Fujitsu Ductless Heat Pump Mini Split 5 Zone Not Heating - Needs Refrigerant Every Year!

  Рет қаралды 7,356

Mikey Pipes - Pipe Doctor Plumbing & Heating & Air

Mikey Pipes - Pipe Doctor Plumbing & Heating & Air

Күн бұрын

Пікірлер: 74
@wundo9372
@wundo9372 3 сағат бұрын
Hey Mikey, local supply houses should sell UV injection kits for refrigeration systems so you can go back later with the ultraviolet light and see where the leak is coming from.
@mikegooch123456543
@mikegooch123456543 10 сағат бұрын
I was wondering why you said that “in such a negative fashion”. Thanks for always keeping it real.
@kens.3729
@kens.3729 9 сағат бұрын
They either have Kids that are Louder than the Smoke Detector or the TV is Loud because their Hearing Aid Battery is also Dead. 🤪👎
@pony053
@pony053 8 сағат бұрын
No judgement from here! I was on a roof this morning, it was 10 degrees, iced flat roof. PS...not a fan of Lennox either, but even less of mini-splits!. Enjoy and learn from your videos, thanks!
@benjaminwallace4626
@benjaminwallace4626 6 сағат бұрын
I have an elite series Lennox 5 ton single stage condenser, I’ve had 12 terrific years out of it, but when it leaks, ill be putting in Bosch
@Jim.D
@Jim.D 11 сағат бұрын
My 2 ton Lennox ac is 24+ years old and last year I had to replace the capacitors for the first time, not bad IMO.
@stevencossaboon3237
@stevencossaboon3237 10 сағат бұрын
Nice work Mike.
@SeatonHeatingAC
@SeatonHeatingAC 10 сағат бұрын
Always have my support!!! I always smash that thumbs up!!! And I always try and watch the whole video so I don't make stupid comments like so many do :).
@bigmoe451
@bigmoe451 5 сағат бұрын
I had to braze a pinhole in my condenser on my 7 year old Diakin 11/2 ton 7 year old mini split. No pan heater unit and ice bent the bottom tube.
@aperson9495
@aperson9495 9 сағат бұрын
The smoke detector chirp 😵‍💫
@helpfulhippo3744
@helpfulhippo3744 7 сағат бұрын
Hi Mike, Would it make sense to have injected some UV Dye while you were charging ? Might make finding the leak a faster prospect in the Spring, but might also just make the next guys job easier if they don't follow up with you... Are the inside units flare fittings also ?
@richroj
@richroj 9 сағат бұрын
that was very good Mike, it sounds like option number 5 is the way to go 👍
@PipeDoctor
@PipeDoctor 9 сағат бұрын
Thanks 👍
@giorgosktoridis903
@giorgosktoridis903 5 сағат бұрын
Nuh for a 4 year old system you should fix the leak probably is in the flare connections on the indoor units
@bradmarshall7075
@bradmarshall7075 9 сағат бұрын
In 2015, Lennox Industries Inc. settled a class action lawsuit over defective evaporator coils in its air conditioning and heat pump systems. The lawsuit, Thomas v. Lennox Industries Inc., alleged that Lennox knew about the problem but did not address it. Lennox denied all claims but agreed to the settlement to avoid further litigation.
@PipeDoctor
@PipeDoctor 9 сағат бұрын
That's interesting, but……all the manufacturers had same class action
@daanski82
@daanski82 2 сағат бұрын
Mike, your not Dumb. Your a human and it seems you need some time to relex. Mistakes happen. And he: to "perfection" is say: "WABI-Sabi"
@Liam25025
@Liam25025 9 сағат бұрын
How does a plumber go about getting into hvac?
@xcmskim4
@xcmskim4 8 сағат бұрын
The warranty on the Fujitsu will expire next year (standard warranty of 5yr parts and 7 yr compressor). I'm surprised that the homeowner doesn't want to get that fixed before the warranty ends.
@Mridgwell
@Mridgwell 11 сағат бұрын
Was hoping you had solution for working on these heat pumps in the cold , portable heater tent electric blanket 😂😂😂 seeing how this will be the norm in NY soon
@PipeDoctor
@PipeDoctor 11 сағат бұрын
Don’t remind me
@joefesi5266
@joefesi5266 11 сағат бұрын
Who is that...a 2 handed Mikey...I didn't even know you had a left hand lolol
@JoeSmith-ov4go
@JoeSmith-ov4go 10 сағат бұрын
WOW! Mikey working! Looks like retirement time...
@PipeDoctor
@PipeDoctor 10 сағат бұрын
No, this is just a day in the life.
@Steve-bm2zm
@Steve-bm2zm 11 сағат бұрын
I love my Lennox heat pump. 15 years and no problems.
@TheRAMBO9191
@TheRAMBO9191 11 сағат бұрын
Dun dun dduuunnnn
@MassiveGarbage
@MassiveGarbage 10 сағат бұрын
Stay away from their furnaces. Absolutely junk. Unless you like cracked heat exchangers and carbon monoxide.
@bradmarshall7075
@bradmarshall7075 9 сағат бұрын
You got lucky!!!!
@Bob.W.
@Bob.W. 10 сағат бұрын
Our HVAC guy wisely didn't show up today since it was below 0degf. Tomorrow I hope. It's warming up
