FAST fix for NON-WORKING furnace with clogged p trap or closed pressure switch reading

  Рет қаралды 157,334

Fast Fix

Fast Fix

Күн бұрын

Пікірлер: 53
@maksshepherds
@maksshepherds 10 ай бұрын
THANK YOU, THANK YOU, THANK YOU!!! We are in Minnesota, and it is WAY below zero today. Of course the furnace was blinking a 31 pressure switch error and we had no heat. Thanks to your video, we now have heat! The furnace was dry and not draining at all. Hooked up the shop vacuum and the drain hose was plugged. Got a LOT of water! All good now and works great! Our family thanks you!! We subscribed!
@FastFixYouTube
@FastFixYouTube 9 ай бұрын
I’m glad to hear that! Your situation is exactly what I experienced and I’m happy my video is helping folks stay warm in these sub-zero temps! I’m glad to be reading this and thank you for taking the time to share. Appreciated! 👍👍😂
@Paradigm1976
@Paradigm1976 6 жыл бұрын
Excellent vid, saved the day here. The 3-1 code was flashing, powered off, unhooked the pressure switch tubes, and vacuumed...Bingo! I have a working furnace again. Thank you, sir.
@FastFixYouTube
@FastFixYouTube 6 жыл бұрын
Paradigm1976 you betcha! Glad the video was of some help.
@drscopeify
@drscopeify Жыл бұрын
Thank you!!!! I have Rheem and got the code 5-9 and I looked over the P-trap but it looked fine however it was not, I watched your video, cleaned the P trap and all kinds of gunk came out, do not trust just looking at it, the yellow/white color can hide all kinds of junk inside.
@FastFixYouTube
@FastFixYouTube Жыл бұрын
Glad you got it figured out! And good tip 👍
@sfigueroa0825
@sfigueroa0825 5 жыл бұрын
Excellent video thank you very much... My furnace had exactly that same problem.. p trap was dirty as hell.. cleaned it and my furnace fired right up.. thank you....
@FastFixYouTube
@FastFixYouTube 5 жыл бұрын
Salvador Figueroa you are welcome! Thank you for the comment 👍
@rimdacinah6384
@rimdacinah6384 4 жыл бұрын
Excellent video thank you very much. You just saved me at least $300.
@FastFixYouTube
@FastFixYouTube 4 жыл бұрын
You are welcome!
@pbapromos5488
@pbapromos5488 2 жыл бұрын
You are a lifesaver! Thank you!
@FastFixYouTube
@FastFixYouTube Жыл бұрын
You bet!
@BradhallhavasuAz
@BradhallhavasuAz 5 жыл бұрын
thank you for the info your the best straight for ward easy as pie guy that is on you tube to learn from
@FastFixYouTube
@FastFixYouTube 5 жыл бұрын
Bradley Hall you bet! I appreciate the comment 👍
@TiminNicaragua
@TiminNicaragua 10 ай бұрын
I get the condensation build up in the trap, remove the hoses, it drains out. Then the furnace will work for a while and fill with water again. Everything is cleaned out. I think the drain may not be pitched right because the foundation may have settled over the years. This only happens when temperatures outside are below about 10 DG.
@FastFixYouTube
@FastFixYouTube 9 ай бұрын
You’re 100% correct. The pitch is wrong. I had to redo my tubes to get the angle correct. I’ve not had a problem since. Best of luck!
@deryyang9438
@deryyang9438 7 жыл бұрын
Drip tube clean out did the trick! Thanks man.
@FastFixYouTube
@FastFixYouTube 7 жыл бұрын
Dery Yang you’re welcome!
@confusedvoyager7916
@confusedvoyager7916 5 жыл бұрын
The pressure switches on most furnaces are Normally Closed. The diaphragm on the pressure switch drives a piston that opens the switch when there is NO vacuum (i.e., when the fan fails or, as in your case, there is a condensate blockage). Other than that pedantic fine point, good video.
@FastFixYouTube
@FastFixYouTube 5 жыл бұрын
Hey, I’m all about the fine points so thank you for the info! I appreciate the comment. Take care.
@JulesODwyer
@JulesODwyer 5 жыл бұрын
On 80 percent Furnaces the Pressure Switches are Open and Close when the Inducer pulls a Negative Pressure on Pressure Switch that Closes to Complete the Circuit
@scottmetzer1634
@scottmetzer1634 3 жыл бұрын
The vast majority of pressure switches are normally open and closed when the inducer starts Stewart
@davidbell3432
@davidbell3432 3 жыл бұрын
The pressure switches are normally open. I think you got it backwards there.
@pareshpitalia559
@pareshpitalia559 10 ай бұрын
Thank you
@FastFixYouTube
@FastFixYouTube 10 ай бұрын
You're welcome!
@edropper2732
@edropper2732 6 жыл бұрын
3 taps (gentle) on the pressure switch housing with the back end of a screw driver and boom!!! My whole house blew up and now I'm dead.If you wonder how I'm dead and posting this it's because I wrote a "Just in case" letter for my Brother to post on the video in which I got my fatal information from...RiPieces Bro....Nah just kidding,,but yeah the 3 taps on the outer housing made a click then the code stopped flashing and the furnace started..New switch time I assume..Thanks for the great video..:)
