Just a word of advice for who ever installed the panel, strip the outer jacket of your wires longer. Having to troubleshoot a system with tiny wires like that is no fun at all. Also leave a bit of slack inside the panel, the next tech to come behind will appreciate. And the 120V in the same conduit as the low voltage is a no no. Not code and it will not pass inspection.
@ArgaTheRexouium11 күн бұрын
unfortunately yes you are correct the 120 should be separated from the zones and nacs however we are trying the best to not mess with the original wiring too much theres not much slack due to scrappers getting in and cutting the wiring right next to the conduit so had not much to work with
@fullraph10 күн бұрын
@@ArgaTheRexouium I would have done a junction box or trough (if too many wires) above the panel. 120v can be in it's own accessible jb close by. And then pipe or armored cable inside the wall, to the panel.
@ArgaTheRexouium10 күн бұрын
There is a trough however the 120 also is also in the trough and theres no easy way to separate it as its all emt and buried in plaster
@Berge9907511 күн бұрын
Good to see that the FA system is working! Hope you do some upgrades on the system.
@seaneduardodiaz989410 күн бұрын
i did not think yall where going to be able to salvage that system! wow!
@sparkplug101811 күн бұрын
Always nice having a friend who can help out with different projects.
@KIRBZVIDS11 күн бұрын
nice to see your getting the place up and working 👌 probably a good idea to have a working fire system
@Sagefox455yt11 күн бұрын
Yea I did not think it would all work but I stand corrected 😂
@ArgaTheRexouium11 күн бұрын
new panel some new devices have a ground fault on the 3rd floor that i need to figure out
@EYL890211 күн бұрын
@@ArgaTheRexouium Probably a wire touching in a conduit box or in the conduit itself, or the cable is damaged.
@alexandersalarms53802 күн бұрын
If you ever have this building public or habited please have a company install and monitor the system
@XeroZenith2 күн бұрын
We have this system monitored by a central station. We are getting everything in the building up to code.
@alexandersalarms53802 күн бұрын
@ oh, didn’t know arga got certified, also note you’ll more than likely be required to upgrade the entire system to new devices and a new, not used panel, and probably get the sprinklers up and going too. I know my state is insanely strict about that
@Candy4greg11 күн бұрын
Love these videos. I never owned a building that I could explore, although I acted like it when I was younger. Lol Very fun to watch!
@alexgreat-wu8ye3 күн бұрын
0:09 thats vintage S464A Honeywell pull station
@Dave-to4vk11 күн бұрын
If I was closer I would be there in a heartbeat to help! I would handle the HVAC stuff for ya.
@juniorelectrician200511 күн бұрын
I’m surprised that a once abandoned building has fire alarms more functional than my high school did and somehow is also 2x as old as my high school.
@ez295811 күн бұрын
Nice choice with the MS-10UD. Extremely user friendly and simple system. I will warn you your AHJ might give you some shit for having the panels 120VAC in the same conduit as the 24VDC fire alarm circuits. It could cause interference and is against code.
@XeroZenith11 күн бұрын
That is how it was originally installed and approved. Therefore we aren't going to modify it.
@thomaswilkins816811 күн бұрын
I'm glad you finally got it working are there any original space age alarms that still work or have all those been retrofitted? Also at 0:46 I spotted what looks like a Sanitaire SC679J which was really interesting because those vacuums are intended for carpet only so I was wondering of that was already in the ward when you bought it and what do you use it for since I haven't seen any carpeted areas.
@aberobinson111 күн бұрын
That Sanitaire caught my eye as well. A real vacuum, not a disposable vacuum.
@thomaswilkins816811 күн бұрын
@@aberobinson1 Yeah unfortunately you don't see too many of them around anymore I still have one that works from the early 80's they are no joke.
@XeroZenith11 күн бұрын
We brought it to the building. It is an amazing vacuum! We do have some carpeted areas.
@AllTheOne21911 күн бұрын
@@thomaswilkins8168 I have a sanitaire s663 that has a broken cord. Gonna get it repaired and get it working.