@alfonsovelazquez9662
@alfonsovelazquez9662 11 сағат бұрын
Nothing better then working with refrigerant when it's 25 deg out
@jasonmonday6565
@jasonmonday6565 11 сағат бұрын
Hey Mikey, how's it going???
@PipeDoctor
@PipeDoctor 11 сағат бұрын
Hanging
@shawnchapman5916
@shawnchapman5916 6 сағат бұрын
What's your top 5 brands of air handlers/condensors?
@dstevens379
@dstevens379 8 сағат бұрын
Up here in Maryland most companies won’t mess with R22 gas and go. My company getting $350 a lb. I’ve put more R22 this yr then last 5-10 yrs. You can lead a horse to water but you can’t make them drink. $150 a lb for 410 you can’t only do what customers want. Some will only realize the truth after wasting thousands then still have to replace at end on day. Then look for the cheapest guy in town to do replacement. Then call back a yr later when it’s not working. LOL It’s a business at end of day not a charity! Keep getting paid SiR
@aks20002
@aks20002 8 сағат бұрын
30 lb. R22 ( legit seller and not the shadowy ones ) are widely available online for approx. $900 , which is $30 / lb. You can get it cheaper thru local sources some times. My HVAC guy let me buy it for $500 from a local seller , when he fixed a leak in my old but trusty R22 system just few months back here in Bay Area. He works by hourly rate, which was not cheap but well worth it particularly with his high level of professionalism and integrity.
@dstevens379
@dstevens379 8 сағат бұрын
Well my hats to you Sir you got your R22 Fixed that since 2020 you can’t buy a dry outdoor unit and charge it with R22. Hopefully it lasts another 2 decades. At the end of day you will be replacing that system but you saved some money to kick can down road.
@aks20002
@aks20002 6 сағат бұрын
@@dstevens379 Yes, I am already on the way to replace my R22 systems. I planned to add multiple single zone heat pumps - one at a time over 2-3 years and existing system will allow me to have that breathing space. Reason I commented was to make people aware that you can still find R22 at reasonable rate if you look around. Bigger challenge is to find a HVAC guy who is willing to touch such a system.
@EricMosegard
@EricMosegard 9 сағат бұрын
Looks like dye on the service caps
@JoseDelao-z9o
@JoseDelao-z9o 8 сағат бұрын
I have a question? Are the branch boxes control boared available?
@bradmironik6137
@bradmironik6137 7 сағат бұрын
Well, since the client signed the document, I wouldn't service this unit until you get an answer in writing.
@jimmyg6215
@jimmyg6215 9 сағат бұрын
Do u think that discolored port has been missing its cap or was that schrader valve leaking? Just asking for a friend ☺️
@ianwally818
@ianwally818 9 сағат бұрын
Hey Mikey, How old is too old to fix one of these units ? Thanks
@scottmaz4063
@scottmaz4063 11 сағат бұрын
#3😂😂😂 enjoy your vacation mikey
@PipeDoctor
@PipeDoctor 11 сағат бұрын
Ty. We are:)
@roberth7559
@roberth7559 9 сағат бұрын
Replace lineset - not the system
@EricMosegard
@EricMosegard 9 сағат бұрын
I would find mouse nests in the tops of these things all the time
@8799crosby
@8799crosby 10 сағат бұрын
I just worked in a Fujitsu in Boston same deal it has a leak , can u charge it while it’s running in heat mode , I could not find a bypass port , but I noticed or your gauges the low side was high and high side was low , usually heats pumps in heat mode they read the same , hence the bypass port .
@eastpark4864
@eastpark4864 10 сағат бұрын
29 degrees is not cold, geez!
@kens.3729
@kens.3729 9 сағат бұрын
Options 1-3 are Worthless and Options 4-5 are the Real Options. 🤔👍
@PipeDoctor
@PipeDoctor 9 сағат бұрын
I know what you mean!
@MassiveGarbage
@MassiveGarbage 10 сағат бұрын
Its hard to not be dumb when its cold.
@craighvac1808
@craighvac1808 9 сағат бұрын
85 psi at 30 degrees Fahrenheit is nothing lol?
@kens.3729
@kens.3729 10 сағат бұрын
Lennox has always been Garbage but the $ 64,000 question is who talked them into purchasing three (3) of them ? 🤪👎
@williamlloyd3769
@williamlloyd3769 9 сағат бұрын
Probably seemed like a good idea at the time
@scottmaz4063
@scottmaz4063 11 сағат бұрын
The 410A is the new R22 prices?
@Balticblue93
@Balticblue93 5 сағат бұрын
R22 30lb bottle is $800 R410A 25lb bottle is $204.00 R32 20lb bottle is $279.00 R454B 20lb bottle is $432.00 Rough estimates, of course. You can find it less expensive and more expensive depending on distributor and account discounts.
@jph77
@jph77 10 сағат бұрын
Vevor fever!
@Chris_In_Texas
@Chris_In_Texas 11 сағат бұрын
