How To Convert 120V Receptacles Or Branch Circuits To 240V! (Also 240V To 120V)

  Рет қаралды 1,403,709

electronicsNmore

electronicsNmore

3 жыл бұрын

Learn how to easily convert 120v electrical receptacles or dedicated branch circuits to 240v, or convert a 240v receptacle (Branch Circuit) to 120v. A step by step DIY electrical guide. How to convert 120v or 240v electrical outlets, properly wire a circuit breaker panel and branch circuit using single and double pole breakers. Enjoy!
DISCLAIMER: Proper safety measures/precautions must be taken when working on 120v or 240v AC mains wiring(branch circuits). The potential exists for serious injuries, property damage, or death. If you're uncomfortable doing as shown in this video, or don't fully understand what was done, then you SHOULD NOT touch the wiring! This channel will not be held liable for the use or misuse of information contained in this video. The person modifying the wiring accepts full responsibility for his/her actions. ELECTRONICSNMORE LLC
A really good, low cost digital multimeter with AC/DC clamp: amzn.to/38L0OlW
*Amazon Affiliate Link Above (I earn a small commission from qualifying purchases)
CLICK BELOW for my extensive video playlists!
/ electronicsnmore
Support the creation of new videos on my channel by watching ads placed on my videos, shopping for items shown in my videos(No additional cost to you) at the Banggood & Aliexpress links provided. You can also support my work by making a Paypal donation. All donations, big or small, are greatly appreciated since many of the videos I produce don't go viral and make all the hours of work I put into them worthwhile. Thank you!
Aliexpress:s.click.aliexpress.com/e/_dY3...
Amazon: amzn.to/2Lg902l
Banggood: bit.ly/2COi2P0
Banggood Flash Deals: bit.ly/2HBu9oq
(Affiliate Links)
Paypal link: paypal.me/electronicsNmoreYT
Bobby Tectalabyss: Thanks for your generous $5 donation!
Jeff Barr: Thanks for your generous $25 donation!
xrayjim: Thanks for your generous $25 donation!
Ryan Pedersen: Thanks for your generous $20 donation!
Wanda Thomas: Thanks for your generous $50 donation!
Peter Hines: Thanks for your generous $10 donation!
Verinspec: Thanks for your generous $10 donation!
Jason Enright: Thanks for your generous $6 donation!
Diega Kendrick: Thanks for your generous $10 donation!
Technovative Products: Thanks for your generous $5 donation!
Jeff Karrow: Thanks for your generous $5 donation!
Iven Brown: Thanks for your generous $5 donation!
Thomas Herrick: Thanks for your generous $20 donation!
Richard Frisch: Thanks for your generous $10 donation!
Bruce Howard: Thanks for the generous $5 donation!
Jayantha Gabbalage: Thanks for the generous $20 donation!
Joseph Vanderbosch: Thanks for the generous $10 donation!
Theodosia Gougousi: Thanks for the generous $10 donation!
Ric Dezorzi: Thanks for the generous $5 donation!
Randy Schader: Thanks for the generous $5 donation!
Hong Lin: Thanks for your generous $20 donation!
Thanks For Watching!
**If you enjoy watching my videos, then be sure to SUBSCRIBE & click the notification bell(set to "ALL"), SHARE links to my videos with others, rate "THUMBS UP", and check out my extensive video playlists for many other videos of interest to you. Doing so helps to ensure that many more videos will be uploaded to my YT channel in the future.**

Пікірлер: 784
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Remember guys, what you see shown in this video is ONLY for 1 or 2 receptacles that you'd like to convert on a DEDICATED Branch Circuit. You MUST confirm that there's nothing else on the branch circuit that you intend on modifying. The branch circuit used in this video for the demonstration was for a washing machine. You can also convert a 240V wall A/C receptacle in a room to 120V if the home no longer uses wall A/C units because the home was modernized with central air. Thanks for watching!
@stephensaines7100
@stephensaines7100 2 жыл бұрын
[ You can also convert a 240V wall A/C receptacle in a room to 120V if the home no longer uses wall A/C units because the home was modernized with central air.] Only if it's split rail feed with a neutral. Many 240V feeds are two wire.
@dlloyd6300
@dlloyd6300 2 жыл бұрын
Is there any reason that you have to make it a single receptacle, if you want to plug in multiple 240 volt capable items?
@draketracy6969
@draketracy6969 Жыл бұрын
Is it possible to split the black wire instead of converting the neutral to a hot line? In my case I have limited brakers and lights are also hooked up to the same braker.
@dlloyd6300
@dlloyd6300 Жыл бұрын
@@draketracy6969 that would not double the voltage. You're just making a pigtail which does nothing.
@draketracy6969
@draketracy6969 Жыл бұрын
@@dlloyd6300 lol thanks I replied to my other comment ..
@ProjectFarm
@ProjectFarm 3 жыл бұрын
Another terrific "how to" video that's taught me something I need to know! Thank you!!
@electronicsNmore
@electronicsNmore 3 жыл бұрын
Thanks for watching! I'm looking forward to tomorrow's video!
@jimhatch14
@jimhatch14 2 жыл бұрын
Hi PF, you should test accuracy of electricians torque drivers, their cost of periodic calibration, etc. Both on incoming performance, (when sent in for cal, is it out of spec? Then find the last year's homes were loose?) and after re-calibration. Myself, I would trust a decades experienced electrician over a so-called torque wrench.
