Level up your chiller career! HVACTIME Chiller Academy offers interactive courses, that can go in the field with you to learn, designed by chiller veteran to guide you through complex chiller systems. Learn at your own pace and gain the expertise to thrive. Limited-time Early Bird Discount available! chilleracademy.com
@briancoulomb Жыл бұрын
Orings are always a challenge on equipment. I’ve had similar problems occur several times. No leaks, makes a non related repair, pressurize and leak check with no issues. Pull an hold a vacuum and then add the charge correctly, only to find a large leak on an oring. The pressurizing and depressurization makes orings move and leak. It is a major kick in the pants. I have gone to the extent of replacing orings on non related components with the concern of this happening.
@ericwagner60872 жыл бұрын
i use a site glass and ball valve arrangement at the recovery cylinder so I can visually see liquid flow and the valves make swapping cylinders much easier.
@HVACTIME2 жыл бұрын
Its a good method. Just havent created the habit.
@dmc3572 жыл бұрын
I usually use a flared sight glass when I’m pulling liquid. As far as the oil leak goes that oil drain line is a weird spot for a leak to develop. Sucks dropping that oil sump to change out that o ring. Looking forward to the other videos to see how you guys make out.
@screwdriver_bandit9 ай бұрын
I’m just starting learning chillers as a long time commercial refer guy. Punching tubes and maintenance with lead guys. I’m going to watch your channel and learn as much as I can. My boss says he wants me to move to the next level as a journeyman tech im glad I found your channel.
@derrickenbuenosaires2 жыл бұрын
Fun stuff ! At the end of the day it's just a machine, you do what you can, not anyone's fault. Ones reaction to the problem is important, then from there come to a conclusion for a solution to the customer. Just another day.
@michaelgonzalez18242 жыл бұрын
I always use a sight glass on my liquid recovery line so I know when I’m done recovering liquid
@HVACTIME2 жыл бұрын
Its a good idea, not something I've made the time for up to this point. Almost have several times.
@czechmate69162 жыл бұрын
Yes Michael I did the same thing and it worked for me.
@denuslevine2105 ай бұрын
Wheres the alarm detector in the plant room? Required in u.k Part of fgas. Luv your vids your a true guru in your trade
@HVACChillin2 жыл бұрын
I had the same exact leak. Just didn’t lose that much refrigerant. Such a pain in the ass oRing to replace, man I feel your pain. We have real good days, then we have bad days. Wonder why we are in this trade. Lol. It all works itself out. I’m sure the customer will understand it’s out of your hands. It would help if you put a liquid line site glass when your push/pulling.
@brianb60932 жыл бұрын
Was the stand-by lube enabled? That would explain why it was it was pumping oil every 24 hours. I’m sure it’s been said already but get a flared sight glass in the pull liquid line. Helps on the push back in too.
@thesilentonevictor2 жыл бұрын
That was good catch at list you can fix it right away then have it back up running customer should be happy to have you on their side
@HVACTIME2 жыл бұрын
Definitely better now than later
@Adcd572 жыл бұрын
These things happen, we bring it up to the customer and go from there.
@EverythingHVACR2 жыл бұрын
That's a long rough day. Great video, keep up the good work 💪
@throttlebottle59062 жыл бұрын
it looks like the "acceleration knob" is more or less the "gas ballast" knob. probably wont make much difference until the inlet pressure is about 35psi or lower. that's my take without seeing one/internal assembly.
@CHOMAHOMA2 жыл бұрын
Good video. Handling big quantities there. Thank you for sharing.
@dar94332 жыл бұрын
When pulling refrigerant from the bottom of evaporators on different chillers, do you ever expirence compressor oil being removed with the liquid refrigerant ??
@HVACTIME2 жыл бұрын
Yes, definitely happens. Usually pulls back out when charging system.
@SombraLocs2 жыл бұрын
You usually distill the liquid refrigerant and pump the oil or let it suck when you're pulling a vacuum on the chiller.
@dar94332 жыл бұрын
So long as the dip tube reaches to the bottom of tank, or turn upside down, hard to do with big full cylinders... On another note, do you ever do push pull using the chillers compressor, until the chiller trips on low pressure, or liquid refrigerant no longer available.. I've done it a few times, works a treat, just watch the static build up on the tank....😄😩⚡️⚡️
@bobrumpf2576 Жыл бұрын
no sniffer (monitor ) on the job? maybe you can sell them on it?