You need to add a new service that you offer... Battery and or smoke detector replacement. How do all these people leave the damn things beep all the time. I get annoyed just watching these videos with them beeping. Great up-sell advantage for home safety. Can check date on detector and replace if over 5-7 years old. Also check CO detector, not sure if there are any rules in your area requiring them in all houses. Would be great opportunity, for those you can get the 10year version that have built in lithium batteries and are just a throw away at the end of 10 years. Pretty small boxes and can carry them on the truck, along with the try of 9V batteries... 🤠👍
@mikedamron3642
@mikedamron3642 11 сағат бұрын
Dementia is real bro. I get those brain parts too.just focus
@ivancook1247
@ivancook1247 9 сағат бұрын
Because they got a patent on 454b and can dictate price where any manufacturer can make r32 which brings price down and a better , safer refridgerant, all political why everyone but daikin went to 454b, one refridgerant heck of alot better than a blended
@bradmarshall7075
@bradmarshall7075 9 сағат бұрын
Leaky Lennox!!!!!!
@dmitrynetes3102
@dmitrynetes3102 11 сағат бұрын
Do you think heat pumps can heat us in the northeast reliably? Love your work. By the way you are careless and don’t care about the environment 😂
@PipeDoctor
@PipeDoctor 11 сағат бұрын
No
@jimmyg6215
@jimmyg6215 9 сағат бұрын
My Mitsubishi is good to about 10F here in New England . After that the electrical usage jumps from about 800-1100 watts to around 2100 watts. Not efficient. Pellet stove is my savior for those really cold days. I am sure the technology will get better in time but 0F is brutal on mini split heat pumps. Geothermal is probably a better choice in my area.
@geekgirl913
@geekgirl913 9 сағат бұрын
I have a Mitsubishi and running it below like 35° is more expensive than using my steam boiler, which is 225K BTUs... We used close to 2,800 kWhs in one month while waiting to replace said boiler. All that and we were still cold. Nothing heats like hydronic heating.
@jimmyg6215
@jimmyg6215 9 сағат бұрын
@@geekgirl913 yea the KWh does add up quick. I had to replace a fan in my pellet stove in December. Part was backorder for almost the whole month and even with my minimal December solar production it adds up fast using the minisplit.
@geekgirl913
@geekgirl913 9 сағат бұрын
@@jimmyg6215 yeah I want a pellet stove insert for our fireplace, they seem to be the most cost efficient.
@guyhulscher6857
@guyhulscher6857 7 сағат бұрын
Do not EVER add sealant to a fujitsu. It will go south for you. Dye only if necessary.
@frankigi
@frankigi 6 сағат бұрын
please stop with those thumbnails...
@tuffram2165
@tuffram2165 9 сағат бұрын
Lennox is the worst residential hvac system on the market period. I'll take a Goodman over Lennox. We go ahead and tell our customers when they start having issues with their Lennox system to be prepared because it's all down hill.
@TheRAMBO9191
@TheRAMBO9191 11 сағат бұрын
we guna figure it out? Yes. we guna do it today? absolutely not. I love that🤣 same. 🤣🫡🥃
Proper Techniques When Replacing Central AC Equipment Explained
20:08
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 9 М.
Tenant Keeps Complaining About No Heat - Landlord Says "Fix It Regardless of Cost!"
22:18
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 150 М.
Мен атып көрмегенмін ! | Qalam | 5 серия
25:41
Каха и дочка
00:28
К-Media
Рет қаралды 3,4 МЛН
Арыстанның айқасы, Тәуіржанның шайқасы!
25:51
QosLike / ҚосЛайк / Косылайық
Рет қаралды 700 М.
OLD GAS FURNACE WILL NOT HEAT HOUSE
59:19
steven lavimoniere
Рет қаралды 8 М.
The Mini Split - REINVENTED.
31:23
The DIY HVAC Guy
Рет қаралды 530 М.
Day In The Life - Commercial HVAC Technician
27:30
HVAC For LIFE
Рет қаралды 7 М.
HVAC Silver Soldering vs Brazing vs Brazing While Flowing Nitrogen!
18:42
AC Service Tech LLC
Рет қаралды 157 М.
No Heat Service Call Trane Package Unit
22:03
HughesMan HVAC
Рет қаралды 6 М.
How to Complete a Successful Central AC with Furnace Preventative Maintenance Service Call
14:55
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 11 М.
Ultimate End of Landlord Tenant Heating HVAC Disputes - Splitting Zones at Boiler
26:00
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 12 М.
Ultimate Landlord Hack - Tenants Can’t Complain About Heat Ever Again!
15:19
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 19 М.
Every Time On The Weekends It Stops Working
20:39
HVACR Survival
Рет қаралды 14 М.
Мен атып көрмегенмін ! | Qalam | 5 серия
25:41