@elkameleong
@elkameleong 2 жыл бұрын
But are you going to test that? 👍🏼
@mr.e8543
@mr.e8543 2 жыл бұрын
didnt expect to see project farm here. thats awesome lol
@HunterJohnson77
@HunterJohnson77 2 жыл бұрын
@@mr.e8543 why?
@moniielka2458
@moniielka2458 9 ай бұрын
I usually hate instructional videos because they're always way too long but only have about 2 mins of real talk. Sure this video was slow but it broke everything down perfectly for a beginner. Thank you
@electronicsNmore
@electronicsNmore 9 ай бұрын
Glad you liked the video!
@negritorican
@negritorican Жыл бұрын
Wow the way you explained everything so well that anyone can understand it. I get nervous when seeing people mess with the circuit breaker without turning it off. You obviously know what you are doing but mistakes always happen. People ALWAYS turn off your circuit breaker when working on it.
@fofobraselio
@fofobraselio 2 жыл бұрын
I needed to change a 240v baseboard heater line into a 120v receptacle and this is the video I needed! Thanks for the know how! Works great and now I have an extra circuit to play with.
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Great to hear!
@olegpetrushak6754
@olegpetrushak6754 2 жыл бұрын
Good explanation. One crucial point is that it's mentioned to turn a breaker on at one point. The tutorial then continues as if the breaker is turned back off, however, this is never mentioned. Timestamp at 7:10. If a beginner is watching this, they may experience a shock because of this. Other than that, it was complete and explained well.
@bombswabs3041
@bombswabs3041 2 жыл бұрын
Thankyou for your video. I might as well have electro-phobia but I've seen others make instructional videos describing the same. I'm also in a bind and just cant get 220 wired in from an "expert" and also cant pay "expert" prices for a lil ole outlet. Its cool, I will do this and am responsible enough to cross compare your information with a massive amount of information I gather from other sources. As a responsible human I can arrive at a consensus and choose how to proceed. Thankyou for your contribution to the DIY space. People Like me are very thankful and will not BLAME YOU if we screw this up! You rock!
@MAXXPLAZMA
@MAXXPLAZMA 7 ай бұрын
BY FAR the best information ive seen so far... EXCELLENT VIDEO ....THANK YOU If everybody that has ever done a tutoriol video was as concise as this ...THE WORLD WOULD BE A BETTER PLACE.
@electronicsNmore
@electronicsNmore 7 ай бұрын
Glad to hear that you enjoyed my video! Be sure to check out my very wide range of videos and share. Thank you
@supergiantbubbles
@supergiantbubbles 10 ай бұрын
Thanks for being so concise and thorough. You're a good instructor.
@edcook9747
@edcook9747 Жыл бұрын
Excellent presentation. Concise and just enough views of the actual work being done. You got right to the point without a lot of unneeded chatter. Have seen a number of these and yours is the best. I already knew how to do this but I like watching some presentations out of curiosity. Also worthwhile as a memory jog if haven’t done in awhile. Nice presentation!
@HenryStarling
@HenryStarling 3 жыл бұрын
One of, if not the best, video explaining this conversion. Thanks.
@electronicsNmore
@electronicsNmore 3 жыл бұрын
Glad it was helpful Henry! Be sure to look over my extensive video playlists below for many other videos of interest to you, and most importantly take one minute to share a link to my channel with others on social networking sites. Thank you! kzbin.infoplaylists
@50plusmtbatbp94
@50plusmtbatbp94 5 ай бұрын
This is soooo old but soooo gooood! The knowing the possible is good enough, the way the information was related makes it stick in your head. Thank you....
@willdorten6867
@willdorten6867 2 жыл бұрын
Man this video is awesome, i was working as an electrician's helper for awhile not too long ago, but the boss wasn't really keen on teaching me things like this. However, i watched him and asked questions, and learned some. I'll also admit, i'm not as quick as a learner as I used to be. Yet, from all that and watching this. it's safe to say I understand the basics. I'd be the perfect entry level electrician's helper for sure.
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad you liked it! Be sure to look over my video playlists below for many other videos of interest to you, and most importantly take one minute to share a link to my channel with others on social networking sites. Thanks Will kzbin.infoplaylists
@poransingh8420
@poransingh8420 2 жыл бұрын
This was an awesome 👏🏽 video!! Literally followed what you said and did, but with 12 gauge wire, and works perfectly for my 230v 15amp AC!! Thanks bro!!
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Great to hear!
@calvinflager4457
@calvinflager4457 Жыл бұрын
I really like the detail in your presentation. Thanks for the great presentation. A minor safety tip is hold the receptacle so that if your screw driver slips it won't skew your holding hand.
@electronicsNmore
@electronicsNmore Жыл бұрын
Glad you enjoyed the video Calvin!
@design8studio
@design8studio Жыл бұрын
This is one of the most helpful videos I have found. Thank you so much. I learned so much.
@dandowns9669
@dandowns9669 2 жыл бұрын
Excellent video. All I'm saying is this. Experience or not, keep poking around in a hot electrical panel with anything, especially a metal screwdriver and your gonna get bit! I know it sounds backwards, but experience at this point is your enemy. No doubt you already know all this. Be safe..
@is_what_it_is
@is_what_it_is 2 жыл бұрын
my thoughts exactly, as i was waiting to see some arc blast.
@WoodgemanX
@WoodgemanX 2 жыл бұрын
At least use insulated screwdrivers.
@GaryYoung-eq1ph
@GaryYoung-eq1ph Жыл бұрын
Rubber!!?
