FPE Fire Hazard | 100 AMP Service Upgrade in Cranford, New Jersey

  Рет қаралды 19,604

Electrician Ron

Electrician Ron

Жыл бұрын

In this video you'll see how an old Federal Pacific Electric panel with STAB-LOK circuit breakers is removed and a new 100 amp service is installed. Updated grounding and bonding too.
The Federal Pacific Electric Company designed, patented and sold circuit breakers, beginning with its first patent in 1949 and ending with its eventual bankruptcy. Its products were later found to be defective and dangerous.
In 1979, Reliance Electric Company bought Federal Pacific Electric Company from UV Industries, and was shortly thereafter bought by Exxon Corporation. But in 1980 Exxon sued, claiming that UV Industries had faked safety tests to gain UL listings for its products, and UL withdrew its safety endorsement.
The Consumer Product Safety Commission subsequently tested the products. Despite CPSC findings in 1984 that the circuit panels were faulty and dangerous, no recall was ever issued. Other independent testing indicated a failure rate of up to 60 percent, yet products still on the shelves continued to be sold. In 2002, a New Jersey court found in a class action lawsuit that Federal Pacific Electric Company had violated the New York Consumer Fraud Act by knowingly selling circuit breakers that did not meet UL safety standards, despite the UL endorsement on its label.
Potentially hazardous Federal Pacific Electric Company circuit panels can still be found in millions of homes built before 1990. They can be identified by the labels on the circuit panel’s front or side.
Classic Electric, LLC | Point Pleasant, New Jersey
License & Business # 16557
(732)-770-1437
Ron Pecina Jr. is a licensed electrician in the state of New Jersey. This allows him to apply for electrical permits, work with live conductors, remove meters, and disconnect service from the utility company. New Jersey observes the 2020 NEC and the Uniform Construction Code. The majority of the work seen here on this channel falls under the Rehabilitation Sub Code (Chapter 6 of the U.C.C.).
ALL New Jersey licensed electricians MUST complete 34-hours of continuing education units each tricentennial period. This includes a mandatory 10-hour code update course. Any work above 10-volts requires an electrical license in New Jersey.
Ron is an active member of the New Jersey Independent Electrical Contractors Association.
Become an NJ-IEC member here: www.nj-iec.org
IEC National: www.ieci.org
WANT TO SEE MORE? How to wire a Generac Standby Generator. WATCH HERE: • Generac Generator Inst...
Classic Electric, LLC is a Generac standby air-cooled generator installer. Generac Dealer # 1019500
Camera: Go Pro 9/ 10.
Editing software: Apple iMovie
Animation software: Apple Keynote
Like, Share, and Subscribe!
Electrical Wiring is NOT a hobby. Call a licensed electrician.

Пікірлер: 271
@FrontRowOrBust
@FrontRowOrBust Жыл бұрын
And just when I thought my Friday couldn’t get any better, Ron hits us with a new upload🎉
@electricalron
@electricalron Жыл бұрын
Happy to hear you look forward to them! Thanks man!
@qv6486
@qv6486 Жыл бұрын
@@electricalron Hi Ron, What advantages do we gain if we use Insulated Neutrals in the example from this video of yours uploaded on Feb 24, 2023 kzbin.info/www/bejne/gnm3q4pqeaiSnKs versus Bare Neutrals for connection between the Main Service Panel to the Meter Base to the Utility Service Mast?
@timrisch4540
@timrisch4540 11 ай бұрын
In California, most homes in the coastal areas and built within the last 50 years with overhead service use a combined meter-circuit breaker panel (load center) located outdoors and recessed into the outside wall. The service entrance cable is contained within metal conduit pipe that runs up inside the external wall and exits through the roof. The conduit can extend up to 3 ft above the roof with a weather head. The service hook is connected to the pipe below the service head. I find that usually individual THHN cables are used in the conduit rather than service entrance cable from the weather head to the panel.
@edwardleonard7538
@edwardleonard7538 Жыл бұрын
federal pacific was sued out of existence and most homeowners insurance companys will not cover you if you still have an active FP service...back in the day when you could still get a FP breaker at your local supply house they would always ask you if you would like a fire extinguisher with that,,,lol the problem with FP breakers is they would never trip they would just arch weld inside the panel.
@electricalron
@electricalron Жыл бұрын
Very true!
