TOP 10 Gas Furnace, PRESSURE SWITCH Error Code Problems!

  Рет қаралды 205,249

AC Service Tech LLC

AC Service Tech LLC

Күн бұрын

Пікірлер: 136
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Tool List- www.amazon.com/shop/acservicetech Support- www.patreon.com/acservicetech For those that are looking for the tools used in the videos: (Linked Below) UEI Digital Dual Manometer- amzn.to/2CWC6BD Fieldpiece SDMN6 Dual Pressure Testing Manometer with Pump-amzn.to/2jyK5Ka UEI DL479 Multimeter with temp sensor- amzn.to/2jtsUbJ 3/16" x 3/16" x 3/16" brass barbed tee- amzn.to/2INSRhQ 1/8" NPTF x 3/16" barb fitting for reading wc pressure- amzn.to/2G563Bq Supco Universal Adjustable Pressure Switch -.01wc -10.0wc amzn.to/2G1y0py Supco Magnet Jumpers amzn.to/2gS4h6z 2 pairs of alligator clips- amzn.to/2CtIL5z Here is the Link for the Yellow Jacket Refrigerant Manifold Gauge Set used in the videos amzn.to/2aenwTq Here is a link to Refrigerant hoses with valves used in the videos amzn.to/2aBumVI Here is a link for RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn Here is the link to the Appion Valve Core Removal Tool- amzn.to/2uYr8WL Here is the link for the Ratcheting Service Wrench amzn.to/2dGV4Nh Here is the link to the CPS Vacuum Micron Gauge- amzn.to/2v1nM3O Here is the Link to the Appion Blue 3/8" to 1/4" Vacuum Hose- amzn.to/2uYlVyc Here is the Link to the Appion Red 3/8" to 1/4" Vacuum Hose- amzn.to/2uYg6Ro Here is the link to the Yellow Jacket 1/4" by 1/4" heavy duty hose straight- amzn.to/2umtcod Here is the link to the pack of 25 C&D valve cores- amzn.to/2J1lurm Here is the link for the C&D Valve Core Wrench, Container, and 3 valve cores- amzn.to/2EVGkps Other tool links can be found in the video description section. Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal- www.amazon.com/shop/acservicetech
@FLOUNDERGUY
@FLOUNDERGUY Жыл бұрын
Great video. I worked on a pressure error for several hours over three days. After watching the video a second time, I thought I should check for a hole in the pressure switch line. The tube was pliable, semi opaque and only about 5 inches long. It looked to be in good shape. I could hear the diaphragm open and closed when I gently blew or sucked on the tube. I checked the continuity on the electrical prongs when I sucked, then blew. The switch was opening and closing. Then I looked very closely for a hole in the vacuum line. I didn’t find one, but I did finally notice a very small, light colored, dead insect in the line. I could barely see it. That was the problem!
@m.muhaiminkhan6940
@m.muhaiminkhan6940 3 жыл бұрын
I can’t express enough how good this video is and how well you explained everything. Thank you so much.
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
Glad it was helpful!
@joonkim5863
@joonkim5863 3 жыл бұрын
I repeatedly watch your video because I could learn a lot as a beginner. I was much frustrated in practice but nobody explained like Craig.
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
Great to hear!
@SemperFiBiologist
@SemperFiBiologist 11 ай бұрын
I’ve spent the past three years trying to find the cause of an intermittent error 31. This video was amazing. Gave me some more things to check.
@Autiger6871
@Autiger6871 2 жыл бұрын
My carrier high efficiency furnace Tstat showed it was heating but no heat blowing cold air. A small black tube had come off on one end. Plugged the tube back in and now everything worked. Thanks for all of your videos. I have been able to repair my furnace and AC by watching these videos.
@Trevormartens
@Trevormartens 2 жыл бұрын
Condensation trap!! Woke up to cold house this morning - had this repaired with time for coffee before work. Thanks so much!
