Bad Oil Sensor Tripping York Air Cooled Chiller HVAC

  Рет қаралды 16,480

HVACTIME

HVACTIME

2 жыл бұрын

Had circuit 1 oil sensor fail causing it to trip a safety lockout. York chillers are real common to have sensor failure but the oil sensor usually holds up pretty good. Recovery on air cooled chillers is usually a pain due to lack of low point to recover from.
Tool Store
geni.us/HVACTIME
hvactimetx.com
You can contact me at Hvactimetx@gmail.com
Support the channel through, venmo.com/code?user_id=316085...
Zelle @ Hvactimetx@gmail.com
As an Amazon Associate I earn from qualifying purchases

Пікірлер: 29
@henrywilliams5093
@henrywilliams5093 Жыл бұрын
You are an excellent teacher sir. It's much appreciative of how you share your knowledge
@Eddy63
@Eddy63 2 жыл бұрын
Interesting job ... Thx for sharing ...
@Stevehevessy
@Stevehevessy 2 жыл бұрын
I couldn’t agree with you more about York adding a recovery valve,I changed a compressor on a yvaa and had to pull the liquid from the eductor line filter
@kc5vgw
@kc5vgw Жыл бұрын
Once you have the gas out. Solder in a few ball valves with flare ports. Also makes life easy when replacing the drier. Turns it into a 20 minute job.
@realestateservicessaleshea99
@realestateservicessaleshea99 2 жыл бұрын
Thanks for the videos!!! Nice work! 🥃🥃🍺🍺🍺🍿🎯 Stay safe. Retired (werk'n)keyboard super tech. Wear your safety glasses!
@salvadorbernardino7558
@salvadorbernardino7558 2 жыл бұрын
Excellent
@mansourghadhban236
@mansourghadhban236 2 жыл бұрын
thnxs more Nd more from Iraq
@randomrefrigeration4564
@randomrefrigeration4564 2 жыл бұрын
You can use a water hose gasket for that adapter works fine especially in a pinch
@northernsupertramp7390
@northernsupertramp7390 2 жыл бұрын
O-ring works just as well too.
@matthewclemons1574
@matthewclemons1574 2 жыл бұрын
According to sporlan you shouldn’t replace the gasket unless it’s damaged.
@throttlebottle5906
@throttlebottle5906 2 жыл бұрын
often it's cheaper to get a whole valve assembly, just for the solenoid coil or the whole assembly may be all that was available. keep the valve as spare on truck or document and leave it inside the machine. what mental genius designed the system so it needed a full recovery to change an oil temperature sensor? I guess they were too cheap to implement a brass or copper probe well.
@kc5vgw
@kc5vgw Жыл бұрын
When the stem leaks, and that’s common. There is a part number for a tube enclosure kit. Better than replacing a whole valve. Also locking your coils into place with a dab of silicone between the coil and the valve body will slow it down on rubbing and the stems will last 5-10 times longer.
@mikolmarisga3893
@mikolmarisga3893 2 жыл бұрын
Hi sir how to troubleshoot chiller Hitachi always tripping
@nickyengle9668
@nickyengle9668 2 жыл бұрын
The only problem w nylok on the drier cap is good luck to the next guy during drier replacement. He will scrape and chip the gasket seat w his control screw driver during gaslet removal.
@HVACTIME
@HVACTIME 2 жыл бұрын
Been using Nylog for years and never once had it do that. You sure your not getting it confused with something else?
@kc5vgw
@kc5vgw Жыл бұрын
Been working on these machines for over 15 years and have never used Nylog on anything. Been working on chillers for 30. I can count on 1 hand how many caps have leaked after changing the cores. I do not ever use sealants on driers ever. Having a lid to seal up that it has to be broke loose is inherently dangerous.
@richardharmon874
@richardharmon874 2 жыл бұрын
Need to get an old school reclaim machine. Those yellow jacket things are junk.my old reclaim machine is big and heavy but reclaims 4 times faster then the yellow junk with the undersized condenser.
@stueyknuxx
@stueyknuxx 2 жыл бұрын
its an Appion recovery unit and not Yellow Jacket, and the Appion goes good man ! Why the rush ? Getting paid by the hour 😁
@richardharmon874
@richardharmon874 2 жыл бұрын
@@stueyknuxx when you have to reclaim a freezer condenser on roof before crane shows up,job is quoted i not trying to play games i want that reclaimed as fast as possible.
@stueyknuxx
@stueyknuxx 2 жыл бұрын
@@richardharmon874 he wasn't recovering a freezer condenser before a crane though was he ;)
@georgev1029
@georgev1029 Ай бұрын
What is the purpose of manually opening and closing drain and feed valve 0-100?
@HVACTIME
@HVACTIME Ай бұрын
To calibrate manually, check operation, or recovery/evacuate
@redman42s7
@redman42s7 2 жыл бұрын
Some BAS/EMS/ networking training would be cool 😎..
@HVACTIME
@HVACTIME 2 жыл бұрын
kzbin.info/www/bejne/l3u5ZZ2gpNCcoLs kzbin.info/www/bejne/hGTJoKttlNyZp5I
@redman42s7
@redman42s7 2 жыл бұрын
👍
@brianwolf9860
@brianwolf9860 2 жыл бұрын
Oil pressure should always be 5-7 lbs from discharge.
@kc5vgw
@kc5vgw Жыл бұрын
Why are you pulling the charge?. If Your replacing the oil temp sensor. Close the iso valves and push the charge into the other side side of the valves. Takes 1 hr tops to get the gas out of that part of the circuit. Usually 20-30 min. Putting 2 days on for a oil temp sensor replace is way out of the norm.
@HVACTIME
@HVACTIME Жыл бұрын
You don't have an access port on the liquid line to do that on this one when the valve is front seated. There are ports on the discharge line but I choose not to pump liquid into the discharge side. This is a YCIV.
Chiller Down Tripping Low Pressure York Air Cooled Chiller
22:19
System Crash takes out Chiller
20:25
HVACTIME
Рет қаралды 17 М.
- А что в креме? - Это кАкАооо! #КондитерДети
00:24
Телеканал ПЯТНИЦА
Рет қаралды 7 МЛН
WHAT’S THAT?
00:27
Natan por Aí
Рет қаралды 12 МЛН
Low Oil Troubleshoot RTAA Chiller
11:24
HVACTIME
Рет қаралды 14 М.
Tripping Low Pressure York Air Cooled Chiller Down
26:01
HVACTIME
Рет қаралды 73 М.
Trane RTAC Pt. 2 - Filter Drier, Vacuum, Recharge
23:33
DFW HVAC
Рет қаралды 10 М.
York Chiller Refrigeration Cycle - YCIV & YVAA AC
30:38
HVACTIME
Рет қаралды 25 М.
Trane RTAC Leak Repair + Oil Filter Part 1
19:57
DFW HVAC
Рет қаралды 11 М.
Troubleshooting a chiller issue today
20:39
Curious HVAC Guy
Рет қаралды 23 М.
- А что в креме? - Это кАкАооо! #КондитерДети
00:24
Телеканал ПЯТНИЦА
Рет қаралды 7 МЛН