@iroc341
@iroc341 7 ай бұрын
Our house was built in 1974, we bought it in 1998. Just now having our Federal Pacific main Panel replaced. I even bought new replacement breakers for this panel, before I found out that those breakers were failing also! Nice job Ron!
@Gr8thxAlot
@Gr8thxAlot 5 ай бұрын
My entire neighborhood is 1960's FPE panels, mostly original. A few of us wiser homeowners have had them replaced with all new service and panels. (Easily identifiable by who has new service entrance heads.) Most homeowners and realtors seem unaware of the danger or don't care. Thankfully, I can't recall any electrical fires here despite that. Fools grilling in their garages seem to cause the fires here, not the FPE panels. :-)
@jaroadkill260
@jaroadkill260 Жыл бұрын
Electrical Inspector here from Texas. It’s awesome to see work from other states and compare the similarities. I very much enjoy you videos and commentary 👍🏽👍🏽👍🏽
@electricalron
@electricalron Жыл бұрын
Right on
@linehandibew6205
@linehandibew6205 Жыл бұрын
When I started wiring houses back in 2001 we were wiring new houses all the time. My boss and I drove in the ground rod outside (yes Long Island only requires 1) we built the entire service, no drop to house yet since it new construction. A few weeks later my boss got a call. The water company hooked up water main at road and had no pressure. Needed up that when we drove ground rod we went right through th brand new copper water main and had no idea because it wasn’t hooked up yet. What are the odds, good time. God rest his soul. Miss you “whitey”
@electricalron
@electricalron Жыл бұрын
I remember those days driving only (1) ground rod. Around here we call 811 before we dig but the ground rods are estimated guess.
@velocity91
@velocity91 Жыл бұрын
I enjoy watching the videos. Thank you for taking the time to film and edit this kind of stuff.
@alfgomez6575
@alfgomez6575 Жыл бұрын
Great job!!!! Mr Ron👏🏽👏🏽👏🏽
@vince6829
@vince6829 Жыл бұрын
Love your videos. Thank you for sharing.
@chuckquinn8026
@chuckquinn8026 Жыл бұрын
Another excellent job. Thanks for taking us along!
@electricalron
@electricalron Жыл бұрын
Our pleasure!
@ClippyC
@ClippyC Жыл бұрын
Beautiful workmanship.
@TheQuedog15
@TheQuedog15 3 ай бұрын
Such neat work
@wpcnola
@wpcnola 4 ай бұрын
Ron, I watch and learn much from watching your work videos, thank you. Also enjoy the high production value of the various tempo musical riffs. ;
@GlenMacNeil
@GlenMacNeil 5 ай бұрын
Your videos are really helpful. Real world stuff. Thanks again.
@spark83ify
@spark83ify Жыл бұрын
Another great video! I look forward to them!!
@electricalron
@electricalron Жыл бұрын
Thanks glad you’re enjoying the videos Travis!
@DanT271
@DanT271 Жыл бұрын
Thank goodness one more FPE panel in the trash where it should be Your workmanship is excellent
@electricalron
@electricalron 4 ай бұрын
Thank you very much!
@godelrt
@godelrt Жыл бұрын
Just in time for a Saturday breakfast and a video treat to go along with it!!! Thanks Ron! Loved it!
@electricalron
@electricalron Жыл бұрын
Hope you enjoy
@hoyte44
@hoyte44 11 ай бұрын
Great job!! The attention to detail is what separates workers from the professionals.
@arnieselectric007
@arnieselectric007 Жыл бұрын
Another near perfect job Ron...You are a great inspiration for all of us tradies brother...
@michaelstaley9979
@michaelstaley9979 Жыл бұрын
Another great video. Each time I watch your videos I learn little tips and tricks especially with upgrading service entrances. Thanks for sharing.
@electricalron
@electricalron Жыл бұрын
Glad you found it helpful!
@fredbrown7954
@fredbrown7954 Жыл бұрын
Great job. Thanks much 🙏
@jimmyg6215
@jimmyg6215 Жыл бұрын
Crowded spaces are no fun. Parents had their Fed Pac replaced 10 years ago (fortunately no issues ever occurred in the house). Panel was also in a confined space. Felt bad for the installer and took down the facade walls and paneling so he could get into the space. Oh the 1970’s were not happy I desecrated the full paneling basement. 😂
@electricalron
@electricalron Жыл бұрын
I tried to be as neat as possible but I had to do what I had to do.