@theericfreeze14939 күн бұрын
I got some of those vacuums and there's just amazing.
@Reaglesracing44_11 күн бұрын
now just need a working sprinkler system
@Dave-to4vk11 күн бұрын
Nice. Get all the life safety systems up and running first. You will sleep better at night.
@drfirealarm10 күн бұрын
great job on getting the fire system to work
@SgFireAlarms9 күн бұрын
You should make more videos on the progressive install of the Fire Alarm System! Looking good so far.
@CatJBL11 күн бұрын
Hey XeroZenith, I was a fire alarm technician back in 2023, You should install a fire alarm booster power supply to hold up all of the notification appliances. I’d recommend the Fire Lite FCPS-24FS8.
@ArgaTheRexouium11 күн бұрын
Did a current measure in alarm already total draw is About 4.5a so no need as the panel has a 7amp psu
@eroesslr984 күн бұрын
Is any original CCTV or access control live?
@wolfy3378910 күн бұрын
nothing like a night in the Psych ward fire alarms screaming and a creepy old and probably haunted piano playing creepy music.
@truckerguy2810 күн бұрын
So when is it getting a deep clean
@jaydeeheh11 күн бұрын
Neighbors must love you
@BeanNamedDean11 күн бұрын
yayayayyaya I like learning more about these oddly obnoxious but also nice alarm systems lol
@dragonicankh11 күн бұрын
Funny how i was about to commet about this on the last posted video, glad to see its alive
@mikeross88010 күн бұрын
Interesting that these had conventional pulls as back in the day many of these used keys in facilities such as these.
@lukep433911 күн бұрын
nice! seems like a fire lite ud panel of some kind?
@robertmailhos815911 күн бұрын
Well at least the fire department will be happy to that fire alarm system is working
@Ronnocbot11 күн бұрын
No dialer installed, so they would never know
@robertmailhos815911 күн бұрын
@Ronnocbot oops I forgot about that piece of equipment
@XeroZenith11 күн бұрын
@@Ronnocbot We do have a dialer. We have a dedicated POTS line running to the panel. We also have monitoring service already setup.
@ArgaTheRexouium11 күн бұрын
@@Ronnocbot ms10ud has a built in udact
@Ronnocbot11 күн бұрын
@ correct. But it was not wired or programmed.
@FI-TECH-25011 күн бұрын
Nice choise with the ms 10ud, but theres one thing: You absolutely need to try adressable. And it doesent even have to be all new stiff, used off of ebay will do it to. The panel is 0,5-1k, and the devices will run ya about 3 to 5k. But this systems good for now. Good stuff, keep it going
@dylannoalan61511 күн бұрын
No they absolutely don't need to try addressable. Building was fitted with a conventional system, they wanted to get the original system going, so they put in a conventional panel.
@ArgaTheRexouium11 күн бұрын
we decided to stick with conventional as we were donated a conventional panel and budget is tight if we had unlimited funds i would put something like a nfs 640 in
@FI-TECH-25010 күн бұрын
@@dylannoalan615 They said it themselves. if they had the budget they would have gotton a nfs640 or something. You are wrong.
@mdmusic9 күн бұрын
Just for the heck of it, try installing a 6" bell in place of one of the horn/strobes :D
@braelinmichelus7 күн бұрын
So weird to hear 2400Hz, like residential smoke alarms in a large commercial building! I do wonder though, is it a mix of Commander 2s and Commander 3s? Or are the high-pitch ones just Commander 3s set to 2400Hz temporal?
@explodingtoast989810 күн бұрын
POV you work at a convenience store and some kid pulled the allarm and you can’t find the anunceator key
@dennisraymond433911 күн бұрын
Far out man. Getting there. Shit that's a big joint lol.
@nightraven300611 күн бұрын
Do a test on a generator backup
@TexasRailfan200811 күн бұрын
So did you install a new panel? I believe I saw that the original panels were gutted in a previous video.
@ArgaTheRexouium11 күн бұрын
yse was a gamewell firequest now a ms10ud
@dakotamcaleer611311 күн бұрын
I would love to clean that up seriously i have major ocd if i could i would i just need proper equipment PPE and music lol
@ogg8410 күн бұрын
Now for getting the sprinkler heads back in service!