@adamwortham6426
@adamwortham6426 11 ай бұрын
Rubber saves lives🤣🤣
@lamar07103
@lamar07103 7 ай бұрын
​@@adamwortham6426prevents life's also
@rupertlundquist8741
@rupertlundquist8741 2 жыл бұрын
Very clear, no nonsense, learned a ton. Thank you very much!
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Great to hear Rupert! Be sure to rate thumbs up, consider subscribing if you like a wide range of helpful and informative videos, and look over my extensive video playlists below for many other videos of interest to you. Taking one minute to share a link to my channel with others on social networking sites would be greatly appreciated. Thanks kzbin.infoplaylists
@Hillaryalsbury
@Hillaryalsbury Жыл бұрын
I can't believe this was free. Thank you!
@electronicsNmore
@electronicsNmore Жыл бұрын
You're welcome!
@floorpizza8074
@floorpizza8074 3 жыл бұрын
Very well done "how-to" video. Thank you!
@electronicsNmore
@electronicsNmore 3 жыл бұрын
Glad you enjoyed it! Be sure to look over my extensive video playlists below for many other videos of interest to you, and most importantly take one minute to share a link to my channel with others on social networking sites. Thanks kzbin.infoplaylists
@kkutube1972
@kkutube1972 2 жыл бұрын
You explained it so well. Thanks.
@kaipo8489
@kaipo8489 Жыл бұрын
One of the best elec videos that ive seen.
@boseashish
@boseashish 7 ай бұрын
How beautifully explained. No confusion at all but yes some basic knowledge is required to appreciate this excellent video.
@USAMark70
@USAMark70 3 жыл бұрын
Perfect timing! I found an old 240v Craftsman air compressor in the trash and lugged it home. I'm curious to see how it works! Just need to swap out one of my 120v outlets in the shop to 240v. This video was very helpful! Thank you!
@electronicsNmore
@electronicsNmore 3 жыл бұрын
You need to make sure the receptacle is on a dedicated branch circuit before converting, otherwise you'll end with 240v at a 120v receptacle.
@USAMark70
@USAMark70 3 жыл бұрын
@@electronicsNmore I could see that causing a problem for sure! Will definitely make sure there is nothing else on the circuit! Love your videos! Thanks again!
@daddydawg1902
@daddydawg1902 Жыл бұрын
Nice video. Very clear explanations. Thank you for your time producing this.
@electronicsNmore
@electronicsNmore Жыл бұрын
You're very welcome!
@mariochacon1058
@mariochacon1058 Жыл бұрын
I went to training school many years ago and I almost forgot. Thank you.😢
@InCountry6970
@InCountry6970 Жыл бұрын
Very straight forward, great video !
@clivefutube
@clivefutube 3 жыл бұрын
Love the extra suspense element of having it live and pointing with the metal screw driver.
@electronicsNmore
@electronicsNmore 3 жыл бұрын
LOL
@wendygerrish4964
@wendygerrish4964 2 жыл бұрын
Yep typical electrician.
@lesliefranklin1870
@lesliefranklin1870 2 жыл бұрын
I enjoyed watching him work on a live panel with a wristwatch with a metal band. So exciting!
@goldfishn3545
@goldfishn3545 Жыл бұрын
@@electronicsNmore you laugh at Clive and jumped into the throat of a guy you claimed was a brit. But as a former licensed journeyman electrician and OSHA 500 outreach trainer who teaches OSHA 10 and 30 hour classes, the safety things you laugh off now will kill you later. I’ve been to enough electrician’s funerals who were invincible like you.
@jameshuynh5436
@jameshuynh5436 2 жыл бұрын
Very clearly slowly safely demonstrated. 👍
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Thanks for watching James!
@mauricelee7299
@mauricelee7299 2 ай бұрын
Thanks so much for this video. It was very well presented and I learned a lot.
@electronicsNmore
@electronicsNmore 2 ай бұрын
Glad you found the video helpful! Be sure to check out my wide range of videos and share my channel with others. Thank you very much
@scotthucks7966
@scotthucks7966 2 жыл бұрын
Great video. Just what I was looking for!
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad you liked it!
@TheHansoost
@TheHansoost 6 ай бұрын
stellar explanation and demonstration. I finally get it.
@Mrdealornodeal618
@Mrdealornodeal618 2 жыл бұрын
Great and informative video. Thank you!
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad it was helpful! Be sure to rate thumbs up, consider subscribing if you like a wide range of helpful and informative videos, and look over my extensive video playlists below for many other videos of interest to you. Taking one minute to share a link to my channel with others on social networking sites would be greatly appreciated. Thanks kzbin.infoplaylists
@thomashill6347
@thomashill6347 Жыл бұрын
Thank you, informative and clear to the points WELL DONE
@electronicsNmore
@electronicsNmore Жыл бұрын
Glad you enjoyed it!
@amorales9613
@amorales9613 Жыл бұрын
Excellent, really excellent explanation.
@RichardKrumm
@RichardKrumm 2 жыл бұрын
WOW this is such a great and informative video. Thanks!!
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad you enjoyed it Richard! Be sure to check out my wide range of videos as well. Thanks kzbin.infoplaylists
@toddrandazzo5534
@toddrandazzo5534 Жыл бұрын
Really fantastic explanation. Wish I'd stumbled on this video much earlier in my electrical learning journey.
@louf7178
@louf7178 2 жыл бұрын
3:50 perfect ElectroBoom opportunity 😁 Good video!
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Thanks for watching! Be sure to check out my latest electrical video as well.