@user-zq5gy2ri6o
@user-zq5gy2ri6o 2 ай бұрын
That is so Michael Myers and all the other villains can kill the power without pulling the meter! Lol
@jcwoods2311
@jcwoods2311 Жыл бұрын
Ron, I really appreciate what you put into these instructional videos. I know some from years of being around electricians, but the details you include have made all the difference in my education about the "why fors" in what you do. A BIG Azz thank you, your knowledge and presentation are over the top.
@robertbarnes2419
@robertbarnes2419 Жыл бұрын
Like the addition of that music! Nice work
@sherwinalvarez7365
@sherwinalvarez7365 Жыл бұрын
As a new home owner this is a ver informative channel. Watched a few of your videos so far since it came up on my feed.
@mikedelaney1414
@mikedelaney1414 Жыл бұрын
Nice production Ron!
@electricalron
@electricalron Жыл бұрын
Much appreciated!
@Gruntled2001
@Gruntled2001 Жыл бұрын
Ron, love your work, and above that, love that you share your work with others. I know that Connecticut Electric makes listed replacement breakers to FPE, but I cannot in a good conscience add a circuit to a panel where three existing breakers fall out of their positions while I am putting a listed replacement in. So, it's a full replacement, or I don't want to touch it.... Thank you again, Ron for making our weekend with a new video.
@RandleMcMurphy-wm8rt
@RandleMcMurphy-wm8rt Жыл бұрын
Inspiring stuff for this 2nd year apprentice! In my old stomping grounds of Cranford, too. Love the idea of being out there on my own one day, like you are.
@electricalron
@electricalron Жыл бұрын
Work hard and get in the classroom as soon as possible. Thanks for watching!
@jeremycirian7824
@jeremycirian7824 Жыл бұрын
Journeyman Electrician from Omaha, NE. Love the channel Ron. I appreciate how detailed you are in your videos and that you take the time to explain things. As we all know, you're never to old to learn new things and in this trade we always learn something new. Keep doing what you do brotha. Props from the midwest
@electricalron
@electricalron Жыл бұрын
Cool, thanks
@thesells1
@thesells1 Жыл бұрын
Enjoy your video, you seem to be a good guy who cares about the customer and getting the job done right.
@tommycho9068
@tommycho9068 Жыл бұрын
Great video. Thanks.
@jrpritchard1622
@jrpritchard1622 Жыл бұрын
awesome job Ron am going start doing what you do i like the method you do with the painted plywood template it is a nicer good thanks for videos be safe 👍
@electricalron
@electricalron Жыл бұрын
Do your best work and the success follows.
@brianbeasley7270
@brianbeasley7270 6 ай бұрын
My home had two 200-Amp Federal Pacific Service Panels. I had them replaced for about $5K total. I'm glad I did!
@davehowell4111
@davehowell4111 Жыл бұрын
Great job 👍
@jimsergi
@jimsergi Жыл бұрын
I enjoy your comments, im from the west coast and like to see your homes on the East side of America
@rodolfovesga979
@rodolfovesga979 Жыл бұрын
Great video Ron keep them coming back lol 😊
@jaimebotello3512
@jaimebotello3512 Жыл бұрын
Awesome content!!
@ptso7580
@ptso7580 Жыл бұрын
AZ and Cali outdoor panels WTH? Haha, coming from AZ and worked in southern Cali for 20 years AZ, NV, and NM as well, I can tell ya weather is mostly great year around. But mostly it's for fire department to disconnect power and housing developments cutting cost with meter combo panels. Helps with solar installation times too.
@sciatl2505
@sciatl2505 Жыл бұрын
Texas has a lot of panels on the outside too
@marinomartire8791
@marinomartire8791 11 ай бұрын
YOU ARE THE BEST RON I LIKE THE WAY U INSTALL THE SERVICE PANEL I HOPE I CAN WATCHING MORE VIDEO GOOD JOB
@electricalron
@electricalron 11 ай бұрын
Thank you.
@roybreeden8928
@roybreeden8928 Жыл бұрын
Well done Ron! Yes, we here in East Tennessee do things a little different than you guys in the Northeast. But that's what I enjoy seeing - how you guys do things. Keep it up! 👍
@arnieselectric007
@arnieselectric007 Жыл бұрын
Hey Roy, do you watch "The Electrical Code Coach" He's in Tennessee also...
@roybreeden8928
@roybreeden8928 Жыл бұрын
@@arnieselectric007 Hey Arnie! Yes, I do watch him from time-to-time. After 42 years in the electric industry, I still enjoy learning and seeing how others around the country are doing things.
