@robertwheeler8476
@robertwheeler8476 3 жыл бұрын
I have seen them come out of the factory with the loader wiring reversed - It starts on full load. I used to check that every compressor unload solenoid was correctly energised on start up
@terryrowe5982
@terryrowe5982 Жыл бұрын
If you pump down the compressor and remove the flare fitting on the end of the slide valve you can put a 5/16 nut driver into the hole and tap on it to free up the slide valve. I went on a job behind another tech to replace the solenoid kit. In the cabinet was another new kit that someone had bought previously. I got suspicious and downloaded the service manual and followed the procedure mentioned above and it worked for years without any issues. Quick fix that several other companies couldn’t do. Customer care and support!
@jollyscaria1922
@jollyscaria1922 7 ай бұрын
Pump down hev stom chillar liqued comprssstom unlorder stck up nog mechisom working systom gas nog passing unlord workinv corold systom comprsorok
@reyruiz7763
@reyruiz7763 3 жыл бұрын
Thanks a lot guys! I have been monitoring trane chillers for couple of months and as an entry level tech i do ask some guys with much more experience and no answers, one even told me got to learn by your self like i did. Any way thanks and keep it up.👍
@PTF491
@PTF491 3 жыл бұрын
what a douche
@stevestadinko6045
@stevestadinko6045 2 жыл бұрын
"Learn yourself, like I did" is just another way of saying "I don't know".
@HCheatNcool
@HCheatNcool 3 ай бұрын
You made perfect sense. Thanks for this.
@Mikton2509
@Mikton2509 2 жыл бұрын
She already has a leaking lip seal (indicated by the aluminum block in between the solenoids and Comp housing) . As stated in the previous comment the sb for troubling shooting is helpful, but an old timer showed me a trick with hooking up a manifold set hp to discharge, planning to suct, and middle port to the Schreiner port on the slide valve cover. You can crack or burp manifold value open momentarily to load or unload disc to load, suct to unload. If you leave suction open and comp does not unload you know that slide valve is issue. If it loads and unloads fine you know to start looking at solenoids or triacs.
@GaneshKamble-gd9cg
@GaneshKamble-gd9cg Жыл бұрын
Hi, Can you explain this through video please.
@hvacinthecity9369
@hvacinthecity9369 11 ай бұрын
Nice
@jmoney_638
@jmoney_638 Жыл бұрын
Learning alot from all of your videos. Thanks for putting these videos out for everyone to watch.
@cthomaspac
@cthomaspac 3 жыл бұрын
I remember once we removed the unloaded plate. Cut a beer can to slip under the plate so it couldn’t load up , until we received the parts.
@tylerf91099
@tylerf91099 3 жыл бұрын
Recently replaced the unloader piston on one of those machines. Seals were so worn down that oil was blowing by and would only operate at 100% open and it appeared that it was just stuck
@abdul007abdul2
@abdul007abdul2 2 жыл бұрын
Pls can u make vidio on RTAA overload setpoints
@larryboy4905
@larryboy4905 3 жыл бұрын
There is a procedure to switch loaders on and off to troubleshoot to see whether the problem lies in the compressor or the controller.
@HVACTIME
@HVACTIME 3 жыл бұрын
Ill look into that, i haven't come across a specific procedure before. Thanks for the tip
@larryboy4905
@larryboy4905 3 жыл бұрын
@@HVACTIME Try Trane general service bulletin RTAA-SB-5 starting page 41.
@HVACTIME
@HVACTIME 3 жыл бұрын
@@larryboy4905 amazing thank you
@abdul007abdul2
@abdul007abdul2 2 жыл бұрын
RTAA OVERLOAD SETTING OR CAN ANY ONE EXPLAIN PLS
@aircooledchilleralltypes4938
@aircooledchilleralltypes4938 3 жыл бұрын
Good sir
@scowell
@scowell Жыл бұрын
There's a male unloader pair (these) and a female unloader (single, on the back), right? So during start-up the female valve is unloaded... but you're saying that after the first start-up in the morning the female valve closes and the *male* unloaders are set too high? And can't move? So if the female unloader couldn't unload it wouldn't even be able to start, but now it can start but runs too hard. Our 120ton is having unloader problems right now, those pistons get sticky! Looks like they want to change the compressor... makes bad noises, like marbles inside.
@_Padma_TausikHasan
@_Padma_TausikHasan 3 жыл бұрын
Why is it necessary to hold a magnet on the LED to bind the sensors of the trare chiller? Why and how does the LED light up when you hold the magnet?