@nianlisang8226
@nianlisang8226 2 жыл бұрын
The best one I have watched! Comprehensively discussed all possible faults. Some other videos are misleading by oversimplifying the error code.
@bradymcneese9388
@bradymcneese9388 Жыл бұрын
Nicely explained. It helped me to figure out my issue. I live in KY. -7 degrees right now. Dealing with the snowstorm that most of the country just got pounded by. Was throwing the 31 code. I watched many videos and was trying different things. Even blew through my pressure switch tubes which fixed it last time. Ended up that icy snow had gathered in my intake for induction motor blocking the downward pointing pvc pipe. Thanks for helping my brain to realize the issue. Merry Christmas!
@whitesheatingairappliancer7101
@whitesheatingairappliancer7101 5 жыл бұрын
Another great video. Your students should be grateful for having a intellectual teacher.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks a lot Ron!
@ravaginggoatman
@ravaginggoatman 2 жыл бұрын
Very good video, but another cause could be wind! I get code 31 every time we have high wind and have been trying to find a way to prevent it.
@romankhochay122
@romankhochay122 9 ай бұрын
This is the best video I have ever seen on pswitch.
@justopeners
@justopeners 4 жыл бұрын
Number 8 , was my problem. I cleared out that port ,and now the furnace is working. It's almost like a calcification that build-up in the port yes ? I have a 80% furnace . Im a diy guy and Thanks Man!
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thanks Just Openers!
@jaimegutierrez9930
@jaimegutierrez9930 9 ай бұрын
Great videos im leraning so much plus im reading alot of HVAC and im learning so much with your videos, i bought your 2 books you have great books , you should make one on furnaces i would buy it so fast because your 2 first books are amazing.
@MrPickledip
@MrPickledip 2 жыл бұрын
This dude is a legend 🙌 he has helped me in the field multiple times ❤️
@riverratfishing
@riverratfishing Жыл бұрын
Had this issue about a month ago. It ended up being the fresh air pipe. The fresh air connected to the exhaust and I put a piece of screen over the exhaust because a bird had built a nest. Well the fresh air was pull heat because of screen. So I disconnected the 2 at the "Y" joint and ran fresh air separate. No more issues. Thanks for all of your videos
@stellarheatingcooling2689
@stellarheatingcooling2689 5 жыл бұрын
Hi I just wanna tell you that your are the best and you have the best video and I am a big fan and thank you for all what you do
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thank you very much Stellar!
@stellarheatingcooling2689
@stellarheatingcooling2689 5 жыл бұрын
You welcome I have a question what will happen if I install bigger compressor in a walking cooler or a air conditioner thank you
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Though I haven't had a circumstance where I had to install a larger compressor for the system, I would just say, that it won't work with a fixed orifice but with a txv the low side should work at normal pressures. Remember that a larger compressor will need more refrigerant passing through the motor winding area to cool down and more oil return for lubrication so both of these will be lower since the txv will adjust the flow for a smaller system. The current will be higher just do to the size. Other than that, not sure but once again, not sure when someone would really be in a circumstance where they need to oversize since you can match hp even if it is not a direct replacement, Thanks and Merry Christmas Stellar!
@DVGuy2
@DVGuy2 5 жыл бұрын
Always informative Videos and step by step diagnosis! Thanks again!!!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks L Brown!
@morganne23
@morganne23 4 жыл бұрын
Good video, informative, dont forget sometimes its just a bad board in general. I had a Trane 80% yesterday no variable speed. Verified pressure switch was closing and remaining closed, no blockage, inducer was on, verified voltage and what inducer was pulling, and removed exhaust to bypass to see if it was blocked and if it would still happen, still getting “pressure switch error”. Ive also had a few furnace control boards immediately give a pressure switch code and the board itself not sending any voltage at all to inducer in the first place, I think you mentioned that. I was taught it is rarely the pressure switch thats actually “bad”
@parkerbohnn
@parkerbohnn Жыл бұрын
It never the pressure switch itself its usually the intake pipe and or the exhaust pipe is clogged. For me I can't unclog the exhaust pipe so I run with the tube off the pressure switch. Trane furnaces are living proof it doesn't pay to save a dollar.
