SIR how to make air balancing hvac in hospital room pls make video on this topic
@rakshithbrahmeswaram3093 Жыл бұрын
Very nice video sir. can you please make a detailed tutorial on cleanroom design using sample project, Thank you.
@haiderabbas47237 ай бұрын
did you find out how to hvac design cleanroom? can i contact you thru whatsapp? thanks
@passionateengineer047 ай бұрын
Yes, we are design consultants. See my email in channel about
@gisound96442 жыл бұрын
As-salamu-alikum, Remarkable presentation, This is most important and Value able HVAC Contain.
@passionateengineer042 жыл бұрын
Walaikumasalam Thank you
@niluboy64833 жыл бұрын
How to calculate all things cooling load with motor size ,blower size, cooling colis size , ahu required CFM and all in detail please make video 🙏 Please reply
@gardineatawreed39492 жыл бұрын
Tank you for your efforts
@MuhammadJawad-mx3yh3 жыл бұрын
Thanks for sharing such valuable knowledge. can you share the HAP report & dwgs?
@passionateengineer043 жыл бұрын
Sorry, its confidential, i will share some other files with you.
@khuhr02 жыл бұрын
@@passionateengineer04 can u kindly share the HAP report with me?
@faisalhussain22793 жыл бұрын
Sir Which instruments use for test the particle size to identify the ISO classes
@passionateengineer043 жыл бұрын
There are different instruments used for particles test, it depends on particles like Aerosol,liquid and solid. Direct imaging uses light emitted by a laser as source to illuminated the particless passing through and measure the area of particles, like an automated microscope. One of instrument is Airy technology Laser particle counter.
@hpzen83713 жыл бұрын
Good video sir
@milonkhan48893 жыл бұрын
Nice video sir... I have one question. i am using ACPH method by E20 form or manual..when i calculate same cooling load by HAP as a result CFM rate is much different comparing with E20 form... So please tell me which i will consider as perfect..
@passionateengineer042 жыл бұрын
What are you defining in HAP , ASHRAE 62.1 or sum of outdoor air? It all depends on your inputs
@hpzen83713 жыл бұрын
Sir, can u make a video on natatorium HVAC system
@manumurali99642 жыл бұрын
If I need to maintain a room temperature of 58Deg. F at what temperature do I need to set the off coil temperature.
@passionateengineer042 жыл бұрын
Detal T = 10 to 15 Depending on type of system.
@niluboy64833 жыл бұрын
Which software useM
@mustafajadallah40072 жыл бұрын
Hi . How can I add treated fresh air to cooling load calculation considering kitchen which has 1800 cfm exhaust. And I want to add 90% fresh air but treated by FAHU 100% WITH entering temperature 75 F
@mustafajadallah40072 жыл бұрын
How 75 F OA can be added to kitchen
@passionateengineer042 жыл бұрын
@@mustafajadallah4007 There is no option for treated air in HAP, but you can calculate it separately using psychometric chart and than add it misc load in HAP
@mustafajadallah40072 жыл бұрын
Thanks for your reply
@ajayvasudevan57433 жыл бұрын
How to calculate ach in cleanroom
@passionateengineer042 жыл бұрын
Q=volume of roomxACH/60 so ACH=Qx60/volume.
@passionateengineer042 жыл бұрын
Calculate the total airflow in room and than use that equation.
@ajayvasudevan57432 жыл бұрын
@@passionateengineer04 okey thankyiu
@adityavibhute62253 жыл бұрын
For 320Sq.ft size of Operation theatre, we use 8 to 10Ton condensing coil. Is it right?? Also can you show how to calculate heat load of clean room using E-20 form??
@passionateengineer043 жыл бұрын
You have to maintain 20ACH, with Standard occupancy of 5-8 persons at any given point of time inside the OT is considered.Standard equipment load of 5-7 kW and lighting load of 1 kW to be considered per OT. For super specialty OT the equipment load can be taken as 7 - 9KW. The fresh air component of the air change is required to be minimum 4 air changes out of total minimum 20 air changes.
@madhukarat19923 жыл бұрын
@PASSIONATE ENGINEER I think as we taken these details, around 6TR/2500 cfm ahu only required for 320 sqft OT..fresh air around 450 cfm...is it right?
Total tonnage is to high what you shown in report but practically that much no one will take because you have taken based on acph
@passionateengineer043 жыл бұрын
You have to maintain ACH, cooling and pressure at same time.
@passionateengineer043 жыл бұрын
Its designed on basis of 50c.
@sridharreddyasr3 жыл бұрын
Tonnage you shown in video is for only one room Or all iso 6 rooms
@passionateengineer043 жыл бұрын
Its for all iso 6 rooms
@sridharreddyasr3 жыл бұрын
Ok thank you
@moayedtawfiq2843 Жыл бұрын
👍🙏
@areenalali4 ай бұрын
Hello , I don't think that using high ACH in load calculation is correct ,, ACH that must be used in HAP is the one related to fresh air requirements , however, the ACH related to cleanliness should be considered to calculate the number of fan filter units to circulate the air through HEPA filters , hope to hear back from you.
@passionateengineer044 ай бұрын
Sorry for that, but you are not right, ACH is a part of load calculation. Based on this, you will select equipment and cfm/ton. Coil load and supply air temp depends on this. Thank you
@areenalali4 ай бұрын
@@passionateengineer04 thanks for your reply ,, but I did many cleanrooms in Canada ,, ACH doesn't mean fresh air ,, these are two different things ,, I agree that fresh air is part if the load calculation and it can be part of the ACH ,, but considering that ALL the ACH is fresh air is something that we don't do .
@passionateengineer044 ай бұрын
Both ACH are part of load calculation. If you are working in Canada, then it's also the same, but the difference is the fresh air unit, like if you are using HRV, makeup air unit etc than you don't need to consider the fresh air ACH. You can do differently, calculate the load, and than put user define air flow based on ACH.
@passionateengineer044 ай бұрын
In which province of Canada are you working? Are you familiar with CSA Z317.2? ALBERTA COLLEGE OF PHARMACY?
@areenalali4 ай бұрын
@@passionateengineer04 I work in Ontario,, would be great if we can have a call to discuss.
@hassankhalidpy3 жыл бұрын
Hi!
@hassankhalidpy3 жыл бұрын
Can you share any Map of any building or hospital like the one explained in video
@joegeorge98283 жыл бұрын
No video only sound
@joegeorge98283 жыл бұрын
No video
@passionateengineer043 жыл бұрын
Kindly check it again, its video with sound. Thanks
@mz60273 жыл бұрын
Bhai urdu ma bat karo. koi gora to ye sunne ga nhi
@passionateengineer043 жыл бұрын
Its for all not for a specific country or language.