Mastering Trane Chillers: High Condenser Pressure

  Рет қаралды 2,647

THE CHILLER GUYS

THE CHILLER GUYS

5 ай бұрын

📱The Chiller Guys Information Sharing Group:
www.thechillerguyshub.com
IN THIS VIDEO, I BREAK DOWN THE DIAGNOSTIC PROCESS FOR THE 4 MOST COMMON REASONS FOR HIGH HEAD PRESSURE ON A TRANE CVHE / CVHF LOW PRESSURE CENTRIFUGAL CHILLER.
SOME COMMON ISSUES THAT MAY OCCUR FROM HIGH HEAD PRESSURE ON A CENTRIFUGAL CHILLER ARE:
HIGH CONDENSER PRESSURE TRIPS
CHILLER SURGING
HIGH CONDENSER PRESSURE HOLD MESSAGES
CHILLER WILL NOT LOAD UP
HIGH EVAPORATOR LEAVING WATER TEMP
I TALK ABOUT:
AN OVERLOADED CHILLER
FLOW ISSUES ON A WATER COOLED CHILLER
AIR IN A LOW PRESSURE CHILLER
WEATHER YOU A NEW AC OR CHILLER TECHNICIAN, OR YOU HAVE BEEN AT THIS FOR AWHILE THERE IS ALWAYS SOMETHING TO LEARN.
FOLLOW ALONG, LEARN TRANE CHILLERS, AND BECOME THE BEST TECHNICIAN YOU CAN BE.

Пікірлер: 16
@TheChillerGuys
@TheChillerGuys 5 ай бұрын
Whos your favorite chiller manufacturer?
@toyinorodare4072
@toyinorodare4072 4 ай бұрын
My favourite is Carrier and Trane
@TheChillerGuys
@TheChillerGuys 4 ай бұрын
I really like Trane stuff, for reliability. And I honestly really like Daikin stuff, and long as it’s taken care of and maintained, But I am biased lol
@muralimurali-lm5hx
@muralimurali-lm5hx Ай бұрын
Trane chillers best ❤
@toyinorodare4072
@toyinorodare4072 5 ай бұрын
Thank you I am now one of your followers I hope to learn alot from you
@TheChillerGuys
@TheChillerGuys 5 ай бұрын
Thanks man, I will be uploading a lot more useful content as well, and videos will get higher quality as time goes on. We also have a facebook page as well if you ever need any help with diagnosing. its called "The Chiller Guys" the link is in the video description. If you ever need anything you can always ask here as well, just takes a little longer for me to reply.
@toyinorodare4072
@toyinorodare4072 5 ай бұрын
@CapitolDiagnostics oh that is great I am working on a CLIVET Air Cool Chiller. One of the Compressors is tripping on High Pressure what could cause it? The high pressure switch is in good condition The Condenser fans are running The coil has been cleaned on Saturday I don't know what to check again, yet it is tripping on High Pressure
@TheChillerGuys
@TheChillerGuys 5 ай бұрын
I can definitely help you with troubleshooting that, but first I will need some more info. If you can get me the following information I can tell you what the problem likely is. 1. Model number 2. How fast is it tripping? Immediately, after 5 minutes, or after awhile of running? 3. Entering and leaving air temp on the condenser 4. Discharge pressure 5. Refrigerant type. 6. Liquid sub-cooling 7. Number of circuits on the machine running and how many If you get me that info I should be able to tell you what’s going on.
@TheChillerGuys
@TheChillerGuys 4 ай бұрын
im really sorry for not replyin, i didnt get this message, im faster on our FB Group. it could have a few things, could be overcharged, could haver a liquid restriction, could be overloaded, condenser could be dirty internally. did you wash it opposite of airflow? sometimes the outside will look clean and its not really clean. you could also have fans shutting off on overload, go up and check all the bearings. another issue i have had is recirculating air. check this stuff and let me know! i can help you with this if your still having issues, again, youtube didnt send me this message, i just happend to see it, im sorry for taking so long man..@@toyinorodare4072
@toyinorodare4072
@toyinorodare4072 4 ай бұрын
@TheChillerGuys thank you man I will work on this
@user-yo8om6cv2j
@user-yo8om6cv2j 3 ай бұрын
How to order your sheets?
@TheChillerGuys
@TheChillerGuys 3 ай бұрын
The diagnostic sheets? the link for them is in the description, just click on the link and it will take you right to them. let me know if you have any issues with it. otherwise just google "the chiller guys" and we should be one of the first ones on the page.
@TheChillerGuys
@TheChillerGuys 3 ай бұрын
let me know if you figured it out man. use the promo code
Smart Sigma Kid #funny #sigma #comedy
00:25
CRAZY GREAPA
Рет қаралды 12 МЛН
When You Get Ran Over By A Car...
00:15
Jojo Sim
Рет қаралды 13 МЛН
Do Line Restrictions Cause High Head?
7:31
HVAC School
Рет қаралды 79 М.
What I do for a living, building engineer!
25:16
Group B EJ25
Рет қаралды 5 М.
Cooling Tower PM Basic's HVAC Training for HVAC Technician
34:57
CGAM 110 Chiller EXV Comm Loss And Not Cooling | Multiple Issues
12:14
Cooling Tower Setpoint For Chiller
19:24
HVACTIME
Рет қаралды 34 М.
Smart Sigma Kid #funny #sigma #comedy
00:25
CRAZY GREAPA
Рет қаралды 12 МЛН