Can you please make a video on head pressure control valve please.
@drew22763 жыл бұрын
i get my gf to run flat after I raise her temp by backing out the screw through an open device, I screw in and out to back tension off, I have some superheat added into that, it gets warmer less chance that will cycle off, and back to normal conditions naturally on its own. I back off again and discharge my load in the theater. the load drops off because the body heat is gone. but I set for that. so that in a nutshell is how I adjust her full capacity attitude and generally a good example of an application of that. happy HVAC guys!
@phrodendekia10 күн бұрын
👏🏻👏🏻👏🏻
@robertmalone96993 жыл бұрын
Your explanation was thorough yet simple and to the point. You didn't try to crowd too much information into video.
@HVACKnowItAll3 жыл бұрын
Thank you sir
@renecuevas4128 Жыл бұрын
I see and read most of the comments Most guys understand quick. Others have No clu n got it confused w Txv. U explain it clear. I m not American n clearly understand ....fl weather around 60 s Good time for LAT and Low Load u put an easy Movie Theater example. Tnks n blessings
@NotThatGuy_YepThatGuy3 жыл бұрын
I struggle with mechanical load and ambient control. Specifically the applications of Hot Gas bypass and Headmaster Valves. I mostly understand what they do, and why, but i have the damndest time troubleshooting if they are the problem. Thanks for this video. Long time watcher, seldom commentor.
@chrisnorris19593 жыл бұрын
Thanks Gary! Great explanation. Watching this video will make the actual Sporlan literature for these valves easier for me to digest.
@HVACKnowItAll3 жыл бұрын
I love hearing that, thank you
@VapourRose3 жыл бұрын
We use the same pipe set up but use a rapid cycle solenoid and no HGBV to control really tight temperatures in our environmental rooms.
@HVACKnowItAll3 жыл бұрын
Cool!
@MistaWhatchaKnow2 жыл бұрын
Do you use a PLC to control the toggle cycle of the solenoids? Or is it controlled by a relay?
@VapourRose2 жыл бұрын
@@MistaWhatchaKnow we use a Loop controller and a relay to cycle it on and off. Company be buy the controllers from is called Future Design control and its the R-22 controller.
@MistaWhatchaKnow2 жыл бұрын
Thanks! I took a look at the website and the controllers they offer. Never heard of this company, but they type of controllers look like a nice drop in for Watlow controllers. I really like the Watlow controllers, but they are very expensive. Most customers don’t need the amount of features either. What I have found out is toggling solenoids works well, however some size units need an adjustable valve inline with the solenoid to meter the amount of hot gas entering the evaporator. This way to can adjust the Hot Gas Bypass Valve to the exact PSI that you want. I watch the controller to see the temp swing. I want to mention that Hot Gas is not greatly energy efficient, although the machines run really well when not cycling and can maintain a consistent temp inside the evaporator. We can hold a temp of -+.5 degrees on oil and water cooling. This helps our customers achieve ultra precision in their processes.
@mikhaielj846 Жыл бұрын
Thanks so much needed this for tomorrow’s job
@epicone24493 жыл бұрын
Great videos man. Listen to your podcast too. Thank you for what you do for the trade
@HVACKnowItAll3 жыл бұрын
Thank you, doing my best haha
@mikefreedom56123 жыл бұрын
Good video! It's a way to balance the load on small refrigeration systems
@daviddesilva49713 жыл бұрын
Great explanation on the hot bypass valve. Thxs for the vids!
@HVACKnowItAll3 жыл бұрын
Thank you and my pleasure
@michaelbalke23143 жыл бұрын
Great explanation of the system!
@HVACKnowItAll3 жыл бұрын
Thank you
@Jeff-Lawrence3 жыл бұрын
Love this style of vid. Great work
@HVACKnowItAll3 жыл бұрын
Thank you I appreciate that!
@mdmuntasiralam774 Жыл бұрын
Great demonstration! Thank you very much. What's the purpose of the pressure equalization line here?
@shockiller4653 жыл бұрын
Thank you sir; Great Video keep up the good work
@bhunter38503 жыл бұрын
Thanks for the knowledge. I think I’ve learned more from your videos than my coworker who considers himself a “super tech”.
@HVACKnowItAll3 жыл бұрын
My pleasure. Lol!
@shanegreen2683 жыл бұрын
Thank you for sharing your knowledge. Great video
@HVACKnowItAll3 жыл бұрын
Thank you and you're welcome
@shanegreen2683 жыл бұрын
@@HVACKnowItAll you bet..
@sdsd42843 жыл бұрын
So technically its job is similar to a epr and a headmaster ? Great vid and EXPLANATION btw u make it very understanding.
