System Crash takes out Chiller

  Рет қаралды 18,498

HVACTIME

HVACTIME

Күн бұрын

Пікірлер: 69
@HVACTIME
@HVACTIME Жыл бұрын
I have produced a 6 page Technical Reference Guide. hvactime.shop/products/yk-tech-sheet
@al.e123iis7
@al.e123iis7 3 жыл бұрын
I'm a software engineer. Did hvac during my undergrad and even an internship at carrier.. thinking of becoming an industrial tech soon. This office work is making me go crazy....
@HVACChillin
@HVACChillin 3 жыл бұрын
BAS COMPANY - “ It’s always the chillers fault. Our control system works flawless “ A lot places I work for always have a method of procedure written up to bypass BAS controls just in case stuff like this happens. Great video as always.
@spikester
@spikester 2 жыл бұрын
The fact they can always tell the chiller is at fault when they only ever have two signal control wires to start & stop such a massive thing.... but never mind that its 2022 they deflect whatever it is they don't need to be aware of based on the system design simply not providing it in the first place.
@therandomchannel6103
@therandomchannel6103 3 жыл бұрын
0:42 your finger was pointing right at the problem 😂 good old jci
@mansourghadhban236
@mansourghadhban236 2 жыл бұрын
Good job so wonderful control technician mansour from Iraq
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 жыл бұрын
Im still new to the industrial side. Coming from residential to comm/ industrial has been quite the eye opening experience. Im trying to learn as much as i can. I love this trade and i especially love the industrial side. In the year ive been on this side, ive learned i love the hydronics side and thats what i want to specialize in. Your videos are great, even if i dont understand some of it. I will become a proficient tech in industrial. I refuse to be average.
@JD-hr6dr
@JD-hr6dr 3 жыл бұрын
That's great that you are ambitious and want to learn, but none of the videos on this channel are truly industrial. This is what we refer to as "heavy commercial". Industrial HVAC/R companies don't deal with comfort cooling chillers such as this. They usually deal with : hydrocarbon process compression, ammonia refrigeration, recreational ice rinks, cold storage warehouses. The manufacturers and equipment they deal with: Mycom, Frick, Vilter, Howden, Sabroe, etc. On the heating side, we call it "process combustion", and it usually involves high pressure steam for things like pharmaceutical, food manufacturing, cement, steel, power generation, etc. Line heaters for pipelines. Boilers by Cleaver Brooks, Babcock and Wilcox, GE Boilers, or other industrial boiler manufacturers. They all use power burners, sometimes dual fuel. Gas valves and actuators by Maxon, everything 4-20 mA loops. Things like Viessmann, Wieshaupt, Riello, Aerco, RBI, Raypak are all considered commercial boilers/burners and you don't seem them in industrial applications You will never see that industrial equipment on this channel. It's a different part of the trade. Another key difference: heavy commercial deals with BMS (like in this video). Industrial applications usually stick with PLCs for process automation, not BMS systems. It's all cool stuff though.
@HVACTIME
@HVACTIME 3 жыл бұрын
@JD its true, I should probably do a better job at identifying that. When I first start a couple years back I was with another company and we had a lot of small industrial accounts. Its something I'm working us into at my current company. As you know its a tough market to get into.
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 жыл бұрын
@@JD-hr6dr we do have quite a few industrial customers and i understand what you said. To be honest here in Buffalo, most of our chillers are not for comfort cooling, they are for process cooling. Heating is a mixed bag of process and comfort here. We have a few places that have ultra high pressure steam. In excess of 1500 PSI and 800-1000° superheated steam. I haven't worked on any of that stuff yet.....but i set goals to get proficient enough to be able to. For me, i am a goal oriented type of person. I set goals to achieve and get good at, then i move on to the next challenge. I love challenges, its what keeps me going.
@spikester
@spikester 2 жыл бұрын
@@jasonjohnsonHVAC I've learned a lot just the last few months, what mostly sets the two industries apart when it comes to the commercial comfort hvac vs industrial refrigeration/heating; especially the boilers, are the unions you are required to join when crossing the barrier. It dives right into the steam/pipefitters.
@REFERTECH4U