@Huey-Gamer10 күн бұрын
yessss
@EYL890211 күн бұрын
Would've been better with an addressable panel... Because it gives you the exact device when it is activated with an address on it, instead of the zone number. Which has a bunch of conventional devices on that same zone. Although it would be alot expensive to do because of isolator modules, monitor modules, addressable pulls, and smokes.
@XeroZenith11 күн бұрын
That would be nice, But upgrading to an addressable system in a building this size would be extremely costly (Well over 50k), especially when considering the regulatory and legal complexities of installing a new system compared to maintaining a grandfathered setup. Would make more sense to use that capital for other parts of the property.
@EYL890211 күн бұрын
@@XeroZenith True, the 10UD works pretty well for what you are going to use it for...
@neohistoryfan101411 күн бұрын
@@XeroZenith my former high school (the same one as LeBron James) still has the original Simplex fire alarm system from 1972; it still works great for being 50 years old. I have a video about it on my channel.
@centralindianaelevatorsesc692511 күн бұрын
Nice system but you need to change those tones man. Sounds to much like a residential alarm. 2:26 sounds really good. You should do the full PA system next. Try to play music throughout the building and locate speakers.
@thomaswilkins816811 күн бұрын
Unfortunately the Gentex Commander 1's with the piezo tone cannot be changed the device at 2:26 is a Gentex Commander 2 set to electro mechanical tone.
@Ronnocbot11 күн бұрын
@@thomaswilkins8168beat me to it. Correct!
@NaoPb11 күн бұрын
I love that tone at 2:26. Wish my home alarm sounded like that.
@Ronnocbot11 күн бұрын
@ Sounds like you need to buy a Gentex Commander 2 or 3
@EYL890211 күн бұрын
Or a Commander 4, but the Commander 4 is ceiling mount only.
@YourLocalFireAlarmTech11 күн бұрын
Man i love to be there working on that system lol looks fun!! What panel is it?
@YourLocalFireAlarmTech11 күн бұрын
Id*
@Berge9907511 күн бұрын
Fire-Lite MS-10UD
@Warp209011 күн бұрын
@@Berge99075 XD
@alphawolffurry-t8r11 күн бұрын
HEY! you fixed the pannel
@Colby.Hutchinson11 күн бұрын
I think they purchased a new one as someone pulled the old one out
@ArgaTheRexouium10 күн бұрын
@@Colby.Hutchinsonyeah used to be a grinnell firequest now a ms10ud 7
@Daltoncom7 күн бұрын
I install Fire-Lite so feel free to reach out with any questions.
@redsquirrelftw10 күн бұрын
I'm actually surprised at how well it seems to work, i was not expecting that it worked at all. Not sure how strict the requirements are to get a system to be compliant but wonder if this system can be kept and used once everything is fully tested.
@korneliusfrik954511 күн бұрын
How about a few really cheap security cameras and a few crts to get that horror mood goin Tip: these round, this little small camera with 3 round white lights, silver plastic cover, with a button on top, the rest being out of black plastic, with this stupid stand that is good for nothing, these are absolutely terrible landwaste and are great cams for horror because they suck ass. By the way i got one as a webcam and these are wuite good for actuall security because they are durrable and with a bit of plastic foil they are waterproof. After that you could make great horror films in there and if you do i could try to make cgi in that. (Im terrible but i know how shotcut works and i have the power of making keyframes with a video editor. And i can make retro ui in figma (or whatever you ask me to make it in as long as it is a free program) and i can code scratch programms which is irrelevant but the list is to short and now its long enough. perfect.) By the way renovating a house like that is timeconsuming and i apprecciate the work and effort really especialy when it is so trashed. Also can i have like plans from the house so i can build it in minetest for no reason :)
@DanTDMJace8 күн бұрын
it aint a house, it's a hospital
@16BitDoggo7 күн бұрын
@@DanTDMJaceerm, actually it's a psych ward
@DanTDMJace7 күн бұрын
@@16BitDoggo erm, a psych ward is a type of hospital
@fixitfaxit40068 күн бұрын
videos on the progressive install of the Fire Alarm System!