@Ben-Wah
@Ben-Wah Жыл бұрын
Ron... excellent video! Few in Jersey talk about the dangers of FPE breakers and breaker boxes. In my old neighborhood, every single home had FPE panels and breakers, and I watched two of those homes burn down thanks to them. Both fires started at the breaker boxes. How they are still in service with no recalls is beyond my understanding.
@electricalron
@electricalron Жыл бұрын
There’s a lot of information online but as the story goes FPE manipulated their products during the listing process. There’s news clips from several decades ago.
@user-le1kj1mq4b
@user-le1kj1mq4b Жыл бұрын
You would make an excellent electrical shop teacher
@electricalron
@electricalron Жыл бұрын
Funny you should say that. First, thank you. Second, I am training to become a teacher at the IEC.
@jaybird4095
@jaybird4095 Жыл бұрын
1st time viewer. I had a FPE panel in our house when we bought it 8 years ago. Swapped it out within the 1st year. Not worth the risk to the family.
@attilagyurovszky1070
@attilagyurovszky1070 11 ай бұрын
great video, just found you on youtube, observation/comment aren't multi-conductor branch circuits required to be on two-pole breakers, great video, great workmanship, keep up the good work
@electricalron
@electricalron 11 ай бұрын
Yes they are and they were installed prior to inspection.
@michaelmorgan7893
@michaelmorgan7893 3 ай бұрын
That duck seal almost reminds me of the stuff they used to use on the railways for everything from wire entry, to seating lenses in place on signal lights.
@christopher20008
@christopher20008 Жыл бұрын
Great video
@stevencole7331
@stevencole7331 Жыл бұрын
I actually saw more failure rates from older general electric panels with breakers failing and damaging busbars which usually led to a panel replacement . I did do a few FPEs . GE was my top panel replacement followed by Challenger and zinsco Now there was probably more of them out there but I did run into existing FPE panels still in operation on occasion with no visible difficulties .
@williamradwanski1998
@williamradwanski1998 12 күн бұрын
Retired service tech from Schneider electric now living in AZ. I recently had problems with my outdoor 200 amp service. Had to replace a 30 amp circuit breaker for my outdoor AC unit. I took a temperature reading of the outside of the box when the sun was going down and would hit the box. The temperature was 150 degrees F. I found the high temperature out here causes nuisance c!b tripping and c/b failures. Way different than PA.
@electricalron
@electricalron 12 күн бұрын
Crazy having that equipment outside with the sin blazing down on it.
@wiley0714
@wiley0714 Жыл бұрын
Thanks! Appreciate ya!
@electricalron
@electricalron Жыл бұрын
I’m glad I could help! Thank you for the Super Thanks!
@garbo8962
@garbo8962 Жыл бұрын
When I did a service or panel replacement I always removed the short flimsy screws from 100 amp circuit breakers and applied a thin coat of noxid paste on them. Several times in damp basements found the screws corroded where they could not be loosened. Was told that yes a panel can be installed by a door that opens up blocking it.
@ernestperino9334
@ernestperino9334 Жыл бұрын
Ron nice clean work good video, multiwire branch circuits require 2 pole circuit breakers or handle ties 210-4B
@electricalron
@electricalron Жыл бұрын
They’ll be installed prior to the final inspection. It’s actually not required under the Rehab sub code here but I do it anyway.
@Bob.W.
@Bob.W. Жыл бұрын
Thanks.
@kylegagnon-rs2lt
@kylegagnon-rs2lt Жыл бұрын
Love ur vids but helpful tip I try to prep the meter before I have the seu connected and mounted to house so I would take out my KO and knock the holes out of back prior
@marc974
@marc974 3 ай бұрын
Too bad you cannot work in Canada lol I need a panel upgrade in Montreal, your videos are so informative ! thanks
@electricalron
@electricalron 3 ай бұрын
Glad you enjoyed them!
@michaelmorgan7893
@michaelmorgan7893 3 ай бұрын
Was watching a couple of guys build a "mini house" out of an old trailer bed, and old pallets like stuff is shipped in. Turned out beautiful, until they ran the electric. I had to cringe when I saw them wire a range top and an AC unit with stranded 12 gage extension cord. I was on board until I saw that. That's a major fire waiting for a place to happen.