@HVACKnowItAll3 жыл бұрын
Not really a head master maintains head for low ambient and an EPR is on the outlet of the evaporator
@sintongbutarbutar84783 жыл бұрын
Very clear explanation, thx
@HVACKnowItAll3 жыл бұрын
You're welcome
@abazism9 ай бұрын
Wow very well explained.
@janeilquino25993 жыл бұрын
Good day sir.thanks for information very clear explanation
@mr.fahrenheit7232 жыл бұрын
This is a great video!
@HVACKnowItAll2 жыл бұрын
Thanks
@neilvestervictor1803 жыл бұрын
great information knowledge is the key to success
@HVACKnowItAll3 жыл бұрын
Yes it is, thank you
@neilvestervictor1803 жыл бұрын
I am a chill water technician from st Lucia
@HVACKnowItAll3 жыл бұрын
Lovely weather I bet!
@neilvestervictor1803 жыл бұрын
yes sunny in the Caribbean with a little rain in between you should take the trip on a vacation lol
@HVACKnowItAll3 жыл бұрын
Yes but our conrona restrictions re-entering are crazy so no traveling for a while.
@TheLinkIsLost2 жыл бұрын
Very well explained. Thanks!
@johnpolos87962 жыл бұрын
Have you worked on environmental test chambers and chillers?
@nimbo94922 жыл бұрын
I have seen some hot gas bypass lines connected to the suction line (in between compressor and evaporator) as opposed to inlet evaporator like in this video. How are they exactly different?
@renecuevas4128 Жыл бұрын
Same question i got when i see his Diagram seems like same Line ......but doing different case scenario as he mentioned Movie Theater....Low Load versus LAT make sense i guess ....
@chantaledamiengatien7253 жыл бұрын
Hi, Great video ! I have also a hot-gas bypass valve on my LG multisplit, but it is bypassing directly the compressor's output to the input of the accumulator (just before the compressor input). When the hot-gas is activated, for example when a split is stopped, I can see the high pressure decreasing and the low pressure increasing. However, what is strange to me, is that when the hot-gas is deactivated after 30 seconds, the high-pressure recovers quite fast its initial value, but the low pressure is dropping much lower than its initial value (for example, from 8.3 bars to 6.7 bars) and seems to stay at this lower value (until the outdoor unit regulation is changing the inverter compressor speed). Do you have some explanation why it behaves like that ? I am not really sure that it is normal since it is generating periodical fluctuations of the regulation :( Thanks a lot and regards
@chova210 Жыл бұрын
Well explained 👏
@syedbasheer82103 жыл бұрын
Good explanation👉
@HVACKnowItAll3 жыл бұрын
Thank you!
@mahmudnady18593 жыл бұрын
Thanks for the information
@juvaeljadman22962 жыл бұрын
Good day sir. What is the actual low pressure of -10 and what is the deffirential walk in chiller. Thank for your help
@natepeterson71453 жыл бұрын
Well done!
@HVACKnowItAll3 жыл бұрын
Thank you
@simohvac92223 жыл бұрын
good explanation thanks
@HVACKnowItAll3 жыл бұрын
You're welclme
@mematyi3 жыл бұрын
Great Explanation! Could you make a video explaining the difference between this Hot-gas bypass valve method and the Evaporator pressure regulator (Danfoss KVP)? Is it technically the same?
@sholapuramtoday1596 Жыл бұрын
If discharge high pressure and high temperature that time not use this please explain
@Sigmameals3 жыл бұрын
Will you be able to put what you explained on a PH diagram or in equation forms using thermodynamic cycle?
@mrgreen90863 жыл бұрын
Great explanation is this system factory or do some components needs to be field installed?
@HVACKnowItAll3 жыл бұрын
Both
@mrgreen90863 жыл бұрын
@@HVACKnowItAll thanks for sharing
@herbertfynnwilliams51773 жыл бұрын
I have questions? am working on a unit that has hot gas valve when you put the unit on the temperature is able to come down to about 19/c but when the hot gas comes on you have the temperature reading 23 and it doesn't come down any more
@HVACKnowItAll3 жыл бұрын
These are room temps? Hot gas is for low load conditions. It needs to be set to supply hot gas when the load and corresponding evap pressure falls off.
@ollirbasepeacefulmusic65082 жыл бұрын
Why you don't see hot gas bypass to use as defrost in domestic fridge or freezer? My dad use to have an old fridge with hot gas bypass defrost
@محمودحمدي-ظ9ظ2 жыл бұрын
Can i replace the sporlan hot gas bypass valve with a solenoid controled by a digital tempreature sensor The sensor will measure suction line temp and control hot gas bypass valve
@stefanocubero63677 ай бұрын
Thanks man!