@REFERTECH4U 3 жыл бұрын
I just want to say that your videos awesome you seem very experienced I appreciate you passing on your knowledge thank you once again
@EverythingHVACR
@EverythingHVACR 2 жыл бұрын
Nice job! Always good information, keep up the good work 💪
@creativetradesman6833
@creativetradesman6833 3 жыл бұрын
No doubt York makes the best centrifugals. That’s a nice machine it’s got some good options. I’m glad to see some Caribbean Blue on your channel.
@HVACTIME
@HVACTIME 3 жыл бұрын
Wish I had more of them
@houstonastrorider713
@houstonastrorider713 2 жыл бұрын
Great video. Getting ready to start working on chillers.. definitely learning a lot. Thank you.
@sreejithts9798
@sreejithts9798 3 жыл бұрын
very fine knowledge sharing about economizer system ,thanks
@countrykid1640
@countrykid1640 3 жыл бұрын
great video, except the NAE controller that you showed is for connected services and is connected to the elink on the upper left hand corner. it is on its own dedicated Port on the Elink. The BAS talks to the Elink directly on another port. The only thing that NAE is doing is taking the data from the chiller and sending it out on the attached modem and does not have any commands to send to the chiller. all of the BAS commands should go to the dedicated BAS port on the Elink card.
@realestateservicessaleshea99
@realestateservicessaleshea99 3 жыл бұрын
We had siemans control in every week. 😆 up grades or glitches. That's why when people talk about how automated they want their home to be I just look and laugh. KISS ! KEEP IT STUPID SIMPLE! 🍺🍺🍺🥃🥃🍿🏌🏻‍♀️ New sub! Stay safe. Retired (werk'n)keyboard super tech. Wear your safety glasses.
@HVACTIME
@HVACTIME 3 жыл бұрын
Happy to have you in the community!
@everestinspections9088
@everestinspections9088 Жыл бұрын
great videos thank you
@Erikmiles87
@Erikmiles87 3 жыл бұрын
In vegas, our water is so bad. Have to run the VSD water line to the evap. Condenser water pump plugs the heat exchanger faithfully and we lose our vsd to high temp
@alimran657
@alimran657 2 жыл бұрын
Can you please make a video on proximity diffreantial and thrust pad
@realestateservicessaleshea99
@realestateservicessaleshea99 3 жыл бұрын
We also had a control panel that if automation goes down put everything in hand and what's not needed off and watch!
@shivaHVAC
@shivaHVAC 2 жыл бұрын
How to replace vsop card for this chiller...any safety precautions need to take before?pls help
@nategadow4482
@nategadow4482 2 жыл бұрын
Great videos, thank you
@JD-hr6dr
@JD-hr6dr 3 жыл бұрын
Another great video, thanks for this. Just wondering if you ever work on modular chillers like Multistack, Arctic Chiller, ClimaCool, or niche chillers like Motivair or Smardt? It would be great to see content on that equipment.
@HVACTIME
@HVACTIME 3 жыл бұрын
Yes but it is pretty limited. We have been working to grow a presence in the industrial side as I get my team built. As of now just trying to keep up lol
@stlbrian33
@stlbrian33 3 жыл бұрын
Good job.👍
@petermcadam953
@petermcadam953 Жыл бұрын
You are brilliant at what you do ! Which state are you based ?
@HVACTIME
@HVACTIME Жыл бұрын
Austin Texas
@tonylaw196
@tonylaw196 3 жыл бұрын
May be a defected sensor or high level interface offline cause the chiller plant go into economize mode. NAE would not switch the chiller directly, it should be through the FEC controller to switch on/off everything. NAE will be phase out and replace by SNE controller.
@HVACTIME
@HVACTIME 3 жыл бұрын
Its an extremely unusual setup. The NAE ties back to a Schneider system and its all kinds on not right lol. They have been putting off a new system for way to long. Hence a Sidewinder from 81 still in operation lol.
@tonylaw196
@tonylaw196 3 жыл бұрын
@@HVACTIME That may be offline between the NAE and Schneider system, mixing two brand BMS may cause the system unstable. I have a experience the NAE offline due to Schneider system keeping to ping the NAE and make it busy. I isolated the Schneider system and the NAE back to online. In this case, it should be replace the Schneider system to Johnson Controls system.
@HVACTIME
@HVACTIME 3 жыл бұрын
@@tonylaw196 I'd be good with that!
@hectortorres542
@hectortorres542 3 жыл бұрын
Thank you for the video very informative
@ares3914
@ares3914 2 жыл бұрын
Do a video on these York chillers. There very interesting and not common in my area so would like to see that
@HVACTIME
@HVACTIME 2 жыл бұрын
kzbin.info/www/bejne/nJ2kfo2LgJiZZ5o
@julianpiper240
@julianpiper240 3 жыл бұрын
Have you got any jobs on the York YCWJ chillers? Or Carrier 19DG / 19XR chillers?