@ClippyC
@ClippyC Жыл бұрын
I learn so much from your video's - thank you. Question - I don't see you torquing any of your connectors or breakers? Is this something you do behind the scenes?
@CaptainMcFartin
@CaptainMcFartin Жыл бұрын
Great video, I know I definitely would’ve taken the door off the hinges that kept hitting you.
@electricalron
@electricalron Жыл бұрын
Good call!
@adassociates8235
@adassociates8235 11 ай бұрын
Every job you did was the of installation art👍👍👍👍 We are so worry that you are never wear safety/insulated gloves😀 which: 1- Your honey is not happy😊 2- we don’t want to miss any of your content videos😊 Also lock your truck as you might need to spend $$$$ on new Milwaukee tools😊
@ellenpecina983
@ellenpecina983 Жыл бұрын
❤ Wow! Can I call you The Magician?!!!
@Fernando-ns3uv
@Fernando-ns3uv Жыл бұрын
Nice job
@electricalron
@electricalron Жыл бұрын
Thanks!
@captainwaring
@captainwaring 7 ай бұрын
Hi Electrician Ron, You know how they say listening to Bach can make a person more intelligent because of his mathematical precision( point and counterpoint); your channel is excellent for improving one's intelligence. What they should be saying is, "'watching Electrician Ron's channel makes a person more intelligent." Well done!! Would I be correct in believing that you have teaching experience at a local community college or some other institution of higher education?
@peterarroyo8772
@peterarroyo8772 Жыл бұрын
Hey Ron Great info and videos. I always wondered what is the main driver to installing the services with service entrance cables instead of conduit. Is it a financial option given to the customer, where one is less than the other? I see both here in PA and I've seen you use each one in a couple of your videos so I'm curious what makes your decision one way or the other.
@josenava8404
@josenava8404 Жыл бұрын
Hi Ron, I really enjoy your videos! Very informative. I do have a quick question (kinda dumb question, actually): The foldable work table you used on this job, who makes it? and where can I purchase it? I live in the Chicago, so we do have all the big box stores. I do handy work around my house and that table would be beneficial to me. Appreciate your time. Thank you and keep up the great workmanship!
@alfgomez6575
@alfgomez6575 Жыл бұрын
Here from CA and yes Panels r required to be install outdoors by garage. Here!
@mostmost1
@mostmost1 Жыл бұрын
I have one in my home. I couldn't find an electrician 8 years ago to do the work. I need to update before I sell the home or catch a fire. It's worked fine in the last 9 years I've been there.
@electricalron
@electricalron Жыл бұрын
The trouble is the circuit breakers don’t always work when you need them to! You’ve been or safe, maybe a little of both.
@throttlebottle5906
@throttlebottle5906 Жыл бұрын
it's easier to put the SE cable through the LB before pipe is placed on either side. same goes for all conduit, if you can, run the wire as your installing the conduit. not all places will allow that, but we did underground SE's that way, no fish tape needed shove it through a section/fittings then glue it, repeat until the end. often times we didn't even drop it in the trench until done. I'm sure we got by with many things in the mid 1990's 🤣
@jbowensjbowen
@jbowensjbowen 10 ай бұрын
Love the footage. Question? Did you have to install an additional fastener for the 100amp main (NEC 408.36.D) due to the main being Plug-in type?
@electricalron
@electricalron 10 ай бұрын
Comes with that piece of esuipment.
@w9gb
@w9gb Жыл бұрын
Changing Electrical Code (recent, here) to have Main Cutoff at Meter Location for New Construction. Ron used Pentrox (NoAlox) - SMART !
@alphasaiyan5760
@alphasaiyan5760 Жыл бұрын
Unfortunately SE cable is not allowed to be used as a service riser here in my municipality. We have to use RMC or IMC for The riser from the meter hub up with a weather head on top. We can use aluminum se cable for sub panel feeders. We can aluminum feeders for appliance and equipment feeds in residential and of course cooper branch circuits.
@seaneyo2006
@seaneyo2006 Жыл бұрын
When you tie in the new entrance cable to the triplex are you aloud in your area to do the work energized? Or do you have to have the PoCo disconnect at the pole?
@MrKen59
@MrKen59 Жыл бұрын
Regarding a sub-panel located within a few feet of main panel using copper wire, am I looking at 4-4-4-6 wire for 100-amp or do we use 3 awg under the 75 degree column? I don’t mean to sound dumb, just curious. I appreciate your narration - wonderful job.
