How Trane Screw Chillers Loaders Work

  Рет қаралды 16,177

HVACTIME

HVACTIME

Күн бұрын

Walking through the sequence for Trane screw compressors CHH loading and unloading function.
Houston Hermetics
jake@houstonhermetics.com
Get 8% off at TruTech Tools with promo HVACTIME
www.trutechtoo...
Get tech support, training, and the Tech Blog at hvactimetx.com
You can contact me at Hvactimetx@gmail.com
Support my COFFEE problem through,
venmo.com/code...

Пікірлер: 42
@dfwhvac
@dfwhvac Жыл бұрын
Great Video and explanation. You’re my KZbin chiller icon lol😂
@tommycollett9584
@tommycollett9584 Жыл бұрын
Great video your a legend learning more and more every time you post thank you 🙌🏻
@SoutheastHVAC
@SoutheastHVAC Жыл бұрын
So many words in 6 minutes
@josebetancourt6866
@josebetancourt6866 9 күн бұрын
Yea only 6 min. I repeat the video 1 H.
@kehindefatai3830
@kehindefatai3830 6 ай бұрын
Trane chiller showing no data communication after resetting the system come up but only one compressor runs while the second refuse to run and keep showing high pressure cut out and the system goes down after 10min showing no data communication what can be the problem
@greglawson740
@greglawson740 3 ай бұрын
I know this is an older video but i need help. You have the most comprehensive videos on the Trane Chillers. Could you please put out a video or even a "short" on how to switch between pumps for like doing PM's
@HVACTIME
@HVACTIME 3 ай бұрын
You can get direct support in the chiller community when enrolled at chilleracademy.com.
@Covercash1982
@Covercash1982 9 ай бұрын
So i have a bad compressor on one of these chillers. I have no room for a fork lift and have no clue how to get the old one out and new one in.You got any ideas?
@HVACTIME
@HVACTIME 9 ай бұрын
I've always used skid plates and rigging equipment with a gantry
@edwardcrane7520
@edwardcrane7520 14 күн бұрын
Excellent job 👍👍👍
@hvacguy11
@hvacguy11 Жыл бұрын
You’re an Hvac legend
@JUANM896
@JUANM896 Жыл бұрын
Thanks bro Really thank you for sharing your knowledge.
@calex9398
@calex9398 Жыл бұрын
🤯lol 👍😅
@AhmedAli-po5xi
@AhmedAli-po5xi Жыл бұрын
In my job location i have facing on problem with chiller of yciv 2 system model.chiller was in normal operations but now a day's chiller going low suction trip same time both system going low suction trip.i changed stepper controller and motherboard also with new one but same issue.after start both systems of chiller goes low suction trip.need help to rectify
@Md.TausikHasan
@Md.TausikHasan Жыл бұрын
Please need your all video with English subtitles.
@zekenzy6486
@zekenzy6486 Жыл бұрын
Great Video. Thank you for sharing
@Patrick-hq7sq
@Patrick-hq7sq Жыл бұрын
I like to use my amp clamp on solenoids to check .
@HVACRTECH-83
@HVACRTECH-83 Жыл бұрын
We are getting 2 new trane chillers with screws next summer, long waiting list, going to be a hot summer at this school this year. But my question is, is there any classes you know of I can attend to learn up on these screw compressors? I've never worked on one and would really love to become more familiar. I doubt trane offers anything, they don't want us to learn their equipment, main reason why I hate trane, there's other reasons though of course
@rileyerickson8478
@rileyerickson8478 Жыл бұрын
Trane offers classes through Trane University.
@ulisessalas4731
@ulisessalas4731 11 ай бұрын
Excelente.... saludos desde Venezuela
@robertrichardson5026
@robertrichardson5026 Жыл бұрын
Learned something new, great video.
@fkdeazevedo
@fkdeazevedo Жыл бұрын
During unloading or on startup what should the oil pressure be on a rtaa and rtud? And during normal operation while it's maintaining what should the oil pressures be.
@MelonBopper
@MelonBopper 2 ай бұрын
Most R series chillers run at 35psid on the oil system for proper oil flow. Trip point at 50psid
@sh6323
@sh6323 7 ай бұрын
awesome video brother
@DerbyDogz
@DerbyDogz Жыл бұрын
We deal with American Hermetics pretty often out of Tennessee. Agreed they are awesome to deal with.
@HVACTIME
@HVACTIME Жыл бұрын
Good people
@AhmedAli-po5xi