@morganne23
@morganne23 Жыл бұрын
@@parkerbohnn I have had a couple bad pressure switches that got permanently stuck before but very rare.
@parkerbohnn
@parkerbohnn Жыл бұрын
@@morganne23 I just run with the tube off the pressure switch. The pressure switch is good the motherboard just got replaced and the motor is a new replacement. The exhaust pipe is 25 feet long and there's some blockage at the furnace no way to get rid of the blockage at the furnace where the exhaust pipe meets the furnace. All the vents outside are clear. It's a piece of junk XR 90 Trane furnace from 2004.
@morganne23
@morganne23 Жыл бұрын
@@parkerbohnn lol yeah I just had like 2 feet of birds nest in an exhaust and intake but the run was so long I could only hook the nest in the intake. I told them to get a duct cleaning company to get the exhaust cleaned out. Not to mention inside the pvc was under finished ceiling. Im not dealing with that. It was a 90% Lennox... the ones put in by contractors in new construction homes that usually end up leaking all over off the inducer.
@ejohnfall
@ejohnfall 5 жыл бұрын
Good technician and great teacher
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks ejohnfall!
@matthewkrueger9319
@matthewkrueger9319 4 жыл бұрын
It's the first "cold" day of the year and hot air was not coming out of the vents. Spent the good part of a day thinking my pressure switch was bad (31 error code) and tinkering with many things. Watched this video and decided what the hell, maybe item number 1 (clogged exhaust) is the culprit. Went outside to look - lo and behold a bird had built a nest in the exhaust pipe over the summer! Took a wire hanger apart and used it to pull lots of sticks and nest particles out of the exhaust pipe on the side of my house, then jacked the heat up using the Ecobee thermostat app on my phone, and glorious air started rushing out of the exhaust pipe. Went back inside and the house was warming up. Thanks so much for the tips! Is there some kind of screen one can put on the exhaust to stop this from happening, or would that be a bad idea? Dryer vents have those plastic mesh covers, it seems like this large pipe is just begging for a bird to nest here every year.
@parkerbohnn
@parkerbohnn Жыл бұрын
My problem is the exhaust pipe is clogged at the furnace and the pipe is 25 feet long so I can't unclog it.
@summitm18hvac90
@summitm18hvac90 5 жыл бұрын
As always, awesome well put video! Thanx brother
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Summit!
@philipcunningham4125
@philipcunningham4125 2 жыл бұрын
Excellent troubleshooting and explanations!
@Stevenowski
@Stevenowski 5 жыл бұрын
Just a different kind of magnehelic gauge! Good information. Keep up the good work!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Yup, thanks Steven!
@psdubl07
@psdubl07 3 жыл бұрын
We had AC installed a few weeks ago and starting 2 nights ago we're getting error 45 on a Rheem high efficiency, gas furnace, which means the low pressure switch is open when the inducer is at high speed. I/m not sure but it seems more than a coincidence that this started happening just a few weeks after the work was done. They sent a tech out to check it, and he said the problem was probably the line clogged because when the furnace was installed (about 6 years ago), they (diff company) ported it out into the ground, which he said could get clogged. He cut the pipe so now it just empties out onto the ground and got it running again. A few hours after he left, it errored out again. The after hours guy came, fiddled around, checked the pressure, clogs etc...checked some of the connections and such, and got it going again saying that he thought maybe the previous error code hadn't been cleared out. It was running, he left, only to have it error out again after an hour or two. It will still run, but just blows cool air out the vents. Anyone have any ideas about why it would run for a bit, then error out and shut off? I feel like some of the things covered in this video aren't the culprit becuase then it wouldn't run at all. Thanks!