@aurvaroy6670
@aurvaroy6670 Жыл бұрын
15 A receptacles are allowed to be on 20 A circuits for two reasons: code and specs. Every good quality 15 A receptacle is specified to handle 20 A pass through on the terminals. Then again, it’s always better to pigtail instead of use both terminals to avoid dealing with pass through current in every receptacle.
@user-qn6yt3zx3w
@user-qn6yt3zx3w 2 жыл бұрын
Converted my kitchen 20A duplex’s to a single 220V and am running a 2.4kW toaster and a 3kW kettle - breakfast is ready much much faster now!
@user-qn6yt3zx3w
@user-qn6yt3zx3w 2 жыл бұрын
@LabRat Knatz brought them from the UK. Installed some Leviton BSRDP-W outlets - awesome setup.
@rsdaarud
@rsdaarud 2 жыл бұрын
Excellent step by step!
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad you think so! Be sure to look over my extensive video playlists below for many other videos of interest to you, and most importantly take one minute to share a link to my channel with others on social networking sites. Thanks kzbin.infoplaylists
@parkershaw8529
@parkershaw8529 2 жыл бұрын
Man, watching your screw driver tip hovering between the two bus bars were exciting!
@electronicsNmore
@electronicsNmore 2 жыл бұрын
LOL. It looked much closer than it was.
@junglehedz216
@junglehedz216 2 жыл бұрын
Also , touching a live bus is not a huge deal, as long as you don’t touch anything else, the other bus or the chassis of the box. I’ve made the mistake of moving to fast with my screwdriver in my hand and accidentally grazed both live bars, melted the tip off my screwdriver and I stunk like burnt electrical for the rest of the day. Ruined a nice Klein screwdriver
@bebyaguilar3226
@bebyaguilar3226 2 жыл бұрын
Gracias señor eléctrico 👍🏼
@Jewclaw
@Jewclaw Жыл бұрын
Best video thus far! Trust me I’ve watched several lol
@electronicsNmore
@electronicsNmore Жыл бұрын
Glad you enjoyed!
@ronymejia3339
@ronymejia3339 9 ай бұрын
Great video got my question solved
@mrkevyn002
@mrkevyn002 2 жыл бұрын
Excellent explanation, and thank you.
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad you enjoyed it!
@avih7311
@avih7311 Жыл бұрын
Great explanation. got confusing a bit when u switched in the middle of 120 to 240 explanation to the reverse.... but at least now it is clear what goes into a conversion.
@rayray9777
@rayray9777 2 жыл бұрын
I liked it when you said make sure only 1 device is connected to the circuit when converting. This is always missed! Great job Thumbs up and a like from me!
@dlloyd6300
@dlloyd6300 2 жыл бұрын
Why can only one device be connected to the circuit?
@orleydoss3171
@orleydoss3171 3 жыл бұрын
Excellent tutorial 👍
@electronicsNmore
@electronicsNmore 3 жыл бұрын
Glad you liked it Orley!
@captclyde7233
@captclyde7233 Жыл бұрын
Really great job sir
@candidoalcantara6718
@candidoalcantara6718 2 жыл бұрын
YOU EXPLANE CLEAR IT WAS GOOD
@Jimbo49o1
@Jimbo49o1 3 жыл бұрын
Best video I've found.
@electronicsNmore
@electronicsNmore 3 жыл бұрын
Thank you! Be sure to check out my other videos and share. I have many other videos explained like this one.
@jamalbenthall151
@jamalbenthall151 2 жыл бұрын
Dam that was a beautiful video. It was explained so well. Thank you 😊
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad you enjoyed it! Please share the link. Thank you
@earthenergyhex
@earthenergyhex 2 жыл бұрын
excellent video for people like me, very well explained.
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad you liked it!
@mihneaciupagea3362
@mihneaciupagea3362 2 жыл бұрын
Just a technical question. Do you happen to know where in the NEC it says you can mark neutral(white) wires as hot (or another color)? As far as i know NEC says you can only do this if the wire is 6AWG or bigger. So as far as I'm aware, this video is not code compliant
@lionheartchannel5842
@lionheartchannel5842 3 жыл бұрын
Thanks for sharing this video Sir, so nice tutorial.
@electronicsNmore
@electronicsNmore 3 жыл бұрын
You're welcome! Glad you enjoyed the video. Be sure to share the video link with others. Thank you
@axie2150
@axie2150 8 ай бұрын
Great video. Helped me win an argument 😂
@rasa5146
@rasa5146 2 ай бұрын
Thank you for this informative video. I am planning to do the same for a washing machine Shall we use earth leakage protection breaker. If yes, what are the recommended specs manuf./model.
@evildead1791
@evildead1791 3 жыл бұрын
Thank you so much for the video, my basement breaker keeps kicking when I use my welder and I'm trying to figure out how to remedy it, this video really helps.
@electronicsNmore
@electronicsNmore 3 жыл бұрын
Just make sure the line is a dedicated line. Thanks for watching!
@frankbiz
@frankbiz 3 жыл бұрын
👍🏻 Your videos and Project Farm are by far my favorite channels. Even though I have subscribed to both and have checked off the bell 🔔, they don't come up unless I search. I think You Tube is going down the tubes.
@electronicsNmore
@electronicsNmore 3 жыл бұрын
Great to hear! I'm not surprised by what you said about YT notifying you. I have close to 40K subs that have all notifications set to on, meanwhile I get only a few hundred watching, the rest are non-subs. YT is giving me the shaft really good, video after video. I should be getting at least 30-50K views per video. Thanks for watching Frank!
