Trane chiller sensor issues. how to bind a trane sensor. Diagnosis and repair. it's hard to stop a trane? Replacing trane sensor tutorial. it's hard to stop a trane.
Пікірлер: 69
@HughesManHVAC3 жыл бұрын
Nice video 👍
@EverythingHVACR3 жыл бұрын
Thanks for watching!
@MegaDee9112 жыл бұрын
I'm glad that worked out for you. I have these sensors dropping left and right here in Florida.
@EverythingHVACR2 жыл бұрын
Thanks MegaDee911! Always verify my sensors on P.M.s they do have a high failure rate, even though Trane told me they have improved
@Ratman_Bejo3 жыл бұрын
thank you for sharing your knowledge of service chiller
@EverythingHVACR3 жыл бұрын
You are welcome, thank you for the support!
@princesswalt40103 жыл бұрын
I adore the sound of the VFD drives spinning on up
@EverythingHVACR3 жыл бұрын
It is a nice sound! Thanks for watching!
@danydjdberonbentzron82743 жыл бұрын
Saludos desde Reynosa Tamaulipas México animo
@EverythingHVACR3 жыл бұрын
gracias señor por mirar, agradezco el apoyo!
@MrBerniebling3 жыл бұрын
The Hateful paste get everywhere no matter how hard I try to be neat! Nice vid
@EverythingHVACR3 жыл бұрын
🤣, you know that's right! Thanks for watching!
@anthonywoolf90873 жыл бұрын
Exactly what my hand said 🤣🤣 nice I like it
@EverythingHVACR3 жыл бұрын
Thanks man! I appreciate you watching.
@hirafatima45683 жыл бұрын
Nice video....thanks for sharing
@EverythingHVACR3 жыл бұрын
Thanks for watching!
@urielhernandez98483 жыл бұрын
Excelllent information
@EverythingHVACR3 жыл бұрын
Thanks man!
@Clifford032 жыл бұрын
The CHL I service is barely 2yrs old and I already have a bad sensor … Thanks for the heads up
@EverythingHVACR2 жыл бұрын
They are a consistent problem with the sensors not reading correctly. Trane says they have improved the sensor design though they look the same to me. Just be sure to use the paste on them and verify your temperatures periodically. Thanks for watching Clifford!
@Clifford0310 ай бұрын
@@EverythingHVACRI gotta agree with you … Found my 3rd faulty suction line temp sensor on Friday … Do I have to pay for the Trane software to bind the new sensor .?
@EverythingHVACR10 ай бұрын
I believe tech view software is free. I think I saw a link posted by subcool hvac on one of his videos recently, but It shouldn't be too hard to find.
@youssef1bentaleb1682 жыл бұрын
nice video bro a need your help
@Max-Svift2 жыл бұрын
There is no temperature sensor reading on the CH530 display. We connect through the TechView interface. Visible connections 16pcs. Through TechView it shows: active - 0 / inactive 16 pcs. Why so? Is there a step-by-step instruction on how to bind a sensor?
@EverythingHVACR2 жыл бұрын
You may have a failed sensor, go to binding view and see if it's there then unbind old sensor that's not reading and bind new sensor. If sensor is there you'll see it in the binding view, it may show up as "Red" because it's not reading all other operating sensors will show "green" always verify sensor temperature readings with a K type probe. -0 is an unusual reading
@Max-Svift2 жыл бұрын
@@EverythingHVACR How do I switch to snap mode? When I select the types of connections, all 16 sensors light up "red". A must burn only one, since only one faulty sensor.
@EverythingHVACR2 жыл бұрын
Not sure what snap mode is but if all sensors show red you may have another issue, I have never seen one do that. That would make me think none are communicating, you could try a re boot of system. You may have to get ahold of Trane tech support.
@jayronesantos45673 жыл бұрын
What is the name brand of thermal paste you used?
@EverythingHVACR3 жыл бұрын
Honeywell tradeline 107408
@Rudy_Suseno19802 жыл бұрын
Is the trane Type R, has a drain valve
@EverythingHVACR2 жыл бұрын
I don't think there is a drain valve but could be wrong, been a long time since this video
@joshstevens98262 жыл бұрын
First hit bind, and don't hit yes yet. After u have hit bind, then put ur magnet on, then hit yes. I've been thru that frustrating situation before.
@EverythingHVACR2 жыл бұрын
Correct, it's much easier on the new chillers, all can be done from the control panel without using tech view. Thanks for watching!