@dominiquepierre916
@dominiquepierre916 2 жыл бұрын
You teach very well 👏👏👏👏. But to be honest ;I dont like career furnace. The parts are too expensive and many times my customers get panic with price of repaire. The ECM ventor motor fails every 5 or 6 years ; The condensation gets plugg so easy.
@andrewgibb8846
@andrewgibb8846 3 жыл бұрын
That third commonomoner looks phenomenomenal.
@awbirnie
@awbirnie Жыл бұрын
Thanks, my issue turned out to be plugged drain line for condensation. Removed end at blower and blew into it.
@danfagan71
@danfagan71 Жыл бұрын
Great job! Explained very well.
@michaelwestmoreland412
@michaelwestmoreland412 7 ай бұрын
Awesome teacher!
@efraimjaime8802
@efraimjaime8802 4 жыл бұрын
Thank you for sharing your knowledge .
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Glad to help!
@gmichael5506
@gmichael5506 4 жыл бұрын
Excellent presentation.
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thank you kindly!
@YTsux24-7
@YTsux24-7 5 жыл бұрын
#11 it's a Carrier. #12 it's a Goodman/Amana. #13 PVC shavings from hack vent installs blocking the drain port. #14 Bugs clogging the drain ports. I once found three mice had somehow gotten into the inducer wheel and burned out themselves and the ID motor. Thanks for sharing!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Ha ha nice! Thanks Tomon8tor!
@capitolrefrigerationheatin7501
@capitolrefrigerationheatin7501 5 жыл бұрын
Number 1 should be it a carrier,lol
@throttlebottle5906
@throttlebottle5906 5 жыл бұрын
cannot say I've seen a pvc shaving blockage, but it's sure is possible
@Stevenowski
@Stevenowski 5 жыл бұрын
I've seen a blockage due to a piece of fruit that dropped down the stack. That was interesting!
@jesusgarcia225
@jesusgarcia225 4 жыл бұрын
On the pressure switch how we know where each hose goes to? top or bottom? from orange or yellow cable? will not matter if it gets reversed?
@jackpast
@jackpast 5 жыл бұрын
Nice troubleshooting flow, Craig! You’re eliminating shotgunning 1 video at a time!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Jack!
@gwinters6847
@gwinters6847 2 жыл бұрын
I came across one new bdp unit that the inducer molded plastic had a malformed seam near top of mating surfaces to heat exchanger... just enough leakage to operate pressure switch on the lower end of break, make point. I lost hair that day . ha. NEVER stop learning!!
@googlesux666
@googlesux666 10 ай бұрын
I'm stuck on error code 32. I think it may be a bad control board as I don't think 120v is going to the inducer motor. The molex connector where you have your leads stuck in is where to check for 120v, correct?
@andysullivan7226
@andysullivan7226 5 жыл бұрын
Had one with the rubber hoses going to the condensate drain, relief port box the relief hose was clogged with grey like stones/dust, we PM the furnaces and flush out the box, the condensate box would flush out so to say, the rubber tubes are alittle hard when we always inspect them, then this one time I squeezed the lines like I do and the tube in that spot busted open and water went flowing. The relief tube and upper drain tube where clogged with this grey stuff and was eating out the rubber. So I always pull lines and check now. The call was for water on floor. No sign of water any where, nothing in condensate drain and never leaked water when I was there. Also noticed alot of water coming out of exhaust, which I known something was not right. Fixed the tubes and perfect now.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Nice thanks Andy!
@arsent8326
@arsent8326 8 ай бұрын
Can a too low or too high gas pressure also cause this? I have a newer icp hvac and it throws 6 flashes, turns off once or twice a day i have to shut the power off wait few mins then turn it back on and it works again. Unit is about 1 year old. I have 2 of the same units 1 of them works normal
@الجمهوريةالشيطانيةراعيةللارهاب
@الجمهوريةالشيطانيةراعيةللارهاب 5 жыл бұрын
Well Said and Explained thank you
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Thomas!