@HVACTIME
@HVACTIME 3 жыл бұрын
kzbin.info/www/bejne/rZysn4trn7aahdU
@TechnicalBrainHVAC
@TechnicalBrainHVAC 4 жыл бұрын
Verynice bro #technicalbrain
@tylerwirth5358
@tylerwirth5358 Жыл бұрын
I have a trane rtwa chiller compressor B tripping on latched fault : compressor overload . This system did have a leak and we fixed the leaks and recharged to factory LBs but when it gets called on right away it’s tripping and my alarm light comes on for latched fault diagnostics is compressor overload do you think this is my problem ?
@tejprakashsingh8790
@tejprakashsingh8790 3 жыл бұрын
What about liquid pressure. Is the condenser fan makes noises when unload not in operation.
@HVACTIME
@HVACTIME 3 жыл бұрын
I dont understand you're question.
@tejprakashsingh8790
@tejprakashsingh8790 3 жыл бұрын
@@HVACTIME sir . When unload not working properly. It's creating high liquid pressure in condenser and thus condenser fan makes noise also . And expansion valve close partially because of unload commands. I dont know how to explain. Poor English😒. Anyway. Expansion valve, loading unloading valve and condenser all works in proportional and in triangle 🔺️. And thanks for sharing your valuable information. God bless you
@HVACTIME
@HVACTIME 3 жыл бұрын
I understand now, yes they all work together but it shouldn't make the fans noisy.
@GaneshKamble-gd9cg
@GaneshKamble-gd9cg Жыл бұрын
Sir, In this case I think the discharge pressure will not rise higher because the expansion valve must be closed and there will less refrigerant entering inside the compressor. If less refrigerant is entering inside compressor then the discharge pressure will also be less. Only the compressor will keep running in this case because of stuck unloading valve. Also I doubt why it is not getting trip under low pressure after reaching the setpoint. Because expansion valve is closed and it will not allow the refrigerant inside compressor and compressor keeps pumping due to failed unloader. Also why the compressor does not cutoff automatically if the unloader is failed but the demand is met. Correct me if I am wrong Sir please. Thank you.
@rocker8692
@rocker8692 2 жыл бұрын
Do these things come with a big troubleshooting manual you can read?
@HVACTIME
@HVACTIME 2 жыл бұрын
Yes sir
@travelmindanao5755
@travelmindanao5755 Жыл бұрын
Ewan ko sayo
@kmidst_kn6329
@kmidst_kn6329 2 жыл бұрын
FYI, should not be opening the panel with mains on and exposed terminal blocks like that. That is very dangerous.
@HVACTIME
@HVACTIME 2 жыл бұрын
Its not ideal but frequently necessary for troubleshooting.
@kmidst_kn6329
@kmidst_kn6329 2 жыл бұрын
@@HVACTIME Definitely makes troubleshooting faster, but there are safer options such as a meter with a wireless display or installing scope probes with the power off and then closing the panel before running again.
@hvacusanda7269
@hvacusanda7269 Жыл бұрын
Don’t tell him how to do his job
@kmidst_kn6329
@kmidst_kn6329 Жыл бұрын
@@hvacusanda7269 Wow it's amazing how stubborn people can be even when it's a literal life and death situation.
@brucemerryman7365
@brucemerryman7365 Жыл бұрын
@@kmidst_kn6329are you a pencil pusher or have you worked in the field?
Low Oil Troubleshoot RTAA Chiller
11:24
HVACTIME
Рет қаралды 16 М.
Compressor Unloader - HVAC Online Training and Courses
11:37
Aircon Academy
Рет қаралды 146 М.
Which One Is The Best - From Small To Giant #katebrush #shorts
00:17
Running With Bigger And Bigger Lunchlys
00:18
MrBeast
Рет қаралды 121 МЛН
Don't look down on anyone#devil  #lilith  #funny  #shorts
00:12
Devil Lilith
Рет қаралды 6 МЛН
How Trane Screw Chillers Loaders Work
6:04
HVACTIME
Рет қаралды 16 М.
Trane Chiller Down for Controls Short
17:40
HVACTIME
Рет қаралды 10 М.
Trane RTAC Pt. 2 - Filter Drier, Vacuum, Recharge
23:33
DFW HVAC
Рет қаралды 11 М.
Diagnosing a Locked Compressor 3D
10:02
HVAC School
Рет қаралды 65 М.
#1 Failure with Commercial HVAC
13:50
Quality HVACR
Рет қаралды 100 М.
Trane RTAC Leak Repair + Oil Filter Part 1
19:57
DFW HVAC
Рет қаралды 13 М.
Trane Chiller Unloader Rebuild - HVAC School
5:39
HVACTIME
Рет қаралды 16 М.