@jasonjohnsonHVAC3 ай бұрын
Good ole CGAM
@EverythingHVACR3 ай бұрын
Yessir, all good except the sensors 😆
@jasonpham0223 Жыл бұрын
hello sir my chiller ch530 circuit 1 stopped after running for 20 mins. and show on the screen External circuit lockout. how do i solve this. please help
@EverythingHVACR Жыл бұрын
External lock out sounds like it's going to be External to the chiller, could be many things but you need to check all pumps, flow switches and anything that may be controlling this chiller.
@kundanchavan24822 жыл бұрын
Train rtac3504 chiller why going low evaporated temperature
@EverythingHVACR2 жыл бұрын
Could be a lot of things, start with the basics Water flow, water flow, water flow. It's like air flow gotta have it, or you got another failing trane sensor.
@Noypihvac3 жыл бұрын
That the most problem with trane cgam suction temp sensor out of range temp reading
@EverythingHVACR3 жыл бұрын
Yeah, all the sensors really, I've replaced a water temp sensor, it gets out of whack and locks out on low water flow. Thanks for watching!
@1MaximusDecimusMeridius13 жыл бұрын
Mine is showing 226 deg suction temp 😂😂
@rakeshbishnoi3639 Жыл бұрын
Hello sir ..my system show "chiller excessive loss of communication" alarm ...so what can i do ... Please provide solutions
@EverythingHVACR Жыл бұрын
I have never seen excessive loss of communication but sounds like you need to start with basic checks, Verify all voltage and that all components operate and no fuses blown. Communication loss is just something not communicating. After voltages and all other things are verified make sure all sensors are reading... correctly... a power reset may be necessary especially if there were any power issues that may have caused a board or control problem.
@robhorner-starlakeny74263 жыл бұрын
What do you mean when you say "bind" and/or "rebind" the sensor?
@EverythingHVACR3 жыл бұрын
The sensors communicate information back to the control. You must remove the old sensor and un bind so the control does not see that sensor anymore. The you have to pull the new sensor in to the control and re bind. Basically setting the control to see that specific sensor. There are many videos on binding trane sensors. Thanks for watching!
@robhorner-starlakeny74263 жыл бұрын
@@EverythingHVACR Thank you!
@_Padma_TausikHasan3 жыл бұрын
Why is the magnetic LED to be caught while binding, and how does the LED light up when the magnet is caught?
@EverythingHVACR3 жыл бұрын
Good question and maybe one for trane, I would guess for one thing it keeps you from buying just any sensor and installing it this way you must go back to trane for parts.
@jonnymac313 жыл бұрын
CGAM best practices, step 1: update software lol. The easy rider is a necessary evil. Get a drop on you and 10 min later your the tin man.
@aircooledchilleralltypes49383 жыл бұрын
Can you please send me the software
@EverythingHVACR3 жыл бұрын
That software is free, you should be able to download it, no licensing needed. Its called tech view.
@lawrencebauzon44293 жыл бұрын
Can be download free?
@EverythingHVACR3 жыл бұрын
Honestly I'm not sure if it's free, it is not used as much anymore and usually the license that cost so it may be.
@lawrencebauzon44293 жыл бұрын
@@EverythingHVACR Thanks bro.
@EverythingHVACR3 жыл бұрын
👍🙏💯
@bernieclement33732 жыл бұрын
How to bind a EEV theres no led!
@EverythingHVACR2 жыл бұрын
Thanks Bernie! Is that a question? Not sure if the EEV binds it might be wired directly to the board. If it does bind you have to swipe a magnet just like the temp sensors then LED should light up.
@bernieclement33732 жыл бұрын
@@EverythingHVACR That circuit will not run. the program shows 22 things its looking at, but the EEV circuit 2 needs to be binded it had some com problem i had to rebind 3 other things.
@bernieclement33732 жыл бұрын
Anyways a Trane tec coming to help in maybe a week or so, oh well.
@EverythingHVACR2 жыл бұрын
If it won't bind you may need a new Valve, otherwise should bind the same way as the sensors I would think but I've never had a problem with the EEVs before
@bernieclement33732 жыл бұрын
@@EverythingHVACR Hello! Update on the chiller, the module harness that plugs into the eev is bad and they dont make them anymore. It sucks that chiller is only 10 years old so need to upgrade to new version of eev, short module harness and board up front that it plugs into. Confirmed by the trane tech to troubleshoot problem.