@EGGINFOOLS
@EGGINFOOLS Жыл бұрын
Thanks for the detail. I have a trane xv95. After 3 seconds of the burner lighting it cuts off. Tries 2 more times then 2 red light flashes for retry lockout. Flame sensor has been cleaned and inducer motor was changed due to bad bearings. Funny thing is that if I pull the vacuum line from the burner box and slightly blow in it when the flame lights i can hear the pressure switch click and it'll stay running every time. It has a dual pressure switch setup. I think the switch is bad.
@parkerbohnn
@parkerbohnn Жыл бұрын
I have an XR 90 Trane and as everyone knows they're the worst furnace ever made. I just run with the hose taken off the pressure switch. The pressure switch works perfectly the motor is a brand new replacement and the intake and exhaust pipes are 25 feet long apiece so I can't suck out anything. So I run with the hose off the pressure switch.
@stephenpistoia1227
@stephenpistoia1227 5 жыл бұрын
Thanks I’ve learned a lot from you. 👍
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Stephen!
@willscott3327
@willscott3327 2 жыл бұрын
I was on the second floor of my home when I heard something abruptly spin down. Apon investigation I was getting the 3 light flashes then pause. I could feel cool air come through the vents but furnace wouldn't fire. Through troubleshooting I started blowing into all the tunes that were in the path of the pressure switch. I also blew into both ends of the pressure switch and I could hear it clicking. When the author of this video said a bird nest could fall down the pvc stack connected to the inducer motor I decided to check. I found a 3 inch piece of wood lodged down into the enducer motor. Once removed my furnace fired up.
@Avargatoth
@Avargatoth 5 жыл бұрын
Also i already had a guy order the part, but wheres the best place to order carrier parts? my furnace is exactly the same as the video just standing up.
@lancerudy9934
@lancerudy9934 3 жыл бұрын
Thanks for the great video!
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
Glad you liked it!
@rocker8692
@rocker8692 4 жыл бұрын
How would you check to see if the vent isn't clogged in the middle of it?
@brandonburr1941
@brandonburr1941 Жыл бұрын
The other tube coming from the pressure switch to the burner box is tripping my pressure switch code.then the heater just keeps short cycling then resets for an hour. What's going on please?
@adlerpaul
@adlerpaul Жыл бұрын
Error code 31 (Bryant Power Plus model 350) after running for 2 hours continues.. Any advice? Thanks
@minnesotasalamander5913
@minnesotasalamander5913 3 жыл бұрын
Good instruction.
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
Glad it was helpful!
@kevinmiller83
@kevinmiller83 3 жыл бұрын
Great video! Very helpful. I had a problem with mine were the installer did not route the drain line properly after it left the unit. Do you do any videos on proper drain line installation or problems. My furnace drain and ac condensate drain were combined before a p trap which was against York’s recommendations and it cause the furnace drain back up after long runs. So I would get intermittent pressure code errors. My hvac guy changed out both sensors and and wanted to change the board next before I said time out. I was surprised that my guy did not use a manometer to check the actual sensors and instead just wanted to start replacing everything since the parts are cover under my York warranty, of course i pay for the labor.
@deanmartin1966
@deanmartin1966 5 жыл бұрын
Great job. Thanks for sharing
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Deanmartin1966!
@mandalyn6895
@mandalyn6895 2 жыл бұрын
So my heat stopped working and I have watched a ton of videos on it. Love yours it’s great!! Lots of good info. My question is this tho. I seen on another video that the number one issue is a dirty flame sensor. So I took mine out and furnace fired right up. Next day same issue. Then I realized that it has error 31. Decided to clean the flame sensor one more time just in case it worked again. It did! But now I’m in the same boat again and thinking I need to replace the flame sensor. Am I wrong? Or should I focus on the possible causes for the error 31?