@frankbiz
@frankbiz 3 жыл бұрын
@@electronicsNmore What all social media is doing across the board is insane. They are so unfair to put mildly. I hope somehow you can get YT to fix the problem. You are amazing, keep up the great work. I have a lot of catching up to do back tracking watching your videos.
@electronicsNmore
@electronicsNmore 3 жыл бұрын
@@frankbiz i completely agree, unfortunately sharing is necessary.
@gyrgrls
@gyrgrls 2 жыл бұрын
@@electronicsNmore Sometimes web counter algorithms can be iffy. More than 20 years ago, I tried out different applets for this. Visit counts can be implemented exclusively, inclusively, and with a laundry list of options and or bugs. Back in the old days it was elementary for someone to pump his own counter with a bot externally, and the big boys like Google and Yahoo try to prevent this by implementing their own devices. But any thing can be circumvented, even with the shortage of available IPv6 addresses. There is a a lot of cheating on sites such as Flickr and Facebook... That said, the analytics don't always stack up on the view count, especially with so many public IP addresses being reissued by broadband providers who provide service for LANS, WANS, etc..
@Radvera
@Radvera Жыл бұрын
Well done! Thankyou!
@elijahwatson8119
@elijahwatson8119 3 жыл бұрын
Just an FYI: It's perfectly acceptable to have a 15 amp outlet on a 20 amp circuit so long as there are at least two outlets on the circuit. A single duplex receptacle qualifies as two outlets. The reason why it's safe and code compliant is that 15 amp receptacles are built to the same standards 20 amp receptacles are. They are perfectly capable of passing along 20 amps. If you take a 15 amp and 20 amp receptacle apart, you'll find they're almost entirely identical except for the extra sideways slot for 20 amp plugs. Tl;dr: so long as you don't need to use any devices with a 20 amp plug, 15 amp receptacles are just fine on a 20 amp circuit.
@emmettturner9452
@emmettturner9452 2 жыл бұрын
@@Billy.80 Whatever. OP’s statement was overly broad. I wouldn’t assume existing outlets in an older home are able to handle 20A. Heck, some aren’t even polarized or grounded. I certainly wouldn’t encourage people to put 20A through them and I’m sure our man making the video doesn’t want the legal liability either. Old outlets/wiring is exactly why our Chevy Volt defaults to 8A on 120v and requires you to override for 12A. It specifies a Level 2 charger (220-240v) and a 30A receptacle for a maximum of 16 amps.
@WoodgemanX
@WoodgemanX 2 жыл бұрын
Never seen any electrical device or appliance with a 120V 20A male plug, in any residential, commercial, or industrial setting.
@elijahwatson8119
@elijahwatson8119 2 жыл бұрын
@@WoodgemanX I've seen one old window AC that used a 20 amp plug. But that's incredibly rare, because usually anything too large for a 15 amp circuit switches to requiring 240 volts.
@elijahwatson8119
@elijahwatson8119 2 жыл бұрын
@@emmettturner9452 you may have a point that some old outlets really aren't capable of passing through 20 amps, I dunno. But anything not extremely old certainly can, and if you have outlets so old you're not comfortable that they can pass 20 amps, I'd probably consider replacing them.
@emmettturner9452
@emmettturner9452 2 жыл бұрын
@@elijahwatson8119 I just went back to the tornado-damaged home we used to live in and found that the landlord’s contractors did not repair the outlet my brother left hanging out of the garage wall to draw their attention to it. It was melted by that same Chevy Volt charger I mentioned before that draws a maximum of 12A. Many outlets cannot sustain the amperage they are rated for. That is the exact reason you have to override the default of 8A every time you want to charge at 12A. The home was about 15 years old. The place we are staying now is also tornado damaged. I believe it was built in the ‘50s and most of the outlets are like nothing I’ve ever seen. They almost look like those foreign outlets that can take blades or round prongs but they are actually two T-shaped contacts with no ground. The place has no heat so we have to run space heaters but there’s no way would I run 20A through these. I just had to install a 240v garage heater in my rented workshop so I could sleep there. 240v equipment is against the least but they already had a NEMA 5-20 connected to 240v. I didn’t find out until I plugged in my shop lights and it fried them. Now I play dumb just so I can get the car charged at Level 2 (no other place to charge it) and I get to run the heater. I still don’t trust the old outlet so I swapped it with a NEMA 6-20 and made a NEMA 14-30 pigtail for my heater.
@ecrusch
@ecrusch 2 жыл бұрын
This was super helpful. Thanks a bunch. (By the way, I subscribed.)
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Awesome, thank you! Be sure to share.
@amazingmax409
@amazingmax409 Ай бұрын
Thank you may I will change 240 voltage for electrical range like this . Do I need to change the wire also? Or more big wire? Thx
@DIYwithBatteries
@DIYwithBatteries 3 жыл бұрын
Cool tutorial :D
@electronicsNmore
@electronicsNmore 3 жыл бұрын
Glad you enjoyed the video! Thanks for watching
@curmudgeonextraordinaire1884
@curmudgeonextraordinaire1884 2 жыл бұрын
As per code you can use either a 15 or 20 amp outlet on a 20 amp circuit.
@KevinCoop1
@KevinCoop1 7 ай бұрын
Only if it’s duplex. If dedicated simplex, it must be 20 amp on 20 amp branch circuit.
