Hvac no cooling service call, Trane chiller locked out with sensor issues

  Рет қаралды 15,130

Everything HVACR

Everything HVACR

3 жыл бұрын

Trane chiller sensor issues. how to bind a trane sensor. Diagnosis and repair. it's hard to stop a trane? Replacing trane sensor tutorial. it's hard to stop a trane.

Пікірлер: 69
@HughesManHVAC
@HughesManHVAC 3 жыл бұрын
Nice video 👍
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
Thanks for watching!
@MegaDee911
@MegaDee911 2 жыл бұрын
I'm glad that worked out for you. I have these sensors dropping left and right here in Florida.
@EverythingHVACR
@EverythingHVACR 2 жыл бұрын
Thanks MegaDee911! Always verify my sensors on P.M.s they do have a high failure rate, even though Trane told me they have improved
@Ratman_Bejo
@Ratman_Bejo 3 жыл бұрын
thank you for sharing your knowledge of service chiller
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
You are welcome, thank you for the support!
@princesswalt4010
@princesswalt4010 3 жыл бұрын
I adore the sound of the VFD drives spinning on up
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
It is a nice sound! Thanks for watching!
@danydjdberonbentzron8274
@danydjdberonbentzron8274 3 жыл бұрын
Saludos desde Reynosa Tamaulipas México animo
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
gracias señor por mirar, agradezco el apoyo!
@MrBerniebling
@MrBerniebling 3 жыл бұрын
The Hateful paste get everywhere no matter how hard I try to be neat! Nice vid
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
🤣, you know that's right! Thanks for watching!
@anthonywoolf9087
@anthonywoolf9087 3 жыл бұрын
Exactly what my hand said 🤣🤣 nice I like it
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
Thanks man! I appreciate you watching.
@hirafatima4568
@hirafatima4568 3 жыл бұрын
Nice video....thanks for sharing
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
Thanks for watching!
@urielhernandez9848
@urielhernandez9848 3 жыл бұрын
Excelllent information
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
Thanks man!
@Clifford03
@Clifford03 2 жыл бұрын
The CHL I service is barely 2yrs old and I already have a bad sensor … Thanks for the heads up
@EverythingHVACR
@EverythingHVACR 2 жыл бұрын
They are a consistent problem with the sensors not reading correctly. Trane says they have improved the sensor design though they look the same to me. Just be sure to use the paste on them and verify your temperatures periodically. Thanks for watching Clifford!
@Clifford03
@Clifford03 10 ай бұрын
@@EverythingHVACRI gotta agree with you … Found my 3rd faulty suction line temp sensor on Friday … Do I have to pay for the Trane software to bind the new sensor .?
@EverythingHVACR
@EverythingHVACR 10 ай бұрын
I believe tech view software is free. I think I saw a link posted by subcool hvac on one of his videos recently, but It shouldn't be too hard to find.
@youssef1bentaleb168
@youssef1bentaleb168 2 жыл бұрын
nice video bro a need your help
@Max-Svift
@Max-Svift 2 жыл бұрын
There is no temperature sensor reading on the CH530 display. We connect through the TechView interface. Visible connections 16pcs. Through TechView it shows: active - 0 / inactive 16 pcs. Why so? Is there a step-by-step instruction on how to bind a sensor?
@EverythingHVACR
@EverythingHVACR 2 жыл бұрын
You may have a failed sensor, go to binding view and see if it's there then unbind old sensor that's not reading and bind new sensor. If sensor is there you'll see it in the binding view, it may show up as "Red" because it's not reading all other operating sensors will show "green" always verify sensor temperature readings with a K type probe. -0 is an unusual reading
@Max-Svift
@Max-Svift 2 жыл бұрын
@@EverythingHVACR How do I switch to snap mode? When I select the types of connections, all 16 sensors light up "red". A must burn only one, since only one faulty sensor.
@EverythingHVACR
@EverythingHVACR 2 жыл бұрын
Not sure what snap mode is but if all sensors show red you may have another issue, I have never seen one do that. That would make me think none are communicating, you could try a re boot of system. You may have to get ahold of Trane tech support.
@jayronesantos4567
@jayronesantos4567 3 жыл бұрын
What is the name brand of thermal paste you used?
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
Honeywell tradeline 107408
@Rudy_Suseno1980
@Rudy_Suseno1980 2 жыл бұрын
Is the trane Type R, has a drain valve
@EverythingHVACR
@EverythingHVACR 2 жыл бұрын
I don't think there is a drain valve but could be wrong, been a long time since this video
@joshstevens9826
@joshstevens9826 2 жыл бұрын
First hit bind, and don't hit yes yet. After u have hit bind, then put ur magnet on, then hit yes. I've been thru that frustrating situation before.
@EverythingHVACR
@EverythingHVACR 2 жыл бұрын
Correct, it's much easier on the new chillers, all can be done from the control panel without using tech view. Thanks for watching!
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
Good ole CGAM
@EverythingHVACR
@EverythingHVACR 3 ай бұрын
Yessir, all good except the sensors 😆
@jasonpham0223
@jasonpham0223 Жыл бұрын
hello sir my chiller ch530 circuit 1 stopped after running for 20 mins. and show on the screen External circuit lockout. how do i solve this. please help
@EverythingHVACR
@EverythingHVACR Жыл бұрын
External lock out sounds like it's going to be External to the chiller, could be many things but you need to check all pumps, flow switches and anything that may be controlling this chiller.