@fkdeazevedo Жыл бұрын
Should you not be pulling from cond?
@throttlebottle59062 жыл бұрын
ahh, the old cannot move liquid if there isn't any problem. DOH!
@thelol17592 жыл бұрын
Man this is such an interesting field, thanks for making these videos!
@reyrodriguez10052 жыл бұрын
Did you build that brass kit, or did you buy it?
@HVACTIME2 жыл бұрын
Built it. Its just a cheap tackel box with an assortment of stuff.
@reyrodriguez10052 жыл бұрын
Love your videos man. I’m a couple years into air cooled and water cooled chillers, mostly Yorks.
@jweschler Жыл бұрын
1/4” discharge hose on recovery for chiller??? I use 1/2” minimum.
@billthetaxcollector45212 жыл бұрын
Have you ever work on refrigeration rack ?
@HVACTIME2 жыл бұрын
No, Ive done walk in's but not rack systems.
@samalmo2 жыл бұрын
This video made me realize how much I love working light commercial HVACr (25-ton or less) 😏
@politiciansthrowstones2 жыл бұрын
But the real money is on big equipment unless you are installing yourself
@Lewdacris9162 жыл бұрын
Thats crazy the system lost a thousand pounds of liquid refrigerant, how much is that gonna cost?
@coldfinger459sub02 жыл бұрын
When I see your bad days. I have nothing to compare with on my little bad days.
@czechmate69162 жыл бұрын
Shit happens but why me?? That’s what I always asked 🤣 I hope your luck changes after this. 🤞🤞
@miket1209 Жыл бұрын
Damn right buddy I bet that machine was tight as a tick until miraculously it gave up the ghost with y’all in the room recovering gas then it blew its charge out that leak y’all didn’t notice tilll now.
@1234youbrianАй бұрын
Is your watch a smart watch
@HVACTIMEАй бұрын
Yes, Samsung
@1234youbrianАй бұрын
@ can you send some info on the model and where you got it . Appreciate it I been looking for one like that
@thegun982 жыл бұрын
Man that sucks so bad.
@HVACTIME2 жыл бұрын
Never fun giving that news
@gantmj7 ай бұрын
Why does that thing look like it has bad cellulite?
@michaelsmith90342 жыл бұрын
Did you learn your trade mostly through school or on the job?
@steveschroeder18822 жыл бұрын
I thought that only happens to me
@JackDavidson-ov2tf2 жыл бұрын
Good catch. Quick question how long would it take to recover 1300 to 1400 lbs from that YK?
@HVACTIME2 жыл бұрын
Using a recovery like this one and push pull. I expect it would have done so in about 6 hours. When we have hired recovery companies in the past with their machines not using push pull it took 8 to 10hrs
@JackDavidson-ov2tf2 жыл бұрын
@@HVACTIME okay got it thanks. Im thinking about purchasing this Navac recovery machine. First time hearing about it when I seen it on your clip. It looks like it does the job and saves time
@HVACTIME2 жыл бұрын
@@JackDavidson-ov2tf it's a incredible machine. You can get 8% off at TruTech Tools with HVACTIME
@sterlingarcher462 жыл бұрын
Something tells me that Somehow the customer is gonna find a way to put the blame on you lot , like : " how come you didn't catch the leak last time you were here huh ? " .Just to make the day even better 😤
@HVACTIME2 жыл бұрын
I presented it in such a way to not open that door. All worked out
@SupremeRuleroftheWorld2 жыл бұрын
@@HVACTIME in my country we call that conversation skill "to make someone happy with a dead bird".
@crabmansteve68442 жыл бұрын
@@HVACTIME My man! I'm in a different trade, but the work is the same (i just put my wrenches on different machines than you), I felt like I really elevated myself as a technician when I mastered the art of working the customer.
@hvacpro852 жыл бұрын
Was the machine powered completely off for that few months of shutdown, or was it just disabled?