@ivanrodriguez8988
@ivanrodriguez8988 2 жыл бұрын
Thank you, great information,
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad it was helpful Ivan! Be sure to check out my other videos and share. Thanks
@patrickgr1547
@patrickgr1547 4 ай бұрын
Excellent 👌
@DRILL-SGT.HARTMAN
@DRILL-SGT.HARTMAN 3 жыл бұрын
Good video, I've never watched you before. I was hoping you didn't add a jumper from the same phase in the outlet box. 🤣, I 've actually run across this before.
@electronicsNmore
@electronicsNmore 3 жыл бұрын
Glad you liked the video Mike! I'm sure plenty of YT videos show that mod. LOL. Be sure to share the video link with others. Thank you
@kathyparker8626
@kathyparker8626 Жыл бұрын
Great Great tutorial , not sure the average person could follow or understand, a lot if information. Hopefully this will send the average person to a license elect.
@gsftom
@gsftom 2 жыл бұрын
Excellent! And something I never knew or understood. Thank you!
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad it was helpful!
@paulineaessa6202
@paulineaessa6202 10 ай бұрын
Excellent!!!
@erwinross
@erwinross 2 жыл бұрын
one of the best explanation
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad you think so Erwin! Be sure to look over my video playlists below for many other videos of interest to you, and most importantly take one minute to share a link to my channel with others on social networking sites. Thanks kzbin.infoplaylists
@richardbedard1245
@richardbedard1245 Жыл бұрын
I don't know why but 240 volts has always been a mystery to me. It never occurred to me that you could do what you just did. Thank you for explaining it so clearly a five year old could wire it!
@jameswilliams9655
@jameswilliams9655 Жыл бұрын
I suspect not shutting the panel off and using a metal fish tape in a live panel are just a few bad examples that could eliminate a few of those five year olds pretty quickly. You should get a licensed electrician if you do not have the training before you make an ash of yourself or find yourself homeless.
@p.c.3479
@p.c.3479 Жыл бұрын
Not all of us are electricians; many just can’t afford to pay one!
@philewuppallthwagh226
@philewuppallthwagh226 10 ай бұрын
If you find yourself saying "There's a free spot for a new breaker! Hmmm, Hi Leg? High Leg? Wonder why someone wrote that on the free spot? " then you can't afford not to hire a licensed electrician!! Bye leg!! Lol. 🤯☠️. 120 Gets your attention. 240 gets you for keeps.
@KevinCoop1
@KevinCoop1 7 ай бұрын
Richard, Instead of listening to what most people say, think of it this way. Your panel is 240 volts hot to hot. A neutral is added half way through the transformer to get two 120 volt connections.
@Sparky-ww5re
@Sparky-ww5re 4 ай бұрын
​@@philewuppallthwagh226good observation. If you come across a panel where every third slot is unused or occupied by a two or three pole breaker, the panel is almost certainly going to be three phase, supplied by a high leg delta, at 120/240V, 208V - ground high leg (or very rarely, 240/480V, 415V - ground high leg) . An easy to make mistake with this system is connecting a single pole breaker to the high leg - required to be marked orange and land on phase B (or C, for installations prior to the 1975 NEC) and smoke up everything on that circuit, always verify with a meter, in case the prior electrician was drunk and forgot to use the correct colors. ;-) These services would only be found in commercial or industrial settings where most of the loads are 3 phase machinery, with limited 120V loads.
@bluudlung
@bluudlung 2 жыл бұрын
this was incredibly helpful, thank you so much!
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Great to hear! Be sure to check out my very wide range of videos and share. Thanks
@Buggy0106
@Buggy0106 7 ай бұрын
I watch your video to learn in which I have . Thanks , don’t watch video and critics.
@omkarsalunke8058
@omkarsalunke8058 2 жыл бұрын
This is amazing sir. Thank you very much for this video. My only question is what if we have a plastic outlet? Where does the ground wire go in that case as we don't have a small enclosure to connect to?
@electronicsNmore
@electronicsNmore 2 жыл бұрын
You mean plastic electrical box? If so, then you should have a bare copper wire or green colored wire that you connect to the receptacle's ground screw.
@joaquinsuarez6090
@joaquinsuarez6090 4 ай бұрын
Great video, thank you and question. I wanted to replace a double regular size 240v braker for a double slim size braker to make space for a new slim braker. I put the 2 slim brakers on the bottom of braker box but never got the 240v because they weren't touching the horizontal metal bar that connects both sides of power legs which was higher in braker box, so I had to put back the big regular size double braker which connects to the horizontal plate and gives me the 240v. Is there a way that I can use the double slim braker to ger the 240v and make space for another single slim braker? Please advise.
@gyrgrls
@gyrgrls 2 жыл бұрын
11:07 Ha! Neutral bus seldom has a dangerous potential on it, except in rare conditions where the triplex meets the tails, and the ground connection is faulty. Note that it is _never_ save to touch a neutral on the inside wiring, because the return path to the bus is unreliable. Many will be shocked to find this out the hard way.
@donphillips5957
@donphillips5957 2 жыл бұрын
Laughed when he did that. I'm inside a box like that, I'm wearing gloves and using insulated tools.
@muromets4929
@muromets4929 2 жыл бұрын
This is the best KZbin video on this topic!
@rolling_marbles
@rolling_marbles Жыл бұрын
The receptacle only has to match the circuit for amperage rating if it’s a single receptacles on the circuit. Code allows for multiple 15A receptacles on a 20A circuit.