@garbo8962
@garbo8962 Жыл бұрын
You stated ground rods must be 6' apart. Was told at several IAEI classes that they have to be at least far apart as rod length. So the 8' ground rod we all use must be at least 8' aoart. If you used 10' ground rods they wlu!d have to be st least 19' apart. Next time that you have time try using two ground rods tied together to illuminate a 120 volt 60 watt incandescent lamp. In the summer might look like a 3 watt lamp and below freezing weather forget about it. You can reduce to resistance like old Ma Bell guys did many moons ago. Would install some kind of salt solution or if in a hurry just piss on ground rod.
@aerofart
@aerofart Жыл бұрын
Hey Ron, thanks for another great video. Are those cable boots on the service lines where they connect to breakers inside the panel? Seems like you were fidgeting with them for a while and were maybe unsure how they’re supposed to stay put. Is that top flap with the holes in it that you were playing with supposed to slide into a slot on the side of the breaker maybe? Seems like that might be the reason they have holes in them, so that if slid into a slot, some raised bumps inside the slot would fit into the holes in the flap and partly “lock” the boot into place. Also, watching you connect the service drop lines, the thought occurred to me, would different precautions be in order when connecting to a metal structure like a steel garage or shed, for example? The idea of being 24 feet up on ladder while connecting live lines always makes me very nervous.
@electricalron
@electricalron Жыл бұрын
The protective covers were adjusted and installed properly. The one flap gets removed for flush finish.
@earlestes8649
@earlestes8649 7 ай бұрын
I’ve got a older couple that need to have their 200 amp fp replaced but they are not much older than me and they don’t have the money even to pay me really. But I figure they will soon I’m 67 and I’ve been doing electrical since 13 years old never been licensed but learned under one.
@jorgecazares9893
@jorgecazares9893 Жыл бұрын
Great video like always Ron. I'm an electrician out of California. I like watching your videos and like watching how it's done in other states. I noticed that you did not install a "BR TYPE HOLD DOWN SCREW KIT" on the main breaker. Is it not required in New Jersey?
@TheTubejunky
@TheTubejunky Жыл бұрын
@ 17:01 It looks as if it has a metallic HD arm screwed to the panel.
@electricalron
@electricalron 4 ай бұрын
Yes, the main breaker is mechanically attached from the factory.
@AngelMartinez-me1bf
@AngelMartinez-me1bf Жыл бұрын
Freaking awesome, what is something you always watch out for when estimating a service change ? Thanks for another great one
@electricalron
@electricalron Жыл бұрын
1. Where is the water main. 2. Is it overhead or underground service. 3. How many circuits are there and will they need to be extended. 4. Parking availability.
@aaron74
@aaron74 Жыл бұрын
Yeah those Federal Pacific panels are still around and they should be replaced asap. Apparently up in Canada there was a separate company called Federal Pioneer, and their panels use the same Stab-lok breakers but apparently there was never a problem with those panels. They aren't made anymore but Schneider Electric still makes replacement breakers for Canadian customers who still have those panels.
@jolyonwelsh9834
@jolyonwelsh9834 Жыл бұрын
There's a company in the U.S. that still remanufactures breakers for aftermarket panels such as Federal Pacific, Wadsworth, ITE pushamatic, and Zinsco. Connecticut Electric distributes them through Home Depot on line. They state that they're manufactured and listed to the latest UL standards.
@aaron74
@aaron74 Жыл бұрын
@@jolyonwelsh9834 I had no idea, that is good to know!
@mostmost1
@mostmost1 Жыл бұрын
I have one in my house!
@jimr2053
@jimr2053 Жыл бұрын
I've seen with stranded wire to tighten, work the wire side to side, tighten again, repeat till the screw doesn't move anymore, is that necessary? Also noticed that you didn't use anti-oxidant on utility side of the splice, was that on purpose? Thanks for all of these videos!
@haweater1555
@haweater1555 Жыл бұрын
What is the "fifth jaw" in the meter base? Is it loop of wire that the neutral goes through, like a clamp meter, which an ammeter can be hooked to on the outside to monitor neutral conductor current?
@jeffbecraft7174
@jeffbecraft7174 Жыл бұрын
In MD we use ground wire connectors and Min. 150amp service
@electricalron
@electricalron Жыл бұрын
Sounds good but 100A is the minimum and GEC’s do not require connectors.
