Mermaid Manufacturing explains how to change the filter dryer on a Mermaid Medi-Kool Climate Controlled Cabinet.
Пікірлер: 25
@Laurel-Crowned3 жыл бұрын
Thank you for showing to cut the new dryer ends nobody else showed that part.
@robgraham12044 жыл бұрын
That pipe is kinked
@MainADMlN3 ай бұрын
As a school-trained licensed and certified HVAC technician. This is working the easy lazy way, which sooner or later catches up to you. Referring to the refrigerant as "Freon" gave me the hives. No deburring? Lazy. The bending is so badly made it kinked the tube, which produces flow turbulence. Not protecting the filter from the brazing heat? Nice way to possibly damaging it. Having nitrogen and planning on using it, but not flowing it during the brazing... oh boy. Carbonization in the inside. That filter might need replacement soon again. But if you only didn't refer to the gas as "freon"....
@hornzhou17353 жыл бұрын
What kind of solder material are you using to solder?
@peniasnyirenda8095 Жыл бұрын
Nice job my fellow technician
@Cholla-Ranch Жыл бұрын
Very helpful. Thank you.
@engineerahmad63753 жыл бұрын
I have a problem. When I try to move a refrigerator from one place to another on the backside the oil inside the compressor return back to the filter and damages it. Is that video help me to avoid that?. Any other solutions could help to prevent the oil from going out to the filter and damage it like a one-way valve or other ideas. Please suggest me solutions. Thank you.
@patricioaguayo90883 жыл бұрын
How about dryer on any reefer unit. Thank you
@jd57873 жыл бұрын
Just wondering : why does the filter need to be changed when replacing a compressor? Is it something that can be done in stages? (change filter on day 1 and compressor on day 2?). Thanks
@vihayster3 жыл бұрын
filter dryer is there for catching moisture, chemicals and copper oxides created during brazing process (because they don't use dry nitrogen at time of brazing). After years of work when you change compressor that filter is almost clogged out and needs to be replaced. If you don't replace it, it may work few years OR only few weeks before gets clogged. When you install new compressor you create even more oxides that have to be filtered. Both compressor and filter should be brazed at the same time so the system is sealed quickly to prevent moisture getting in. New compressors and filters comes with sealed both ends so compressor oils (which very often are hygroscopic) and filter's desiccants are protected until installation time.
@jd57873 жыл бұрын
@@vihayster thank you! Much appreciated :)
@YESHUASAVES777YYY10 ай бұрын
My dryer filter is very cold any ideas ?
@markspc13 жыл бұрын
Your solder is bubbling up, too hot frame.
@kcengiz3633 жыл бұрын
How do you understand you got problem in the filter dryer?
@davidcromer2675 Жыл бұрын
95% of the time that’s the clog if you have blockage. There are ways to test. You are going to replace that anyway during a service where you are going into a sealed system.
@Freonleon4 ай бұрын
Hack, using wire strippers to cut the cap tube, and drier.
@Skoalman86854 жыл бұрын
You kinked the pipe and then didnt even talk about pulling a vacuum lol.
@johnflanagan41034 жыл бұрын
No nitrogen purge while brazing. What a mess.That cap tube will plug up.😨😳
@vihayster3 жыл бұрын
yeah...seems to be new normal. I haven't seen any videos with nitro in use during brazing refrigerator components. I think everybody assume that filter will catch everything, lol
@christopher61472 жыл бұрын
@@vihayster I haven’t seen any either. strange
@ramavtar892073 ай бұрын
👍🇮🇳🕉️🙏
@reefermadd.22043 жыл бұрын
Shop mentality . That was the lazy way of doing that.