electric that could be used but instead it’s not. It’s nothing to do with the meter side of things but more the equipment using the power. And power factor isn’t really used in domestic properites
@0liver0verson9
@0liver0verson9 Ай бұрын
@@Ronny86_ ok thanks, all good to know
@cameronmantell9959
@cameronmantell9959 Ай бұрын
@@0liver0verson9 Yea, Ronny is right: nothing to do with supply but depends what loads are installed. Inductive loads like induction motors will lag the power factor by nature, dropping the power factor. Lagging power factor reduces real power, but the supply company still needs to pay to transport the total current (real + reactive). They are only concerned with VA through the lines, so they effectively charge you more than the real power you are using. Only really applies to commercial properties that would have lots of inductive loads (e.g. lots of induction motors)
@0liver0verson9
@0liver0verson9 Ай бұрын
@@cameronmantell9959 Well I just learnt something! Cheers
@scotchy88
@scotchy88 Ай бұрын
Im surprised the supply authority hasn’t come knocking on their front door!
@Uk_Grid_Engineering
@Uk_Grid_Engineering Ай бұрын
This is the issue with solar, tye inverters are all designed to produce a perfect power factor, when a prem has an amount of reactive power and an amount of real power, the solar can offset the real but cannot change the reactive, that remains constant, hence why the oower factor is worse with solar
@residualelectrical
@residualelectrical Ай бұрын
Just read the white paper, thanks man!
@cliveramsbotty6077
@cliveramsbotty6077 Ай бұрын
does direction of flow matter when im using my clamp meter to measure current?
@MrMaxyield
@MrMaxyield Ай бұрын
AC amps and DC amps should be measured separately... There are 2 separate positions on a meter to measure each one respectively...
@three-phase562
@three-phase562 Ай бұрын
He is measuring power, so the meter needs to know the direction of the current to differentiate between exporting an importing electricity. Hence the clamps have a direction arrow, so you put them all in the same direction. For normal clamp use on AC to measure current only, it doesn't matter quite so much.
@ShalomBrother
@ShalomBrother Ай бұрын
No
@cliveramsbotty6077
@cliveramsbotty6077 27 күн бұрын
@@three-phase562 thanks
@we-are-electric1445
@we-are-electric1445 Ай бұрын
That 0.33 PF looks suspicious !
@walseee
@walseee Ай бұрын
BOOOOSH
@hvsparky
@hvsparky Ай бұрын
Great video pal 💪🏼💪🏼
@residualelectrical
@residualelectrical Ай бұрын
Thanks mate!
@1992Craigster
@1992Craigster Ай бұрын
Noice
@samuelchamberlain2584
@samuelchamberlain2584 Ай бұрын
Crap led drivers ?
@residualelectrical
@residualelectrical Ай бұрын
Possible, but the PF is a lot better at night so can’t be those alone!
I power logged a whole building for a week - This is what i found | REC005
32:52
Switching 11kV VCB Tamco
7:34
competence 33kv
Рет қаралды 2,5 МЛН
小丑揭穿坏人的阴谋 #小丑 #天使 #shorts
00:35
好人小丑
Рет қаралды 45 МЛН
СОБАКА ВЕРНУЛА ТАБАЛАПКИ😱#shorts
00:25
INNA SERG
Рет қаралды 3,2 МЛН
Smart Sigma Kid #funny #sigma
00:14
CRAZY GREAPA
Рет қаралды 106 МЛН
Palestra Graphica 2024
1:19:06
Prograu FAUrb UFPEL
Рет қаралды 372
Terminating a 630A 3 phase supply
25:46
Residual Electrical
Рет қаралды 9 М.
£20,000 electricity bill? Lets investigate why | REC003
18:55
Residual Electrical
Рет қаралды 16 М.
Installing my favorite 3 phase distribution board
27:35
Residual Electrical
Рет қаралды 61 М.
GUESS WHO'S BACK! | Thomas Nagy
22:31
Thomas Nagy
Рет қаралды 35 М.
Commercial electrical fault finding
33:50
Residual Electrical
Рет қаралды 22 М.
Large Diesel Generator - Shuts Down With An ERROR | Can I fix It?
19:31
Don't Get Burned by MC4 Solar Connectors
13:41
eFIXX
Рет қаралды 190 М.
Working in a 2000A widow maker
58:52
Residual Electrical
Рет қаралды 349 М.
小丑揭穿坏人的阴谋 #小丑 #天使 #shorts
00:35
好人小丑
Рет қаралды 45 МЛН