When the generator number 3 is on alone, the voltage and amperage values are normal, but when we parallelize the other generators, the amperage values in the generator number 3 increase too much and load too high deviation alarm is given.
@leckyjake2 жыл бұрын
hello Chief, I would suggest to do these test. Considering that all filters are clean for all the generators. 1. Run the generators and observe the speed at no load. You need to compare each generators at no load and if there is unequal values then adjust the governor speed droop. You also need to manually measure the voltages of each generators by using portable voltmeter and not the one on the board. Sometimes measured values on the board are not accurate. If there is an unequal voltage then adjust it on the avr. Last is to Try to parallel the generators manually to eliminate the cause if whether the fault is coming from the pms card or on the generator side. I hope these will help
@sikandermanhas72222 жыл бұрын
Adjust gen no 3 voltage from potentiometer to adjust towards required amperage value
@00hate002 жыл бұрын
What do I need to work on a ship? I'm a college graduate. 2 yrs refrigeration mechanics. I do commercial refrigeration. What do I need to do to work on a refrigeration shipping vessel like this?
@shitake192 жыл бұрын
You American?
@00hate002 жыл бұрын
@@shitake19 yes
@lightfdar2 жыл бұрын
This is your new intro... boss!!
@vedatinal24712 жыл бұрын
First of all, thank you very much for your information. I am working as a chief engineer on a ship. There are 4 690 volt generators on our ship. When we parallelize the generators, the generator number 3 gives load too high deviation alarm. How we can solve this problem. I would be glad if you help.
@sikandermanhas72222 жыл бұрын
Chief also check the power factor of gen no. 3 which will be less compared to the other paralleled gen. If so then u only need to adjust the voltage of gen no 3 that too reduce the voltage upto the level that power factors of both gen. running parallel come same... Ur amperes will also get adjusted
@r-ainjel47352 жыл бұрын
lecky ano name ni Mayor po? parang nakasama ko siya dati sa Senator po.
@rouqeann2 жыл бұрын
Wass up lofs
@rinak59322 жыл бұрын
Kuya Lecky...so glad to know you are doing great!^ I have a question about daikin‘s keypad controller malfunction. Can it be fixed without changing the whole thing? Thanks!^
@PakPinoy2 жыл бұрын
Ang Ganda po nya!!! Daughter nyo po sya?
@jefranco06342 жыл бұрын
Yung girl po na crew ano po yung role nya? Gusto ko po ring makasampa nang barko, graduate BSEE at REE licensed, kaso babae po ako. So di ko alam tutuloy ko ba. Sana masagot nyo po. Thank you
@vedatinal24712 жыл бұрын
I changed the current transformers in generator number 3. I changed the syncronoscope. I changed the screen. I changed the cotroller. Unfortunately I couldn't find a solution. please help.
@MosaicTK2 жыл бұрын
I thinks its coz other generators are not taking load and this alarm coming. Did u try to overall the generators or clean turbocharger?
@ralpamomas86882 жыл бұрын
Good day sir, I am an aspiring ETO. Gusto ko sana makabarko as eto pwedi po ba magtanong sainyo sa messenger? Pa help po hehe sana po matulungan