@AhmedAli-po5xi Жыл бұрын
@@HVACTIME Dear hvac expert from long time i am watching your following to you.I am from pakistan.i am facing one problem in my yciv chiller.this chiller have to to systems.chiller was running normal but i recive complaints chiller trip both system same time trip due to low suction alarms.We changes steppers controller and new mother board.water flow also also ok in cooler suction tranduser also replaced.Share your advice.thanks for repling.
@REFEREEMOUSE
@REFEREEMOUSE Жыл бұрын
Love the explanation!
@mikelazzari503
@mikelazzari503 11 ай бұрын
Do you work for Trane? Just wondering how you would plug into there newer chillers without the proprietary software?
@HVACTIME
@HVACTIME 11 ай бұрын
I have the software license. I don't work for Trane though.
@Eighty8Fitter
@Eighty8Fitter 5 ай бұрын
You don’t need proprietary software for Trane nor a license
@MelonBopper
@MelonBopper 2 ай бұрын
You cannot plug into a trane system without the software. Tech View for any Dynaview systems and Tracer TU for any UC or Symbio systems. But the licenses need to be purchased for the software.
@Cloudstrafie
@Cloudstrafie Жыл бұрын
Tried the app says it's for older android :/
@HVACTIME
@HVACTIME Жыл бұрын
Thats weird, there should be a current version
@vickygalanis4965
@vickygalanis4965 Жыл бұрын
THANK YOU🎉
@jonnymac31
@jonnymac31 Жыл бұрын
Sweet, man.
@thesilentonevictor
@thesilentonevictor Жыл бұрын
Great video
@Practicing_HVACR
@Practicing_HVACR Жыл бұрын
At 3:20 you said that during shut down the female unloader is deenergized. Is that correct? Or is the female unloader energized?
@Practicing_HVACR
@Practicing_HVACR Жыл бұрын
Noticed that you repeated it at 3:42 and 3:51 but at the start you said the unloader was energized. Seems like you mixed up the words?
@Practicing_HVACR
@Practicing_HVACR Жыл бұрын
Was reading through the RTAA IOM to study this further and noticed it says. “The female unloader valve is the first stage of loading after the compressor starts and the last stage of unloading before the compressor shuts down.” Appreciate your videos, I don’t know about any other channels that make quality large tonnage HVAC videos like yours. I mostly work on under 100 tons so I’ll dabble with this equipment occasionally. It’s good to be able to see the equipment to supplement the studying I’m doing in manuals and other resources.
@Practicing_HVACR
@Practicing_HVACR Жыл бұрын
Looks like I found the other answer in the manual. Kind of odd that energizing the unloader valves loads the compressor and vice versa. You would think it should be called a female loader valve. “The female unloader valve solenoid receives a constant signal from the UCM, based on system cooling requirements. To load the compressor, the female unloader valve solenoid is energized and discharge pressure is passed through the normally-closed port and into the cylinder. This pushes the female unloader valve closed. To unload the compressor, the female unloader valve solenoid is de-energized and the discharge pressure is relieved to the suction of the compressor. The female unloader valve retracts into the cylinder and the compressor is unloaded.”
@HVACTIME
@HVACTIME Жыл бұрын
Yes the female unloader gets denergize as a final step before shutdown. So when loading starts it gets energized and stays energized until shutdown.
Chiller tripping LOW SUCTION Trane RTAA
8:07
HVACTIME
Рет қаралды 10 М.
RTAA 400 ton chiller Piston Replacement
13:12
John Hoyer
Рет қаралды 60 М.
Minecraft Creeper Family is back! #minecraft #funny #memes
00:26
An Unknown Ending💪
00:49
ISSEI / いっせい
Рет қаралды 57 МЛН
Help Me Celebrate! 😍🙏
00:35
Alan Chikin Chow
Рет қаралды 56 МЛН
How Screw Chillers control Load
5:44
HVACTIME
Рет қаралды 3,7 М.
Trane Chiller Compressor Unloader Stuck - HVAC Technician
9:28
Trane Chiller open and cleaning
25:20
Tech 360 Dallas
Рет қаралды 3,6 М.
Trane screw compressor abnormal noise problem solved | Trane screw chiller
8:19
HVAC Tech Guide by sreejith
Рет қаралды 17 М.
Minecraft Creeper Family is back! #minecraft #funny #memes
00:26