@JerryLynch2
@JerryLynch2 5 жыл бұрын
Lol, dude! I was tripping for a second!
@2121groundzero
@2121groundzero 6 жыл бұрын
Thanks! This got my furnace working
@cipherion
@cipherion 3 жыл бұрын
Well done
@FastFixYouTube
@FastFixYouTube 3 жыл бұрын
Thank you!
@Goodi8
@Goodi8 7 жыл бұрын
Ok just did this and viola ! Furnace working :)
@FastFixYouTube
@FastFixYouTube 7 жыл бұрын
Orlando Productions awesome! Glad your problem is solved! Keep an eye on the pea trap. I had to re-plumb the condensation tubes in order to eliminate the problem completely. Sure beats using the oven to heat the house.
@GuitarP0RN
@GuitarP0RN 2 жыл бұрын
I woke up to a smell of hot heat exchanger with no fan. Checked my furnace and found the condensation pump unplugged and some water on my basement floor 🤔 I guess I'll be doing this later today. My Tempstar furnace is showing a fault code 4 blinks. Furnace is less than 6 months old 😞
@FastFixYouTube
@FastFixYouTube 2 жыл бұрын
Sorry I’m so late in this reply. Did you get this issue fixed and if so, what was the problem?
@GuitarP0RN
@GuitarP0RN 2 жыл бұрын
@@FastFixKZbin It's fixed. A mouse was stuck in the squirrel cage causing it to become unbalanced and the molex plug vibrated out from the fan motor. My cat must have lost one of the mice she caught and brings into the house to play with until it can't play anymore(mouse death).
@FastFixYouTube
@FastFixYouTube 2 жыл бұрын
Oh wow! Mice get everywhere that they’re not supposed to be. Good kitty!
@Traceyi1000
@Traceyi1000 6 жыл бұрын
I was getting 3 red blinking light pressure switch stuck closed. Someone replaced pressure switch but unit still not working. It won't even fire up now. Any thoughts!
@D.hanSr870
@D.hanSr870 5 жыл бұрын
Same here
@mauhuynh5828
@mauhuynh5828 Жыл бұрын
It is not pressure switch, have you checked pressure tube inlet hole? Condensation trap? You should vaccumed the induce motor hole as well. Remember unplug all the connection to pressure switch when you vaccum.
@HealthInfo
@HealthInfo 7 жыл бұрын
great video.
@FastFixYouTube
@FastFixYouTube 7 жыл бұрын
HealthInfo thank you!
@alexc6137
@alexc6137 5 жыл бұрын
You should seal the inducer fan/motor with a high temp caulk when you put it back.
@FastFixYouTube
@FastFixYouTube Жыл бұрын
Hmm…..
@vladekvladinov5753
@vladekvladinov5753 5 жыл бұрын
Well, i can see that your P trap is A LOOP!!! Thats not right imo. You wanna changed that, then you wont have that kind of problem more often. Great video
@FastFixYouTube
@FastFixYouTube 5 жыл бұрын
vladek vladinov yes, I’m no expert on p-trap design, but I thought it was odd as well. Thanks for the comment!
@chrisewalt25
@chrisewalt25 Жыл бұрын
Mine is setup the same, is there any reason I couldn't run the drain tubing straight down without having a "trap" in it?
@DanielGarcia-ky7cp
@DanielGarcia-ky7cp 6 жыл бұрын
blew into tube three times. Still didn't work.
@amberestel7785
@amberestel7785 2 жыл бұрын
My yellow light has never worked
@FastFixYouTube
@FastFixYouTube 2 жыл бұрын
Hmm…I assume your furnace works and the light is burned out? Or perhaps your model doesn’t have a continuous yellow light as an indicator of nominal function.
@twistalimes8351
@twistalimes8351 5 жыл бұрын
I’m pretty sure there is not a drip tube on my furnace. 🤬
@austinisfullpleasedontmove653
@austinisfullpleasedontmove653 3 жыл бұрын
Then you have a low efficiency furnace.
@scottmetzer1634
@scottmetzer1634 3 жыл бұрын
You actually mark your wires going to a limit switch LOL
@FastFixYouTube
@FastFixYouTube 2 жыл бұрын
I know…
Furnace Pressure Switch Troubleshooting
16:57
Word of Advice TV
Рет қаралды 829 М.
The Most Common Reason Why A Gas Furnace Won't Turn On
8:25
Everyday Home Repairs
Рет қаралды 1,8 МЛН
Triple kill😹
00:18
GG Animation
Рет қаралды 18 МЛН
Human vs Jet Engine
00:19
MrBeast
Рет қаралды 198 МЛН
Osman Kalyoncu Sonu Üzücü Saddest Videos Dream Engine 275 #shorts
00:29
I Turned My Mom into Anxiety Mode! 😆💥 #prank #familyfun #funny
00:32
Top 5 Furnace Problems and How to Fix Them
20:07
Word of Advice TV
Рет қаралды 1,4 МЛН
Furnace Inducer Motor Troubleshooting! Top 8 Problems!
14:11
AC Service Tech LLC
Рет қаралды 341 М.
Furnace Troubleshooting Condensate Piping
3:29
Nortek Global HVAC
Рет қаралды 485 М.
FURNACE FIX | PRESSURE SWITCH STUCK OPEN
19:02
backontheroaddiy
Рет қаралды 29 М.
How to Test Pressure Switch on a Furnace
14:14
Word of Advice TV
Рет қаралды 633 М.
Goodman Pressure Switch Issue
24:22
Michigan Heating Guy
Рет қаралды 72 М.
How to Jump Pressure Switch on Furnace
6:56
Word of Advice TV
Рет қаралды 718 М.
Triple kill😹
00:18
GG Animation
Рет қаралды 18 МЛН