Chiller tripping LOW SUCTION Trane RTAA

  Рет қаралды 9,907

HVACTIME

HVACTIME

Жыл бұрын

A continuation of the oil level call. I got the final issue resolved now.
Get 8% off at TruTech Tools with promo HVACTIME
www.trutechtools.com/?ApplyPr...
Get tech support, training, and the Tech Blog at hvactimetx.com
You can contact me at Hvactimetx@gmail.com
Support my COFFEE problem through,
venmo.com/code?user_id=316085...

Пікірлер: 25
@TheMinecraftACMan
@TheMinecraftACMan Жыл бұрын
I love how all the weird problems tend to have a really simple cause like this.
@daviddesilva4971
@daviddesilva4971 Жыл бұрын
Looks like a previous technician was upset with the control panel. Thxs for the vids!
@jasonjohnsonHVAC
@jasonjohnsonHVAC 10 ай бұрын
Knowing sequence of operations can be an extremely valuable tool.
@lukehodgson5222
@lukehodgson5222 Жыл бұрын
Great job man! I learn a lot about chillers from your channel. Thanks for putting out the information.
@HVACChillin
@HVACChillin Жыл бұрын
Great troubleshooting!!!
@fshn76
@fshn76 Жыл бұрын
I love to watch your videos. I hope to be working on the big stuff someday.
@jamesfitzsimmons381
@jamesfitzsimmons381 Жыл бұрын
You’re one smart tech
@thesilentonevictor
@thesilentonevictor Жыл бұрын
Troubleshooting at its best
@mariob3265
@mariob3265 Жыл бұрын
I had a similar situation with a YLAA york chiller, compressor was grounded, replaced the tandem set, when i started the circuit up the Hot gas bypass was on, it was cold outside when we started the circuit so i thought the bypass being on was fine, came back next day to check oil levels and clean up the job site and one of the compressor was out on thermal, reset the fault and the loop was at 60, and i could hear the hot gas bypass valve on, i checked my solenoid and i wasnt getting voltage, well ended up finding out someone had taken the hot gas output , removed it from its terminal and landed it on the LLS for stage one, So it was bypassing on every run cycle, I dont know who did it , but i can only assume it was to add add since we have winters down to -30f. Put it back to its terminal and havent had a problem since.
@Manny32V
@Manny32V Жыл бұрын
I've had a lot of issues with female unloader solenoids either being energized all the time or not energizing at all. i have an account with 3 RTAC chillers and have replaced two dual triac boards along with solenoid female unloaders. The rtaa is quite a bit difference than the rtac as far as the controls but they function basically the same.
@jackandaustinsdad
@jackandaustinsdad Жыл бұрын
do you have a vid of adding the oil and the procedure used? great video thank you!
@TheRenaissanceBuilder
@TheRenaissanceBuilder Жыл бұрын
Good and informative video, thank you. Wish you didn’t hafto yell but it’s noisy, not sure theres any way to avoid that.
@LC-qi5ff
@LC-qi5ff Жыл бұрын
Where did all the oil go?
@hubert187
@hubert187 11 ай бұрын
We have a RTAA, and the pressure readings are all messed up. Turns out the chiller uses the temperature sensor to convert the pressure using a pt chart for r22. (We use nu22). Do you know if the refrigerant temperature probe has a well? Or is the temperature probe held by a gasket?
@ChillersRepair
@ChillersRepair Жыл бұрын
do you just record with your phone?
@royamberg9177
@royamberg9177 Жыл бұрын
Good diagnostics. Finding a screw up can be tricky. And the response is it's always did that or something to that effect
@BasharatAli-xg2yf
@BasharatAli-xg2yf 4 ай бұрын
Havc chiller 5 mint raining .and off whts porablam
@calicuts909
@calicuts909 Жыл бұрын
Hello sir question for you we have an old chiller for a high school campus that is going off on unsafe suction. I know that each classroom evaporator coil is extremely dirty. Would that cause the chiller to go on unsafe suction?
@HVACTIME
@HVACTIME Жыл бұрын
It can if the return water to the chiller is coming back to cold.
@chungkaryee8331
@chungkaryee8331 Жыл бұрын
Hi sir, i would like to ask do you know what causes : Low Saturated Suction Temperature (SST) alarm happen? I have change the temperature sensor but still coming out one time per day. After manual reset the alarm then the compressor can run again. I was out of idea. Thanks.
@fathmasameer7523
@fathmasameer7523 Ай бұрын
Check your exv
@djawahvac2833
@djawahvac2833 6 ай бұрын
Bisakah anda membagikan wiring diagram rtac 300d? Karena saya mengalami kesulitan contactor run tidak bekerja
@jrtapia2229
@jrtapia2229 Жыл бұрын
So what happened to the oil? So after the system is working for a few days, you gonna have to remove some of the oil?
@HVACTIME
@HVACTIME Жыл бұрын
The oil was lost from leaks, repairs, and a compressor change out. In that process we lost just enough to start having symptoms without enough going back in. The system was functioning it was just not able to load properly so we weren't having a migration issue. Since we got the oil level up we have not had any further problems in the oil has maintained properly.
@mdsbayezid2024
@mdsbayezid2024 Жыл бұрын
Sir Hindi mein batao
Low Oil Troubleshoot RTAA Chiller
11:24
HVACTIME
Рет қаралды 14 М.
Startup Issues with Trane Chiller
7:23
HVACTIME
Рет қаралды 7 М.
Получилось у Вики?😂 #хабибка
00:14
ХАБИБ
Рет қаралды 7 МЛН
Me: Don't cross there's cars coming
00:16
LOL
Рет қаралды 13 МЛН
🌊Насколько Глубокий Океан ? #shorts
00:42
CGAM 110 Chiller EXV Comm Loss And Not Cooling | Multiple Issues
12:14
Diagnosing a Locked Compressor 3D
10:02
HVAC School
Рет қаралды 44 М.
Trane chiller EXV  installation
4:25
HVAC Tips&Tricks
Рет қаралды 7 М.
HVAC 070 Suction line Filter Drier
14:04
Love2HVAC with Ty Branaman
Рет қаралды 17 М.
Cooling Tower Setpoint For Chiller
19:24
HVACTIME
Рет қаралды 34 М.
Trane RTAC Pt. 2 - Filter Drier, Vacuum, Recharge
23:33
DFW HVAC
Рет қаралды 10 М.
URDU I HIND I ME | Chiller low pressure || chiller men low pressure kin wajeh  aata hai |
11:32
TRANE INTELLIPAK Not Cooling!!! Diagnosing Compressor Lockout EP88
14:21
Получилось у Вики?😂 #хабибка
00:14
ХАБИБ
Рет қаралды 7 МЛН