@uptownphotography
@uptownphotography Жыл бұрын
I have a Goodman 80% model Horizontally mounted unit in attic saying via the code that the pressure switch is stuck open. I could use some advice/input how to proceed and what to check next. Note: Inducer motor works, but no ignitor turns on. (I replace the Flame detection sensor thinking that was the issue because last week the furnace did not work and then started working normally again for about 4 days. Now it's not working again and as mentioned blinking that the pressure switch is stuck open...Thanks... Phil NYC Area
@tommartinez62
@tommartinez62 2 жыл бұрын
I got an error code of three flashes on my 12 year old Goodman furnace. Jumping the pressure switches did not work so I started testing them , flame roll out sensors, etc. They all read good, the only thing left at that point was the circuit board. Replaced that an we are golden. Error codes are kind of a joke with furnaces. If the sequence of events are interrupted that is where the error code seems to flash to.
@Atl-pu6fk
@Atl-pu6fk 2 жыл бұрын
Excellent video.
@bobbiemckee
@bobbiemckee 2 жыл бұрын
Very helpful. Thank you
@1venomous1
@1venomous1 3 жыл бұрын
Can the two wires on the switch go on eatherside? I replaced the switch, but there was no writing or guidance on which wire went to which prong.
@hsulli6715
@hsulli6715 5 жыл бұрын
Another great video. 👍👍
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Homer!
@nomanjones4803
@nomanjones4803 3 жыл бұрын
I had a problem with the pressure switch not opening after last cycle, I took switch off and had continuity between com & NO, I noticed a very small amount of water inside switch, after getting the water out and no continuity between terminals I reinstalled switch and The furnace started and ran fine. how would water get into switch?
@reedkwize1
@reedkwize1 5 жыл бұрын
I have an American standard freedom 80 hat only furnace and I have the pressure switch error code. My furnace will start, the flames would come on and before the blower motor kicks in, the furnace starts cycling ( inducer motor stops then stops) then the code comes on. Help!!!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
On an 80% unit, it is usually the hole where the tubing is connected at the inducer cloggs, the pressure switch is bad, or the exhaust pipe has a problem. It could also be a cracked heat exchanger but you may notice the flames rolling back if that was the case. I use my SDMN6 to check pressure switches. You can also read resistance across the switch with multimeter set on ohms to see if when it clicks closed if you are getting close to 0.0ohms of resistance. I just checked one on friday that was reading 300ohms so I knew the pressure switch was the problem, thanks
@reedkwize1
@reedkwize1 5 жыл бұрын
It’s not the pressure switch, I have two furnaces and I swapped the switches and the switch worked on the other furnace. Sometimes it will go as far as the flames coming on, and before the blower motor kicks in, it starts to cycle.
@reedkwize1
@reedkwize1 5 жыл бұрын
Thanks by the way🤙🏾
@lightningsmokerXx
@lightningsmokerXx 2 жыл бұрын
My 2008 Ruud/Rheem Furnace Model: UGFD-07EMCKS , flashes 5 & 7, so code 57 High Pressure Switch (contacts open - inducer high ) and the heat wont stay on. I cleaned the flame sensor, turned the power on , put the bottom furnace door on, and the furnace lighted and worked for about 5min , until i switched the fan to auto from on. And wont re light. Its a modular controlled furnace with a "v " wire and says you cant manually light the pilot. Not sure what to do about code 57.
@wilheys.6224
@wilheys.6224 5 жыл бұрын
Thank you, sir! For sharing!!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Wilhey!
@geojor
@geojor 5 жыл бұрын
thanks for this good information ...
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thank you!
@rickbraden4272
@rickbraden4272 2 жыл бұрын
Very good!
@df56gh4d5h
@df56gh4d5h 5 жыл бұрын
You said there was a link to a video on fixing the condensate trap but I don't see it?