@josueespino5532
@josueespino5532 Жыл бұрын
@@electricalron what he means to say is that in MD and DC, we are now required to use KENNY CLAMPS (or equivalent in some counties). It’s a requirement from the local AHJ
@OnusofStrife
@OnusofStrife 11 ай бұрын
North Carolina also has panels outside as well.
@alphasaiyan5760
@alphasaiyan5760 Жыл бұрын
Also FPE breakers are backwards from other breakers when they are on and off. On is toward the outside and off is to the inside. Which is actually a code violation.
@johnkreno2488
@johnkreno2488 Жыл бұрын
Just curious, the hot conductors on the left are red and black, doesn't that indicate that they are either 220 or multi wire branch circuits ? Doesn't that require that both breakers that are in a black/red pair have a mechanical link between the breakers ? I don't know if those covers that you are adding on the main service entry wires are required, but I really like those. It's a nice touch.
@electricalron
@electricalron Жыл бұрын
Yes, a MWBC does require a common trip circuit breaker and that’s what’s there.
@Skialta2024TX
@Skialta2024TX Жыл бұрын
Have you had any install requests for energy monitoring panels like the Leviton Load Center or the Sense Energy Monitor/Square D Wiser? That would be interesting to see.
@TheTubejunky
@TheTubejunky Жыл бұрын
Those are very intricate it seems. I've seen them in solar installs & it makes well hell of a rats nest in the panel.
@xenadu02
@xenadu02 Жыл бұрын
CA requires main service disconnect outside now and they love integrated meter base panel units so that's why some homes have the main panel outside. However here in SF most homes have it in the garage including the meter, though the rules very recently changed not to allow that.
@electricalron
@electricalron Жыл бұрын
No exterior service disconnect until at least 9/6/23 in New Jersey.
@Bill_N_ATX
@Bill_N_ATX Жыл бұрын
The exterior service disconnect is just so much safer for firefighters. My house in Texas was built with one in 2000 but I’m not sure if it was the usual case. My home was custom built by an engineer and it shows all over the place in features that were way ahead of their time.
@FHES2005
@FHES2005 Жыл бұрын
As always great work But I got a question with all the electronic devices around these days wouldn't have been ideas to upgrade to a 200 amp service
@TheTubejunky
@TheTubejunky Жыл бұрын
I'm assuming size of dwelling and perhaps price may have been a factor. I would also have suggested the 200amp upgrade.
@haweater1555
@haweater1555 Жыл бұрын
If the house is equipped with gas stove and water heater, the upgrade to 200 A may not be justified. If it has a gas clothes dryer (not very common), even less.
@edisont.picard4112
@edisont.picard4112 Жыл бұрын
You install what the customer is willing to pay for.
@Bob.W.
@Bob.W. 10 ай бұрын
They are selling it, so just doing the minimum. Need to ditch the FPE panel.
@wiley0714
@wiley0714 Жыл бұрын
Rookies Questions : Why (2) outside grounds, and not just the (1)? Is that code? Is you have to add 15/20 amp breakers would you distribute as evenly as you could on each phase? If a ground bar will/does allow for (2) grounds, say 2/3 #14's, would you double them to save a spot on the bar when installing for future add on per say? When you put in the ground rods, why the distance out from the house ( to protect foundation from water, or is there a distance per code away from the home? I know you said (6 feet apart from each rod). Just picking your brain there for knowledge. Great work. Thanks for the time and effort after long days of self labor. esp to edit and upload etc.
@electricalron
@electricalron Жыл бұрын
Will, I’m working now and will respond to each of your questions when I get a moment at my desk this evening.
@electricalron
@electricalron Жыл бұрын
Only (1) ground rod is required if you can prove to the inspector you have 25 ohms or less to earth. If not, then (2) grounds are required. Equal distribution of circuits on a single-phase service is null and void. It does not matter. If the panel specs (2) equipment grounds per grounding terminal than you are good to use (2) EGC’s of the same size (#12/ 14 AWG). The spacing of the ground rods is 6 feet because the soil could be different at that distance (I think).
@camheady235
@camheady235 Ай бұрын
Don't pound your ground rods too close to the foundation because you may hit the footing which is wider than the foundation wall. BrickSaver LLC
@siriusjones6719
@siriusjones6719 Жыл бұрын
Great video, as always sir. What is that fold up table at 32:50? I got to get me one of those!