@kansasstatealerting287411 күн бұрын
Awesome!!!!!!!
@ShiaGaming8811 күн бұрын
You should install motion detectors that are connected to the fire alarm so if someone sets one off it goes off
@TheClayton30611 күн бұрын
Like he wants it to pass fire inspection so thats a terrible idea
@ShiaGaming8811 күн бұрын
@@TheClayton306can’t you use a different tone
@EYL890211 күн бұрын
@@ShiaGaming88 For motion detectors and door contacts, a security panel is needed. Like a Honeywell Vista panel.
@Colby.Hutchinson11 күн бұрын
orr security-
@EYL890211 күн бұрын
@@Colby.Hutchinson A security panel is better, than paying for someone to guard the building.
@Channel-iu7rn11 күн бұрын
Is the panel new? Did the old panel that was stolen have 10 zones? Will you be getting some batteries for the panel?
@XeroZenith11 күн бұрын
Yes to all three.
@EndeavorsDnB10 күн бұрын
Nice, tht was quick!
@Midwestaviationspotting199511 күн бұрын
How many elevators are in this building
@litz1311 күн бұрын
From the original tour, just one (and it's been deactivated currently)
@ArgaTheRexouium11 күн бұрын
just one old dover
@fastcsx141211 күн бұрын
How common are commander 1 systems I’ve been looking around me I rarely see any. Heck I rarely see Gentex systems near me.
@ArgaTheRexouium11 күн бұрын
i worked on a couple not very common now
@fastcsx141210 күн бұрын
@ ahh I see thank you! Then like what year would a system like this be installed, plus I wonder this has to be some at recently abandoned of there is some commander three. Sorry for the ramble reply thank you.
@Fadude34569 күн бұрын
Gentex commander 2s cool
@mixerdude10 күн бұрын
Did that system call the fire Dept in the past?
@alphawolffurry-t8r9 күн бұрын
yes but the caller is not connected
@16BitDoggo7 күн бұрын
All systems are required to to meet code.
@TechnicalIssuesOfficial11 күн бұрын
Nice.🎉
@GvShorts7311 күн бұрын
Did you replace some alarms with some new commander 3's?
@ArgaTheRexouium11 күн бұрын
yes need to set the tones to at least mostly match still
@michaelh1223111 күн бұрын
XeroZenith i collect fire alarms and i was wondering, if you ever upgrade the system would i be able to get some old devices like ther pull stations and horsn strobes and the stopper covers
@FireSafetyTech11 күн бұрын
I can give u some
@michaelh1223111 күн бұрын
@@FireSafetyTech you can contact me from the info in my bio
@JJ971511 күн бұрын
Do you plan on replacing the old fluorescent lights with LEDs?
@Some_Random_Teen11 күн бұрын
He’s slowly replacing the bulbs with led tubes as they burn out if I remember right
@ArgaTheRexouium11 күн бұрын
correct
@iHoneWolf11 күн бұрын
Is that alarm broken 3:53 it sounds raspy compared to the other alarms.
@patrykgoanimate11 күн бұрын
It might be on a different tone because some of the alarms have multiple tones
@thomaswilkins816811 күн бұрын
It's on a different tone
@ShieyV2komputroniks11 күн бұрын
The smoke detectors might need to be replaced tho . Thes look rough
@ArgaTheRexouium11 күн бұрын
ill be testing them before i trust them they are about 30 years old now
@AAron-cu9qu11 күн бұрын
Is the system for fun or u need it
@XeroZenith11 күн бұрын
We are required to have a working fire alarm system in this building.
@AAron-cu9qu11 күн бұрын
Gentex 2
@ArgaTheRexouium11 күн бұрын
gentex commander 1s with 3s replacing failed devices
@AAron-cu9qu11 күн бұрын
What about smoke detector
@ArgaTheRexouium11 күн бұрын
we have mostly system sensor 1400 detectors been replacing the dead ones with I3