@dinushakumara45802 жыл бұрын
is this condition liquide refrigerant may be come back to the compressor
@bradmironik61373 жыл бұрын
Good video. I follow on how the hot gas creates a load on the evaporator but is there another component after such as an accumulator to return the refrigerant back as a vapor? I haven't seen this setup in the field before. Thanks.
@HVACKnowItAll3 жыл бұрын
There is never a receiver after an evaporator, the receiver is after the condenser. It's still returning as a vapour, the discharge gad is highly superheated vapour
@HVACKnowItAll3 жыл бұрын
Sorry my bad, thought you said receiver but none the less no vapour will get back during hot gas byapss
@bradmironik61373 жыл бұрын
Thanks for responding. So you are saying the hot gas in the evaporator has some heat removal but not to the point of changing state? Therefore vapor still returns to the low side of compression.
@capitolrefrigerationheatin75013 жыл бұрын
@@HVACKnowItAll I see accumulators after evap to catch any liquid,saves compressor from slugging
@Username-ng8jy3 жыл бұрын
Yes those are common in refrigeration. I used to do commercial refrigeration. It was a vital component especially freezers where the coil must be flooded with liquid for below zero temps.
@oriansinkleryukon2680 Жыл бұрын
What actually shuts cooling down will the hot gas bypass continue to run when show is over
@HVACKnowItAll Жыл бұрын
If it hits full on set point, the system will shut down. The hot gas will stop feeding on the off cycle.
@sumantaparamanik78632 жыл бұрын
It can be use Blast Freezer? Plz explain me
@fret2fret2213 жыл бұрын
The way you explained this sounds like it operates similar to a TXV...
@Username-ng8jy3 жыл бұрын
Nah dude. Nothing at all lol. A txv is there to throttle liquid into evap to provide cooling. This is just a valve that allows heat to enter the low side to increase pressure a bit when there is no load.
@723lion3 жыл бұрын
HGBV is for tight temperature control.
@arazqurbanov816210 ай бұрын
Salam size bir sualim var? Valve soyuq hava seraitnde isleye biler
@maheradous9257 Жыл бұрын
Good job
@ramilolanda85172 жыл бұрын
How do bypass valve of expansion valve works?
@peterrivas083 жыл бұрын
Really good video but could you or someone please explain the difference between this and a headmaster valve? Are they essentially they same just different terms? Thanks
@ES-ml4cg3 жыл бұрын
Headmaster or OROA is for head pressure control at low ambient conditions.
@peterrivas083 жыл бұрын
@@ES-ml4cg thank you for the reply. Sorry I'm just confused, but why do you need to keep the head pressure up? So the low side stays up as well?
@aircooledchilleralltypes49383 жыл бұрын
But what is the function of the equlizer line
@andrewnolan8449 Жыл бұрын
One of the very important part on hot gas defrost missing …
@HVACKnowItAll Жыл бұрын
This is not hot gas defrost, it's hot gas bypass
@joeschneider673 жыл бұрын
Thanks
@HVACKnowItAll3 жыл бұрын
My pleasure
@pangmlrani52003 жыл бұрын
Does the compressor delivery pressure becomes less when bypass valve is open?
@HVACKnowItAll3 жыл бұрын
No it becomes more, it's adding pressure the to suction line
@HVACKnowItAll3 жыл бұрын
But on the discharge line the pressure will drop a little, sorry, not exactly sure what you're asking.
@Sorcerers_stash3 жыл бұрын
Good stuff
@HVACKnowItAll3 жыл бұрын
Thank you
@fret2fret2213 жыл бұрын
The guy training me saw one of these the other day and legit said “I’ve never seen anything like that before...” 🤦♂️
@tonydellapennajr26813 жыл бұрын
You're dragging the guy training you because he hasnt seen something?
@harendradangwal63822 жыл бұрын
Hot gas bypass valve in Air dryer not allowing to transfer the Cold refrigerant into evaporator why? transfer hot refrigerant into evaporator
@mkamal28923 жыл бұрын
how does hot gas bypass work??
@HVACKnowItAll3 жыл бұрын
That was explained in thr video
@Boz12111112 жыл бұрын
seems like it wastes energy not to cycle compressor?
@jasonjohnsonHVAC Жыл бұрын
RAWAL DEVICE WOULD BE GOOD IN THIS EXAMPLE
@arazqurbanov816210 ай бұрын
Salam
@Coonhoound893 жыл бұрын
Awesome
@josebetancourt6866Ай бұрын
Easy explanation. Thanks 👍
@fret2fret2213 жыл бұрын
The way you explained this sounds like it operates similar to a TXV...
@HVACKnowItAll3 жыл бұрын
Not exactly, TXV opens on a rise in bulb temperature. A hgb valve opens on drop in suction pressure.