Relay setting calculation|Restricted Earth Fault Protection relay Setting Part-2|KNEE POINT VOLTAGE

  Рет қаралды 31,281

ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE

ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE

Күн бұрын

PART-2
KNEE POINT VOLTAGE, RELAY PICK UP AND STABILIZING RESISTOR CALCULATION FOR REF RELAY SETTING
Two things I should rectify first.
1. By mistake I have said percentage impedance of 8.25 ohm, but percentage impedance is expressed in percentage only, and not by ohm. That has been an unconscious mistake.
2. The formula for calculating the fault current is not completely visible. It shall be (2500/(1.732*0.433*0.0825))
In this video we have explained calculation of knee point voltage, pick up, stabilizing resistor for restricted earth fault relay setting calculation. These calculations are required for successful implementation of Restricted Earth fault protection of alternator and Transformer.
Restricted Earth Fault Protection is also known as differential earth fault protection. It is basically earth fault protection but works on differential relay principle.
Restricted Earth Fault Protection is used to detect earth fault inside a machine in general.
#ElectricalTechnologyAndIndustrialPractice,
#ElectricalEngineering, #ElectricalTechnology,
#RelaySettingCalculation, #REFRelaySetting, #RestrictedEarthFaultProtection
#REF
The explanation given in the video is applicable for all the below mentioned topic.
1. REF Relay setting
2. Restricted Earth Fault relay setting
3. Protection against internal earth fault
4. REF Relay setting calculation.
5. How to calculate settings for restricted earth fault relays
6. Restricted Earth Fault Protection philosophy of relay setting
2. How restricted Earth Fault Protection relay setting is done
3. REF relay setting principle
4. Differential earth fault Protection setting
5. Setting calculation of restricted Earth Fault Protection relay
6. REF relay setting
7. Restricted Earth Fault Protection CT selection
8. REF Protection of Alternator
9. REF protection of transformer
10. Knee point voltage calculation
11. stabilizing resistor calculation
12. high impedance restricted earth fault relay setting
Please visit our website
electricaltech...
Please like, share, comment and subscribe our channel.