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
I added it in the description section, thanks- kzbin.info/www/bejne/nabJZId7iMdmjJI
@eddieshvac843
@eddieshvac843 5 жыл бұрын
I had one last week that would crank up and run.but not quite fast enough. Low rpms
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Nice, if the cap and voltage were good, sounds like the windings bad, thanks
@MVPProductionsBeats
@MVPProductionsBeats 2 жыл бұрын
I had a pressure switch open while inducer is on code. I don’t have a manometer but I checked the tube from switch to inducer it’s fine, I cleaned the port on the inducer that the tube connects to and it’s fine. I tested the pressure switch and it was working, I was getting 24 volts right before the inducer vacuumed it and closed the switch then goes down to 0. However at one point I started getting a low voltage at the pressure switch while inducer was on, I was seeing about 5 volts which was strange. Furthermore at another point the code was on and I was literally measuring the switch at that point and it was fine. I changed the pressure switch because it was fishy. However the problem happened again but then it stopped. My only other assumption would be the control board.
@lancerudy9934
@lancerudy9934 5 жыл бұрын
Can you show how to hook up the tool to read the pressure
@JuanTodoli
@JuanTodoli 5 жыл бұрын
Cool review.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Juan!
@audirx8
@audirx8 5 жыл бұрын
The drain tube coming out the bottom of the furnace at the pea trap I took the water drain hose off and its sucking air in to it Is that normal or should it be blowing out?
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Yes, the water weight stops the suction and allows the water to flow through the trap and out of the furnace. You should fill the trap again with water after cleaning it, thanks!
@Avargatoth
@Avargatoth 5 жыл бұрын
So i had my inducer motor wheel inside break apart, i replaced it and a year later its doing it again, so i bit the bullet and ordered the whole new house unit with the motor and such....is this normal to happen?
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
The carrier inducer internal wheel typically doesn't break compared with other manufacturers. Is the wheel hitting water constantly in reference to how the furnace is pitched?
@Avargatoth
@Avargatoth 5 жыл бұрын
AC Service Tech LLC i dont believe so, its not like its particularly humid but its odd that just short ammout of time, i gota take it appart soon any way see the condition, overnight it just kept turning on, ran for a bit then off.
@jjyemg2397
@jjyemg2397 5 жыл бұрын
You are awesome!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Glad to Help JJY!
@heruvarishebey7323
@heruvarishebey7323 5 жыл бұрын
so the inducer comes on, the ignitor lights up, I hear the click on the gas value but the gas don't come out the value , the trouble code Is one blink for ( gas low, gas pressure, gas value , flame sensor) check the flame sensor and no curient is coming from the board , but I would think , no current would come until the furnace fire up . also I had water damage in the house that my have gotten in the furnace , do anyone have idea whtat the problem could be
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
You would need to read the voltage going to the gas valve and the gas pressure going in and out of the gas valve, thanks
@PBS-nm1uu
@PBS-nm1uu 5 жыл бұрын
what would cause it to have a wrong pitch ???
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
That would be improper installation or sagging due to not enough supports, thanks
@lindamyers7071
@lindamyers7071 5 жыл бұрын
I have a 7-yr-old Goodman GKS9 gas furnace. It goes through one cycle (stays on as long as needed to reach temp setting) and shuts off, but when the temp drops it won't start the next cycle. Instead, the fan blows cool air and I get an error code 3-pressure switch stuck closed. I replaced the pressure switch-same behavior. I can turn the furnace off then on to start a cycle. Any thoughts on the cause?
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Has the condensate drain and tubing been blown out or vacuumed? That will trip the pressure switch intermittently, thanks and lookm up "acservicetech clean furnace drain"
@lindamyers7071
@lindamyers7071 5 жыл бұрын
@@acservicetechchannel The drain and tubing were vacuumed; I watched your video and did it again (great video-very easy to understand), but still having the same issue.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
You should be checking the pressure switch with a multimeter to see when it is closed or open and if 24v is crossing it. If there is no problem there and the board is saying that there is then the board would be at fault but you would really need to take your readings at the pressure switch first, thanks!