@kundanchavan2482
@kundanchavan2482 2 жыл бұрын
Train rtac3504 chiller why going low evaporated temperature
@EverythingHVACR
@EverythingHVACR 2 жыл бұрын
Could be a lot of things, start with the basics Water flow, water flow, water flow. It's like air flow gotta have it, or you got another failing trane sensor.
@Noypihvac
@Noypihvac 3 жыл бұрын
That the most problem with trane cgam suction temp sensor out of range temp reading
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
Yeah, all the sensors really, I've replaced a water temp sensor, it gets out of whack and locks out on low water flow. Thanks for watching!
@1MaximusDecimusMeridius1
@1MaximusDecimusMeridius1 3 жыл бұрын
Mine is showing 226 deg suction temp 😂😂
@rakeshbishnoi3639
@rakeshbishnoi3639 Жыл бұрын
Hello sir ..my system show "chiller excessive loss of communication" alarm ...so what can i do ... Please provide solutions
@EverythingHVACR
@EverythingHVACR Жыл бұрын
I have never seen excessive loss of communication but sounds like you need to start with basic checks, Verify all voltage and that all components operate and no fuses blown. Communication loss is just something not communicating. After voltages and all other things are verified make sure all sensors are reading... correctly... a power reset may be necessary especially if there were any power issues that may have caused a board or control problem.
@robhorner-starlakeny7426
@robhorner-starlakeny7426 3 жыл бұрын
What do you mean when you say "bind" and/or "rebind" the sensor?
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
The sensors communicate information back to the control. You must remove the old sensor and un bind so the control does not see that sensor anymore. The you have to pull the new sensor in to the control and re bind. Basically setting the control to see that specific sensor. There are many videos on binding trane sensors. Thanks for watching!
@robhorner-starlakeny7426
@robhorner-starlakeny7426 3 жыл бұрын
@@EverythingHVACR Thank you!
@_Padma_TausikHasan
@_Padma_TausikHasan 3 жыл бұрын
Why is the magnetic LED to be caught while binding, and how does the LED light up when the magnet is caught?
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
Good question and maybe one for trane, I would guess for one thing it keeps you from buying just any sensor and installing it this way you must go back to trane for parts.
@jonnymac31
@jonnymac31 3 жыл бұрын
CGAM best practices, step 1: update software lol. The easy rider is a necessary evil. Get a drop on you and 10 min later your the tin man.
@aircooledchilleralltypes4938
@aircooledchilleralltypes4938 3 жыл бұрын
Can you please send me the software
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
That software is free, you should be able to download it, no licensing needed. Its called tech view.
@lawrencebauzon4429
@lawrencebauzon4429 3 жыл бұрын
Can be download free?
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
Honestly I'm not sure if it's free, it is not used as much anymore and usually the license that cost so it may be.
@lawrencebauzon4429
@lawrencebauzon4429 3 жыл бұрын
@@EverythingHVACR Thanks bro.
@EverythingHVACR
@EverythingHVACR 3 жыл бұрын
👍🙏💯
@bernieclement3373
@bernieclement3373 2 жыл бұрын
How to bind a EEV theres no led!
@EverythingHVACR
@EverythingHVACR 2 жыл бұрын
Thanks Bernie! Is that a question? Not sure if the EEV binds it might be wired directly to the board. If it does bind you have to swipe a magnet just like the temp sensors then LED should light up.
@bernieclement3373
@bernieclement3373 2 жыл бұрын
@@EverythingHVACR That circuit will not run. the program shows 22 things its looking at, but the EEV circuit 2 needs to be binded it had some com problem i had to rebind 3 other things.
@bernieclement3373
@bernieclement3373 2 жыл бұрын
Anyways a Trane tec coming to help in maybe a week or so, oh well.
@EverythingHVACR
@EverythingHVACR 2 жыл бұрын
If it won't bind you may need a new Valve, otherwise should bind the same way as the sensors I would think but I've never had a problem with the EEVs before
@bernieclement3373
@bernieclement3373 2 жыл бұрын
@@EverythingHVACR Hello! Update on the chiller, the module harness that plugs into the eev is bad and they dont make them anymore. It sucks that chiller is only 10 years old so need to upgrade to new version of eev, short module harness and board up front that it plugs into. Confirmed by the trane tech to troubleshoot problem.
No Cooling Service Call, York package unit
13:34
Everything HVACR
Рет қаралды 968
Nutella bro sis family Challenge 😋
00:31
Mr. Clabik
Рет қаралды 14 МЛН
Slow motion boy #shorts by Tsuriki Show
00:14
Tsuriki Show
Рет қаралды 4,7 МЛН
How to Unbind and Bind Trane Sensors
3:29
Mark Stevenson
Рет қаралды 132
Trane Chiller Rtac 300 Ton Complete review! Air cooled chiller! Hvac System hindi/urdu
9:39
HVAC INFORMATION & KNOWLEDGE SHARING
Рет қаралды 17 М.
Unit is not Cooling, No AC Service Call
12:37
HughesMan HVAC
Рет қаралды 8 М.
TXV TROUBLE, ICE ON EVAPORATOR, HOW TO ADJUST THE TXV?
10:29
leckyjake
Рет қаралды 179 М.
HVAC cooling season, rooftop unit p.m tips, tricks and what to look for
19:12
Trane sensor bind in step by step TechView
6:57
Robles
Рет қаралды 13 М.
Installing RunTru By TRANE Split System | Would I RECOMMEND Them??
16:51
How Trane Screw Chillers Loaders Work
6:04
HVACTIME
Рет қаралды 14 М.
Nutella bro sis family Challenge 😋
00:31
Mr. Clabik
Рет қаралды 14 МЛН