Пікірлер: 62
@rameshtripathy5978
@rameshtripathy5978 5 жыл бұрын
It is very much useful for the commissioning engineers !
@priyal5354
@priyal5354 6 ай бұрын
Vs =60V will appear across secondary terminals of CT, right? How to choose Is?
@kulkarnir93
@kulkarnir93 3 жыл бұрын
Sir, Thanks for giving such good knowledge about REF protection. How RCT of 4 nos CTs i.e. 3 phase CTs & 1 neutral CT. Also explain the exact method of calculating wire connected with the 4 CTs.
@yokeleetan8525
@yokeleetan8525 Жыл бұрын
It seems from your calculation Vs is the voltage across the relay and stabilising resistor.
@thetruelegend2502
@thetruelegend2502 5 жыл бұрын
Thanks sir, Crystal clear to understand
@shantanumajhi5408
@shantanumajhi5408 3 жыл бұрын
Very Useful
@elavarashanrajesh6560
@elavarashanrajesh6560 Жыл бұрын
Very usefull sir thank u very much ❤❤❤❤❤
@surendrakverma555
@surendrakverma555 2 жыл бұрын
Very good. Thanks 🙏🙏🙏🙏
@mdborhan2690
@mdborhan2690 3 жыл бұрын
very nice
@jitendradubey3682
@jitendradubey3682 4 жыл бұрын
Thanks sir.... Very informative 😊😊😊🙏🙏🙏
@patelsiddharth7698
@patelsiddharth7698 Жыл бұрын
Sir can we use REF protection for 1MVA transformer?
@jppatnaik2240
@jppatnaik2240 3 жыл бұрын
For Each CT whether we consider of One CT (or) all 3 CT ? ( RCT )
@raviteja-bf8vj
@raviteja-bf8vj Ай бұрын
Say for suppose if the fault has occurred within the Restricted zone and only N CT is seeing the current. In that case say 10 Amps of secondary current has appeared. For that to drive through REF relay coil, a specific voltage will be developed. Since CT is a constant current source if primary current is constant, voltage across CT secondary will vary based on VA burden. If 700 Ohms is being connected as Rstab then to drive 10 Amps of current and 700 Ohms of load, a voltage of 7kV is required. Which in that case metrosil will operate and bypass that as surge. I was not able to understand in normal conditions, when the Rstab is connected, how the current is being flown through relay citing heavy burden.
@sridhar3377
@sridhar3377 2 жыл бұрын
Is there any video of this calculation also done for the condition of NCT with resistively grounded??
@zahidulislam2458
@zahidulislam2458 3 жыл бұрын
Nice
@hzbajlanihzbajlani6699
@hzbajlanihzbajlani6699 3 жыл бұрын
We have a factory that requires 6 MVA electric power , Can we use one large transformer and limit the fault current with NGR? our transformer is 11/0.4 KV
@hplar2972
@hplar2972 3 жыл бұрын
Hi,just want to ask you is it earth that was intalled at MSB also the same funtioning?
@hplar2972
@hplar2972 3 жыл бұрын
I mean earth fault relay
@wongsabarchannel1335
@wongsabarchannel1335 Жыл бұрын
Do you have Low Impedance REF Calculation Video?
@bristykhatun2404
@bristykhatun2404 3 жыл бұрын
thinks sir vary good job
@learnbyshiva725
@learnbyshiva725 4 жыл бұрын
Thanks sir very good job
@CartoonwonderlandEdu
@CartoonwonderlandEdu 5 жыл бұрын
Love u yar ur vedios are so good to understand
@rakeshnanda9506
@rakeshnanda9506 6 жыл бұрын
Nyc explanation sir
@jyothiyecherla7964
@jyothiyecherla7964 4 жыл бұрын
Here RCT Value means combination of 4 cts or one ct?
@hosseinshabaniroshan8174
@hosseinshabaniroshan8174 2 жыл бұрын
Hi.I want to know exactly how to draw the characteristics of this relay...? Do the differential current and bias current ,which are the necessary characteristics for this relay , come from the normal state of the relay or from fault condition?
@ajithomas8342
@ajithomas8342 Жыл бұрын
🎉
@shankhachongder6065
@shankhachongder6065 5 жыл бұрын
Thank you for the video sir
@balakabimuki2023
@balakabimuki2023 4 жыл бұрын
Hello sir, After calculated VS , why should we use the formula of CT Vnee>2Vs?? and here this video you increased the voltage from 120 to 400?????and you told that we can use 650V also..how to choose the maximum voltage ???
@pceprojectspvt.ltd.6183
@pceprojectspvt.ltd.6183 4 жыл бұрын
In case the earth fault is inside the zone , how to ensure that insertion of stabilising resistor will not lower the fault current below the pick-up setting of the relay
@yctsang6561
@yctsang6561 4 жыл бұрын
I have the same doubt
@shashah769
@shashah769 2 жыл бұрын
😍😊
@mdborhun15
@mdborhun15 3 жыл бұрын
Wow
@thinkseeeatthroughvickus4555
@thinkseeeatthroughvickus4555 4 жыл бұрын