@HVACTIME2 жыл бұрын
Just disabled
@michaelgonzalez18242 жыл бұрын
Just finished watching the rest of the video, 😳
@nicholaslandolina Жыл бұрын
Once moistened gaskets loose moisture they are done
@blake_edwards2 жыл бұрын
Woops. Could that have been a dry rot failure?
@HVACTIME2 жыл бұрын
No, the next video next week will show why it happened
@royamberg91772 жыл бұрын
Fiasco. The normal
@steelzmb42622 жыл бұрын
You learn something new everyday
@jasonjohnsonHVAC2 жыл бұрын
Happy Thanksgiving to you and the family
@HVACTIME2 жыл бұрын
You too buddy!
@jeffreyrex82322 жыл бұрын
Those Orings are not ideal. Bit of a faff to change but easy enough. The coughing on start up was giving the low charge game away. Really sorry to see this my man.
@ayoutubewatcher70092 жыл бұрын
glad I don't work on chillers anymore
@HVACTIME2 жыл бұрын
Why did you stop?
@kc5vgw2 жыл бұрын
Try not flowing water until you go into vapor mode. Push pull doesn’t work well when there is cold water going thru the barrel. The freeze danger only occurs during vapor. The whole problem your having is because the recovery unit will not build pressure because it’s condensing instead of pushing.
@HVACTIME2 жыл бұрын
How does vapor cause the pipes to freeze?
@politiciansthrowstones2 жыл бұрын
It's liquid that will cause freeze you can put vapor to saturation and then change to liquid with water flow. Plus warm the tank to help the process
@cdoleoj1 Жыл бұрын
Its is incredible how many techs in this industry do not understand how push/pull works or the physics of it. NO you do not need to flow water thru the chiller when you do a push and pull correctly as the pressure in the chiller is not changing, you are just using vapor pressure to push out liquid, since your pressure inside does not change your saturated wont change, there is no significant refrigerant evaporation when push pulling, there is absolutely no risk of freezing, I understand some techs want to be on the safe side, but when you truly understand what you are doing you know your are on the safe side. When you stopped adding liquid to your recovery tank that was your first red flag, that gave away the game, you were done recovering liquid, you had lost the charge. I have been doing this for 24 years now, lost count on how many chillers I have had to pull refrigerant from, always push/pulled, never have I ever turned ON a water pump. Once you are certain no liquid remains inside chiller, you just pull the vapor and that is it. Always use a sight glass on your liquid line to tank and always check for low points that can trap liquid. No need to turn ON a pump and having to flow water thru an OFF chiller making the ON chiller work harder.
@cdoleoj1 Жыл бұрын
@kc5vgw you are so wrong is actually scary, have you had any professional training or work experience?
@CryptoAbe2 жыл бұрын
What's sad is this is the most extreme work you can do. No one today really wants to do this type of work. Residential is almost dead and pay rates are exceeding commercial pay. Commercial paid techs are undervalued but dieing breed.
@HVACTIME2 жыл бұрын
Commercial guys in my area can make double what most residential guys do. But not enough of us doing it anymore either.
@qomco2 жыл бұрын
Depends. Residential can make commission. Id love to go commercial some day when I get smart
@HVACTIME2 жыл бұрын
@@qomco residential can make more at lower levels but once your an experienced tech there is more money in heavy commercial. There is a big education gap is part of the problem. A senior residential guy is an entry tech for the heavy commercial side.
@SAAJ60002 жыл бұрын
No worries. If you lose 100pounds of 134a that only 200.000 tons of co2 you let out to the atmosphere
@SAAJ60002 жыл бұрын
Oh sorry you said 1000 pounds? That’s only 1.400.000 million kg then. My apologies
@SAAJ60002 жыл бұрын
US always leading the way
@SAAJ60002 жыл бұрын
Ohhhh wait. Gwp of r134a is 1430. So if you let 1 kg out it’s equal to 1,4 tons of co2. I’m sorry
@SAAJ60002 жыл бұрын
Mtt how about mtt to your children’s children
@Thermoelectric72 жыл бұрын
@@SAAJ6000 it's not like the leak was intentional. He's a technician, he fixes problems. Go lobby politicians about refrigerants instead. Plenty of folks have drums and drums of old R12 just sitting around that will do way more damage.