@user-lf7en6rf8m
@user-lf7en6rf8m 2 жыл бұрын
Hi, new to the channel, thank you very much. Will check in often 👍 Phx az
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Thanks for watching!
@sklee1644
@sklee1644 2 жыл бұрын
Thanks for sharing.
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Thanks for watching Sam! Be sure to rate thumbs up, consider subscribing if you like a wide range of helpful and informative videos, and look over my extensive video playlists below for many other videos of interest to you. Taking one minute to share a link to my channel with others on social networking sites would be greatly appreciated. kzbin.infoplaylists
@jamesortolano3983
@jamesortolano3983 Жыл бұрын
Love this channel ,always learn something new. Thanks for content,editing nd clear concise instructions. Looking forward towards more content.
@gregshaw1008
@gregshaw1008 2 жыл бұрын
Exactly what I was looking for. Thank you.
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Great to hear Greg! Be sure to rate thumbs up, consider subscribing if you like a wide range of helpful and informative videos, and look over my extensive video playlists below for many other videos of interest to you. Taking one minute to share a link to my channel with others would be greatly appreciated. Thanks kzbin.infoplaylists
@V4suki
@V4suki Жыл бұрын
Why do you say thet phase carries power when both neutral and phase wires carry power since is alternateing current?
@MoneyShot702
@MoneyShot702 3 ай бұрын
Buying a hybrid heat pump dryer 14amp 240v. Right now I have 2 dedicated 120v branch outlets running on a 12/3 Romex w/ bare ground and converting to 6-20r. Would I use the neutral wire as ground and just tuck away the bare ground wire? If so should I also unhook the bare ground from the bar on the panel since it's not being used?
@BYENZER
@BYENZER 3 жыл бұрын
1. NEVER, EVER work on electrical, whilst wearing jewelry or watches. 2. NEVER, EVER use a metal object, (screwdriver), as a POINTER inside an electrical cabinet. 3. NEVER, EVER TOUCH a NEUTRAL BAR. A system fault, CAN be HIDDEN and the neutral CAN be carrying FULL PHASE VOLTAGE.
@electronicsNmore
@electronicsNmore 3 жыл бұрын
I knew it was just a matter of time before a Brit would come along and post a comment like yours. They've been problematic on a few of my electrical videos.
@BYENZER
@BYENZER 3 жыл бұрын
@@electronicsNmore Awe, don't take it personal. You do good vids! But a BRIT?? I'm no Brit. I am an U.S. Air Force Nuclear Weapons electronics technician, and an electrician whose wired many houses. So,, when it comes to EWEKTWISITY, I know a thing or two. BUT, if Brits have been posting on your vids, BE thankful. Them, BRITS, are FAR better educated than us YANKS. Best to heed their advice, warnings, etc. They know what they're talking about. Usually, you do too, but, you definitely weaved out of your lane, just a weeeee bit, on this one.
@electronicsNmore
@electronicsNmore 3 жыл бұрын
@@BYENZER You said, "whilst", a British word. The watch on my left wrist(I'm right handed), sure that can be an issue, but after decades, never a problem. As for the screwdriver, the handle was insulated, and the tip was 1 1/2" away, so not a problem. It may have looked closer on video. The neutral wire should never be live on a well functioning electrical system UNLESS the neutral wire has a very poor connection or if it's disconnected from the transformer. The panel is bonded to the neutral, that means I shouldn't touch the panel with my bare hands either? I said very clearly in the video, "I don't recommend you do it". In the future, I suggest you do not use caps. It's no different than yelling at me, and it pisses me off. I have no respect for viewers that yell at me, or demean me.
@BYENZER
@BYENZER 3 жыл бұрын
Here's how a BRIT would reply to your last reply: "My My! Me thinks, thou doth protesteth, quite much"!
@BYENZER
@BYENZER 3 жыл бұрын
Hang in there tiger! You're doin alright. Just plz show safer electrical practices when preaching to the masses. And, always remember this: "Never let, someone you dislike, take up residence in your head,,,, rent free"! Carry on sir. Carry on!
@Sparky-ww5re
@Sparky-ww5re Ай бұрын
Great video. Although in most cases a 240 volt receptacle will be on an individual branch circuit for one appliance such as a heavy duty air compressor in the garage, there are some situations where it is acceptable to convert a 120V circuit to 240V, with more than one receptacle, replacing all the receptacles with NEMA 6-15/6-20. You'll most often see this in grow houses where high powered grow lights are used, since this allows for twice the total wattage for a given amp draw, thereby resulting in significant savings in wiring costs. Most metal halide, high pressure sodium and LED luminaries have quad ballasts, where they can be wired for 120, 208, 240, or 277V, with some models having 5 taps, allowing for 480V as well. Many integrated LED luminaires, and commercial grade electronic fluorescent ballasts are 120 ~277V universal voltage as well.