@HVACTIME
@HVACTIME 3 жыл бұрын
None that I have filmed
@johnhanson4909
@johnhanson4909 3 жыл бұрын
You could just put the optiview in local control and start it
@HVACTIME
@HVACTIME 3 жыл бұрын
I was keeping it simple for the customer when the automation got fixed.
@buildingstatux7720
@buildingstatux7720 3 жыл бұрын
Feel free to join the Boiler and Chiller guy group on Facebook and post these videos please
@HVACTIME
@HVACTIME 3 жыл бұрын
I appreciate the invite, just struggle with the time to do so
@prettycureforever7102
@prettycureforever7102 3 жыл бұрын
When you say ecominiser mode do you mean the rtu have eco mode settings or just a green thing. ?
@HVACTIME
@HVACTIME 3 жыл бұрын
They have a plant economizer using condenser water and chilled water
@buildingstatux7720
@buildingstatux7720 3 жыл бұрын
Good morning what those letters means at the electrical disconnect panel SCHP ???
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 жыл бұрын
Secondary chiller pump.
@buildingstatux7720
@buildingstatux7720 3 жыл бұрын
@@jasonjohnsonHVAC thank you do u mind translating all of them for me please
@edwardgarza5104
@edwardgarza5104 3 жыл бұрын
How is the chiller still running when you pulled the start stop relay? Is the chiller looking for a open circuit to start? Did you place it in hand? Or did I miss something? Thanks
@edwardgarza5104
@edwardgarza5104 3 жыл бұрын
I see now the relay is using a double pole double throw one normally open and one closed
@HVACTIME
@HVACTIME 3 жыл бұрын
@@edwardgarza5104 this chiller gets a start signal then it receives a stop signal when the automation shuts it down. After getting the signal it can loose the start contact and stay running as long as the stop contact doesnt close.
@edwardgarza5104
@edwardgarza5104 3 жыл бұрын
@@HVACTIME ok so both sets are on one relay? The start on the NO contact and the stop on the NC? Thanks for the response.
@HVACTIME
@HVACTIME 3 жыл бұрын
@@edwardgarza5104 exactly
@allanfernando5358
@allanfernando5358 3 жыл бұрын
Hi sir, How are you? Sir can you please show as the compressor contactor how it operates during start-up. I mean how it changes one to other part. Thank you sir.
@HVACTIME
@HVACTIME 3 жыл бұрын
kzbin.info/www/bejne/i56xh4t5j8qCrdE I explained that in this training.
@buildingstatux7720
@buildingstatux7720 3 жыл бұрын
Are you located in new york?
@HVACTIME
@HVACTIME 3 жыл бұрын
Austin TX
@BeGr8_CeSaR
@BeGr8_CeSaR 2 ай бұрын
What's your thoughts of houston. I'm from NY plan on moving there 2025 summer. 20yr tech. How's the pay.
@darvinmack615
@darvinmack615 3 жыл бұрын
Help! VSD-100% Motor Current Overload/Vane Motor Switch Open
@michaelmccleery948
@michaelmccleery948 3 жыл бұрын
Is the old train chiller still R-11?
@HVACTIME
@HVACTIME 3 жыл бұрын
Yes
@markefulton
@markefulton 2 жыл бұрын
JCI NAE, there's your problem with the whole thing.
@HVACTIME
@HVACTIME 2 жыл бұрын
🤣🤣
@James-vf5gs
@James-vf5gs 3 жыл бұрын
They should have made the remote stop relay fail safe, if the relay fails, the BMS cannot shut down the chiller.
@realestateservicessaleshea99
@realestateservicessaleshea99 3 жыл бұрын
If the automation fails you just can't start a chiller (tower,condenser pumps,chiller pumps,ect) have to be on before that baby Cooks or big troubles ahead! Also they must have flow issues to bypass flow switches????
@mohammedtanveer5247
@mohammedtanveer5247 2 жыл бұрын
What is password
@Attest411
@Attest411 3 жыл бұрын
Customer: Ever since you started your KZbin channel things started screwing up!! HVACTIME: But look at my subscribers!
@HVACTIME
@HVACTIME 3 жыл бұрын
Lol good one
Bad Oil Sensor Tripping York Air Cooled Chiller HVAC
18:52
HVACTIME
Рет қаралды 17 М.
So Cute 🥰 who is better?
00:15
dednahype
Рет қаралды 19 МЛН
To Brawl AND BEYOND!
00:51
Brawl Stars
Рет қаралды 17 МЛН
Une nouvelle voiture pour Noël 🥹
00:28
Nicocapone
Рет қаралды 9 МЛН
Chiller Basics - How they work
16:37
The Engineering Mindset
Рет қаралды 2 МЛН
I Messed up chiller board
15:55
HVACTIME
Рет қаралды 9 М.
TRANE CHILLER  SOFTWARE TECH VIEW BINDING PROCESS
20:38
HVAC Tips&Tricks
Рет қаралды 8 М.
HVAC Tech School: Understanding Chiller Surge
10:08
ControlTrends Smart Buildings
Рет қаралды 308 М.
Chiller Surging During Centrifugal Chiller PM
14:19
HVACTIME
Рет қаралды 22 М.
Cooling Tower Setpoint For Chiller
19:24
HVACTIME
Рет қаралды 39 М.
Oil System YK York Chiller
16:54
HVACTIME
Рет қаралды 18 М.
EXV Takes Out Chiller on Trane Air Cooled Chiller
15:01
HVACTIME
Рет қаралды 23 М.
So Cute 🥰 who is better?
00:15
dednahype
Рет қаралды 19 МЛН