@electricalron
@electricalron Жыл бұрын
Dewalt like $99 Home Depot
@everythinghomerepair1747
@everythinghomerepair1747 Жыл бұрын
I’m from AZ. It’s true all panels are outside lol. And the newer ones have AFCI breakers that bake in the heat all day.
@hugh007
@hugh007 Жыл бұрын
I had my old 200 Amp Federal box changed out about 20 years ago. The house was built in '73. I'd have thought they were all gone by now. Question: My electrician had JCP&L disconnect the drop for him and re-connect after the work. Was that a requirement in Morris county NJ or by someone else? Looks like you did it yourself. Thanks. Great videos.
@electricalron
@electricalron Жыл бұрын
Maybe your guy just wasn’t comfortable doing this himself. Pretty sure JCPL charges to come out and disconnect/ reconnect.
@haweater1555
@haweater1555 Жыл бұрын
What is the brand of the new panel? You don't have to use arc fault breakers?
@jsb7546
@jsb7546 Жыл бұрын
Dayum up in the 90's already not excited for this summer at all bouta triple digits all summer just like last year.
@FreeAmerican-mm2my
@FreeAmerican-mm2my Жыл бұрын
My city requires that the SE in the weather be in conduit - North Alabama We can use it from the meter to the panel without conduit if less than 6 feet.
@Framdark
@Framdark Жыл бұрын
Might me a dumb question but why does the neutral cable have no insulation around it if it carries return current? Because wouldn't when you have to run it through the circuit panel it would touch the metal box causing issues and what about arcing? Again this might be a dumb question so sorry. Love your videos
@howtodoelectrical200
@howtodoelectrical200 Жыл бұрын
This is one of my fav electrical channels 🫡 knocking work out solo 👍🏽, great teaching as well 👍🏽
@electricalron
@electricalron Жыл бұрын
I appreciate that!
@TheTubejunky
@TheTubejunky Жыл бұрын
Yeah big props to him for solo sweating through the days! I think he may have seniority over most other employees: (unless it's a one man operation from boot)
@colinpenfold2971
@colinpenfold2971 Жыл бұрын
From UK. Is the ground connected to the Neutral at the distribution board? Here we have this system in many installations.
@electricalron
@electricalron Жыл бұрын
Yes. It’s called Solidly Grounded.
@user-le1kj1mq4b
@user-le1kj1mq4b Жыл бұрын
I notice you don’t leave any slack in the meter box? Just curious. Thank you
@budnesto
@budnesto Жыл бұрын
@ElectricianRon, I thought 200amp service is the norm now when doing a panel replacement ?
@electricalron
@electricalron Жыл бұрын
This guy was just eliminating the FPE panel to sell the house.
200A Service Upgrade | Garwood, NJ  #electrician #serviceupgrade
36:06
Electrician Ron
Рет қаралды 29 М.
МАМА И STANDOFF 2 😳 !FAKE GUN! #shorts
00:34
INNA SERG
Рет қаралды 4,9 МЛН
Heartwarming: Stranger Saves Puppy from Hot Car #shorts
00:22
Fabiosa Best Lifehacks
Рет қаралды 21 МЛН
ОСКАР ИСПОРТИЛ ДЖОНИ ЖИЗНЬ 😢 @lenta_com
01:01
FEDERAL PACIFIC ELECTRICAL PANELS - why their panels are dangerous
23:27
HAD TO STOP THE APPRENTICE - FIRST BOARD SWAP
15:55
Bright Spark Electrical (midlands)
Рет қаралды 7 М.
100 AMP SERVICE UPGRADE | Seaside park, N.J.
46:38
Electrician Ron
Рет қаралды 14 М.
Upgrading an electrical service from 100A to 200A | Clark, New Jersey
27:57
100 AMP TO 200 AMP PANEL UPGRADE | Sunny Side Linden, NJ.
20:26
Electrician Ron
Рет қаралды 50 М.
Рука застряла в заборе
0:27
RICARDO
Рет қаралды 1,5 МЛН
Let me show you (P12)
0:21
Discovery Boy
Рет қаралды 6 МЛН
Черешня из Китая размером с КУЛАК: На стероидах?
0:12
Собиратель новостей
Рет қаралды 6 МЛН
Immersive outdoor dining Chinese rural dog Little puppy Rural dog
0:30
Country Puppy
Рет қаралды 14 МЛН
Он просто решил сэкономить на плитке, но...
0:25
ВЕЛОСИПЕД ЗАГОВОРИЛ
0:15
KINO KAIF
Рет қаралды 14 МЛН