@MarcoLiftz
@MarcoLiftz 2 жыл бұрын
Great video thanks bro
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Glad you enjoyed it Marco! Be sure to check out my other videos, and most importantly take one minute to share a link to my channel with others on social networking sites. Thanks kzbin.infoplaylists
@donphillips5957
@donphillips5957 2 жыл бұрын
My apartment they replaced my 240 AC with a 120, and plugged it into a nearby regular outlet. The 240 outlet was left unused. This overloaded the outlet circuit which was constantly tripping, I replaced the 240 with a single 20A 120v outlet, and corrected the connections in the box
@blackhorse2947
@blackhorse2947 Ай бұрын
I have a 220V receptacle for my wood lathe. I moved it about 5 ft for better access. Now the lathe power cord will not reach the 220 outlet. Can I daisy chain from that outlet to the new location or should I home run a new cable and add a 20 amp breaker. I never run two machines on 220V at the same time. I would appreciate your advice. Thank you
@beijing561
@beijing561 2 ай бұрын
Very detailed tutorial. Question, let's say a outlet has four sockets where you can plug different appliances to them, it is 15amp sockets and circuit, will increasing the circuit say to 30 amp, increases the load this outlet can handle? And therefore more load for the four sockets? But they are still the 15amp sockets. Normally the overall load the sockets can take 15amp in total and that is almost 4amp each if all sockets are plugged. Maybe a better question is , how do you , if there's a way, make all four sockets capable of handling 15amp individually even when they are all plugged in the same time, under one single circuit ? I know if you use four different circuits you can do that, my question is under one single circuit. Thanks in advance
@slappymcfatface8056
@slappymcfatface8056 2 жыл бұрын
You wouldn’t have to make a neutral wire a hot wire if you already have 2 black(hot) wires would you? I’m converting a regular 120 double outlet to a single 240 volt 15 amp and was confused that no neutral was needed.
@cw5865
@cw5865 Жыл бұрын
I have been baffled as I think in DC and although never had an issue with 115 with the neutral, the 230 concept escapes me. AC being a different beast the box was also a place on confusion. Never thought about I guess what they call phases, and even after over decades on the planet I have wired houses and changed out breakers, switches etc I still always thought a neutral (which i equated to negative) was needed. Your video helps alot as i was just wanting to convert some water pumps to 230 and never even knew the wire colors. Will have to rewatch in order to rewire my thinking from years of working on cars, bikes and some planes.
@jackreacher4100
@jackreacher4100 Жыл бұрын
Dude, just remember 110 plus 110 equals 220. All the second one is, is two hots instead of one. super simple. Same concept with two hots.
@cw5865
@cw5865 Жыл бұрын
@@jackreacher4100 Yeah I just had to accept the fact that it just the way it is and a different animal from DC
@Ottero87
@Ottero87 11 ай бұрын
I was thinking the same thing... wondering "sooo, how do you get the neutral?" I guess since the neutral and grounding bar are the same thing, he's using the ground wire as the path back to the panel to complete the circuit.
@cw5865
@cw5865 11 ай бұрын
@@Ottero87 I don’t think the 230 needs it being alternating phase, but don’t quote me as Tesla was a genius…
@antilogism
@antilogism 2 жыл бұрын
I don't keep up with changes but the last time I looked NFPA 70 it didn't allow changing a small neutral wire to a line by coloring just the ends. That was only allowed for 4 AWG and up.
@KevinCoop1
@KevinCoop1 2 жыл бұрын
NEC 2017 and 2020 started moving into identification of conductors. They avoided it for decades.
@louayhom
@louayhom 2 жыл бұрын
i have a question for you after i liked your video.. if i do what you said in the video and i have more receptacles have 120V. and i need to keep them at 120v. what i should do?
@rouvingbird7986
@rouvingbird7986 Жыл бұрын
How would you go from the 120/240v panel shown in this video to a 240v single pull device? Do you need a transformer and disconnect at that point?
@MrJames-nx3un
@MrJames-nx3un 2 жыл бұрын
thank you, sir
@electronicsNmore
@electronicsNmore 2 жыл бұрын
You're welcome!
@edgars4532
@edgars4532 2 жыл бұрын
This is only if you use 20 amps no more? the wire can get hot.
@electronicsNmore
@electronicsNmore 2 жыл бұрын
Thanks for watching!
120V 240V Electricity explained - Split phase 3 wire electrician
12:24
The Engineering Mindset
Рет қаралды 5 МЛН
1🥺🎉 #thankyou
00:29
はじめしゃちょー(hajime)
Рет қаралды 80 МЛН
DELETE TOXICITY = 5 LEGENDARY STARR DROPS!
02:20
Brawl Stars
Рет қаралды 10 МЛН
Increíble final 😱
00:37
Juan De Dios Pantoja 2
Рет қаралды 16 МЛН
How to replace a 120 volt receptacle with a 240 volt receptacle?
5:30
Won't These Melt?!? 15amp Receptacles on 20 amp Circuits!!!
11:47
Electrician U
Рет қаралды 1,2 МЛН
How to Get 220v From 110v
14:48
DIY Homestead Projects
Рет қаралды 3,2 МЛН
How NOT to Wire Light Switches in 2024 (New Rules)
15:21
Backyard Maine
Рет қаралды 807 М.
How To Add An Outlet To A Finished Wall
10:51
Everyday Home Repairs
Рет қаралды 10 МЛН
Sub Panels Explained - Why are neutral and ground separated?
16:22
The Engineering Mindset
Рет қаралды 1,1 МЛН
How To Install a 220 Volt Outlet
15:20
askmediy
Рет қаралды 193 М.
How to change a 120v to 240v outlet | Handyman
8:29
Ron Comes In Handy
Рет қаралды 45 М.
#rockpaperscissors Fun! #kidsfun
0:11
J House jr.
Рет қаралды 21 МЛН
best soccer saving money bank 💰
0:10
AU
Рет қаралды 18 МЛН
СДЕЛАЛА рандомную ТАТУ
0:17
Виктор Лодин
Рет қаралды 4,9 МЛН
When cats see food 😱🤣🥰
0:29
Ben Meryem
Рет қаралды 16 МЛН