@bdf8642
@bdf8642 3 жыл бұрын
My concord furnace will not run unless I tap the pressure switch with my finger. Then it will run until the thermostat gets to temperature. Then it won’t turn on again until I tap. Any ideas?
@parkerbohnn
@parkerbohnn Жыл бұрын
Spray the switch with WD-40.
@levilinton5743
@levilinton5743 3 жыл бұрын
You didn’t mention if you take the burner door off and it fires up it’s the intake pipe
@donnierobertson3088
@donnierobertson3088 3 жыл бұрын
Ok
@esdrasparedes360
@esdrasparedes360 5 ай бұрын
Where is the adress to buy supply
@morganne23
@morganne23 4 жыл бұрын
Anyone else have issues with 90% Nordyne furnace tripping inducer limit all the time? Its my own furnace, not a customer. I have cleaned the secondary (even though it wasnt really dirty) the A-Coil, always change filters, slope on exhaust is fine, etc... it is not an under sized unit, nothing blocking any vents, blower wheel cleaned, the weird part is, the collector box stays pretty cool. Wondering if it is possible it is smashed behind the collection box. Also, read somewhere that restrictor plates inside the inducer on some have been known to fall off or rot. Not sure how true. Weird part is, once I cleaned the A-Coil, it stopped tripping the limit for the remainder of winter (it was January) once I cleaned it, it stopped and heated beautifully. Like 6 degrees in 40 minutes no tripping, then, following winter (this year) started in again) you cant tell me the A Coil re plugged that fast. Especially with how well I cleaned it.
@cd-stephen
@cd-stephen 4 жыл бұрын
was looking at your book and i don't see anything in the toc about furnace repair
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Our present book is on refrigerant charging and troubleshooting but we presently do not have one out on electrical or furnaces yet, thanks!
@cd-stephen
@cd-stephen 4 жыл бұрын
@@acservicetechchannel winter is coming 😄
@cd-stephen
@cd-stephen 4 жыл бұрын
I appreciate all the hard work you guys do on KZbin publications I will pick up your full kit to support your channel
@kennyw7453
@kennyw7453 5 жыл бұрын
Excellent video
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Kenny!
ECM X13 Blower Motor Troubleshooting!
8:07
AC Service Tech LLC
Рет қаралды 199 М.
Air Conditioner Troubleshooting! Connecting, Measuring, Fixing, Disconnecting!
21:05
Фейковый воришка 😂
00:51
КАРЕНА МАКАРЕНА
Рет қаралды 7 МЛН
АЗАРТНИК 4 |СЕЗОН 3 Серия
30:50
Inter Production
Рет қаралды 825 М.
Шок. Никокадо Авокадо похудел на 110 кг
00:44
Inducer Motor Not Coming On - How to Check It
29:28
Word of Advice TV
Рет қаралды 595 М.
Furnace Pressure Switch Troubleshooting- Definite Testing Procedure!
13:31
AC Service Tech LLC
Рет қаралды 56 М.
Top 5 Furnace Problems and How to Fix Them
20:11
Word of Advice TV
Рет қаралды 1,4 МЛН
Furnace Pressure Switch Troubleshooting
17:06
Word of Advice TV
Рет қаралды 800 М.
How to Test Pressure Switch on a Furnace
14:26
Word of Advice TV
Рет қаралды 611 М.
How to Jump Pressure Switch on Furnace
7:00
Word of Advice TV
Рет қаралды 701 М.
Crucial Knowledge To Heat Pump Troubleshooting
14:15
Jersey Mike HVAC
Рет қаралды 31 М.
Should You Replace a Bad TXV with a Piston? & TXV Diagnosis!
21:53
AC Service Tech LLC
Рет қаралды 28 М.
HVAC CONTACTOR Operation, Types, Ratings, Problems, Testing!
16:06
AC Service Tech LLC
Рет қаралды 84 М.
Фейковый воришка 😂
00:51
КАРЕНА МАКАРЕНА
Рет қаралды 7 МЛН