YK online training at chilleracademy.com Get Confidence and Accuracy with this Troubleshooting Guide! hvactime.shop/products/yk-tech-sheet
@Kbrew8888Ай бұрын
Being put in front of a YK chiller for the first time in my career was a little intimidating...this video was extremely valuable to me in learning exactly how the oil system works and put me on the right track. Thanks for making the effort to inform other technicians! You're a rockstar!
@jpac2g Жыл бұрын
This video is pure gold, thank you for sharing your knowledge. Videos like this weren't available, and in this detail, just years ago. I can tell that you know your stuff, keep them coming please, Thank You!
@bill8985 Жыл бұрын
It has been decades since i had to buy, install, and maintain one of these guys... Your explanation was super clear and brought back some nostalgia. Thanks!
@Erikmiles87 Жыл бұрын
Thanks. Was explaining eductor lines to my apprentice. I’m going to show him this video so he can see the internals
@twilks7878 Жыл бұрын
I love these chiller videos, I work at JCI and you explain better than my JM.
@TheRenaissanceBuilder Жыл бұрын
Good video bud. I giggled a bit over the camera angles only because I recognize how difficult entertaining camera angles can be to find sometimes
@멍꿀-e5t8 ай бұрын
I am a JCI YK centrifugal turbo chiller engineer. The video was very helpful. I would appreciate it if you could upload more videos. I am curious about the role of each material inside the chiller. The information about the oil line is similar to what I thought. thank you
@EverythingHVACR Жыл бұрын
Great information Holden, thanks
@DannyBokma Жыл бұрын
Ow man, all this information, thanks so much for sharing these insights! What a wonderful world an time we live in ^^!
@HVACTIME Жыл бұрын
Thank you for the support!
@fathmasameer7523 Жыл бұрын
Great experience you deserve more subscribers dude thanks
@tylerferrell2959 Жыл бұрын
Dude you kill it in these videos
@GordonHVACR Жыл бұрын
Thanks for making this outstanding video! Proud of your hard work !
@onesimpleman1 Жыл бұрын
Excellent video on oil system
@brandonwalker484211 ай бұрын
Did you have to recover all the refrigerant to work on the sump or where you able to isolate. I have to work on oil sump. I have isolation valve on discharge piping going to condenser but nothing on the evap. So, my question to you is do I need to recover the entire charge.
@HVACTIME11 ай бұрын
Yes, you wiil need to recover charge.
@wata_laf11 ай бұрын
Wildly informative 👍🏼👍🏼
@gatoguevara71 Жыл бұрын
Great job thank you for sharing your experience
@bornjanuary25 Жыл бұрын
Kindly make review for Carrier chiller GX30 and 30GT with your amazing manner ( operation , service and maintenance )
@igariokmihailov44619 ай бұрын
great video buddy, i have a small leak on the oil sight glass, could be the o-ring , do i have to drain the oil in order to replace it, or i have to remove the front plate also? Thanks in advance
@texture6 Жыл бұрын
Thank you to infinity
@DronePilot4k7 ай бұрын
Thanks for the video , appreciate you taking the time to share. What is the sequence for the solenoid on the oil return line? Is it open during on cycles and closed on off cycles?
@HVACTIME7 ай бұрын
Yes, and the oil temp will influence it opening
@DronePilot4k7 ай бұрын
Thank you very much , so if the oil temperature in the sump is already low it will stay closed?
@HVACTIME7 ай бұрын
@@DronePilot4k exactly
@DronePilot4k7 ай бұрын
Thanks!
@HVACTIME7 ай бұрын
Thank you very much!
@dmc357 Жыл бұрын
Great video!!
@foodtravelxp24 Жыл бұрын
Dear boss my york centrifugal chiller a Alam coming oil-low differential pressure calibration. So i can remove this alarm??
@justinkendollrozinek Жыл бұрын
Super smart
@kobebryant4750 Жыл бұрын
What is the meaning of oil variable speed pump contacts open? Plss help me
@jasonjohnsonHVAC Жыл бұрын
Good stuff
@hvac88264 ай бұрын
❤
@joshstevens9826 Жыл бұрын
I'm curious, do you take annual oil samples? Or is it when a problem is suspected? Where I am wr do filters and oil samples with every annual we do.
@HVACTIME Жыл бұрын
I do annual samples with lab analysis
@jarredallen Жыл бұрын
I hate opening york chiller oil sump. they are always in an awkward location. they either in between compressor and condenser shell or at the bottom of the shells.
@technicalfeatures5748 Жыл бұрын
Sir can you tell me how to cooling YK chiller heartsink, i have facing this problem high heart sink temperature
@technicalfeatures5748 Жыл бұрын
This is soild state starter
@Henryolson099 ай бұрын
Ferncos and PVC on the pressure safety valves!? That might be worse than not piping them outside at all
@kettlergaudi10 ай бұрын
please advice have you ever have this problem ?, I am getting the oil loss in oil sump chiller York YK Centrifugal. The oil seems goes to evaporator The above problems occurs after : 1. We have changed the oil Return Solenoid 2. add extra valve for changing the TXV oil temp control (so if we need to change the txv no need to transfer pump down the R134a) 3. Change the new oil pump The actions that we already redone : 1. change again the oil return solenoid to the old one 2. change the oil cooler heat exchanger 3. change the txv oil temp control to the old one, but the extra valve for service still there (because of welded) 4. checking the oil block eductor inside the oil sump ( the springs are doing pretty well) The problem still remain ,getting the oil loss in oil sump chiller York YK Centrifugal. The oil seems goes to evaporator please advice, do you have any suggestion
@HVACTIME10 ай бұрын
How much run time in-between trips?
@kettlergaudi10 ай бұрын
only about start up 5 minutes , the oil sump level already minimum. The chiller still can run, but we just turn off the chiller off because the low level oil
@kettlergaudi10 ай бұрын
before we already pump down out the oil in the evaporator with its r134a , drain all the r134a and the oil in evaporator side
@Ariff-zt2gc Жыл бұрын
Hi bro Holden , basically i've experiencing quite a number of times OIL - VARIABLE SPEED PUMP - DRIVE CONTACTS OPEN FAULT ALARM . Checked and verified no voltage across the output . Replaced to a brand new VSOP Board as well but the fault came back again in just 2 months . Any other alternatives or solution on what to check ? Can temporarily bypass somewhere to make the system online ?
@southendcycleworks Жыл бұрын
The VSOP boards lately are not very good quality. They usually come with a 1 year warranty and I've had to use it many times
@nellAyaR2034 Жыл бұрын
Might want to get the input line inductor for vsop
@rmalanis134 ай бұрын
Having issues with a yk right now. While running sump LOP is about 60psig and evap is 38 psig. Changed oil filter and eductor. All valves open. Oil return solenoid working. But eductor filter stays hot, could it be bad balance piston seal, or faulty/plugged eductor block? If any one can assist it would be greatly appreciated
@rmalanis134 ай бұрын
To clarify Changed eductor filter, not block
@HVAC-EngineerRam Жыл бұрын
I want join this channel in Hindi language
@andrewjacks8671 Жыл бұрын
What does MTT mean? Multi-task trebuchet?
@HVACTIME Жыл бұрын
Make The Time for your spouse and family with our busy schedules.
@andrewjacks8671 Жыл бұрын
@@HVACTIME MTT. I like it. Thanks for the in-depth videos. Much appreciated.