Please make a video on - what all relays can be connected from same CT, and where CTs to be installed in case of transformer protection, bus bar protection, so that it wii give an idea how many CTs required
@thinkseeeatthroughvickus4555
@thinkseeeatthroughvickus4555 4 жыл бұрын
Can you do a video on PS or PX class CT sizing?
@ranjan1436
@ranjan1436 5 жыл бұрын
pls make a video on knee point voltage. so far it is fantastic.
@electricaltechnologyandind5335
@electricaltechnologyandind5335 5 жыл бұрын
There is already a voltage on knee point voltage selection. Check the restricted Earth fault protection series
@wary8113
@wary8113 3 жыл бұрын
WHICH CT RESISTANCE TO BE TAKEN IN CALCULATION? 3 CT OF LINE & 1nct is in parallel?
@ManojkumarSahoo_electrical
@ManojkumarSahoo_electrical 3 жыл бұрын
Sir, How to calculate the power rating (Wattage) of stabilizing Resistor for REF relay.
@ABHAYSINGH-um3wc
@ABHAYSINGH-um3wc 4 жыл бұрын
excellent but please make the more easy those concepts
@nageshpawar2455
@nageshpawar2455 4 жыл бұрын
THANK U VERY MUCH SIR....
@kameshwarmehta5507
@kameshwarmehta5507 3 жыл бұрын
Fault current calculation how.....
@ashiqurrhman292
@ashiqurrhman292 3 жыл бұрын
Nc
@ashutoshpokhriyal1020
@ashutoshpokhriyal1020 5 жыл бұрын
Sir please share distance protection setting calculations
@jamesowusu-ansah595
@jamesowusu-ansah595 4 жыл бұрын
Sir please, by safely choosing the the knee point of the CT to be twice Vs...Then it's safe to say the LCT's won't get saturated for high value external faults right?
@electricaltechnologyandind5335
@electricaltechnologyandind5335 4 жыл бұрын
Yes. That is one of the check point of REF setting
@jamesowusu-ansah595
@jamesowusu-ansah595 4 жыл бұрын
@@electricaltechnologyandind5335 So if it's unlikely to enter saturation by safely selecting your CT knee point, then i really don't see the need of a stabilising resistor Also, won't the stabilising resistor reduce the current in the event of a ground fault within the protected zone, hence, the relay might not operate?
@electricaltechnologyandind5335
@electricaltechnologyandind5335 4 жыл бұрын
When vs has occurred that will drive current through relay. For that stabilizing resistance is given. Please watch the video again
@jamesowusu-ansah595
@jamesowusu-ansah595 4 жыл бұрын
@@electricaltechnologyandind5335 But Vs only occurs when the CT'S get saturated right?
@electricaltechnologyandind5335
@electricaltechnologyandind5335 4 жыл бұрын
No. When current flows.
@neerajpiplani185
@neerajpiplani185 4 жыл бұрын
Wonderful explanation. Could you please explain why knee votage should be atleast twice Vs
@shujaatkhan6637
@shujaatkhan6637 4 жыл бұрын
Dear Sir, Can you please make a video on Knee point voltage
@mdronvai4405
@mdronvai4405 3 жыл бұрын
❤️🥰😏
@naimulislam41
@naimulislam41 3 жыл бұрын
nc
@akhilsm6840
@akhilsm6840 4 жыл бұрын
Why the CT saturated even though the CT knee point voltage is very high
@electricaltechnologyandind5335
@electricaltechnologyandind5335 4 жыл бұрын
Normal protection relay doesn't have high knee point voltage
@dilipsahusahu680
@dilipsahusahu680 4 жыл бұрын
Please please please Hindi sir
@musicvideo1566
@musicvideo1566 3 жыл бұрын
very good
@sujonshahofficial2572
@sujonshahofficial2572 3 жыл бұрын
Wow
Relay setting calculation|Restricted Earth Fault Protection relay Setting Part-1|CT selection
12:39
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 39 М.
Quilt Challenge, No Skills, Just Luck#Funnyfamily #Partygames #Funny
00:32
Family Games Media
Рет қаралды 55 МЛН
小丑教训坏蛋 #小丑 #天使 #shorts
00:49
好人小丑
Рет қаралды 54 МЛН
Neutral Grounding Resistor Sizing and application|Restricted Earth Fault Current
12:54
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 62 М.
Restricted Earth Fault Protection|REF relay working principle
11:56
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 149 М.
CT KNEE POINT VOLTAGE | COMPLETE ONLINE TRAINING | SUBSTATION DESIGN COURSE | IETP | +919354439397 |
2:21:17
Institute of Engineering Training and Placement
Рет қаралды 2,4 М.
REF(Restricted Earth Fault) Protection || Hindi
12:39
Insight Tecs
Рет қаралды 18 М.
IDMT Relay setting calculation|TIME GRADATION|RELAY CO-ORDINATION
14:05
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 40 М.
Transformer Insights: Will Secondary Load Impact the Primary Current?
13:34
Gaurav J - TheElectricalGuy
Рет қаралды 9 М.