LifePo4 battery preparation.
27:27
easyowerwall - building the frame
12:11
easyowerwall welcome
1:41
Жыл бұрын
Пікірлер
@joe-y1z
@joe-y1z 13 күн бұрын
Thank you for this video! I'm building an ebike battery and opted for the 80A jkbms. I was really unsure how to set this up, but thanks to your video i now know all of the settings i need to set!
@Anointingify
@Anointingify 15 күн бұрын
Good video but you didn't talk much about the importance of the schotky diodes that you used. Good work.
@gio4447
@gio4447 20 күн бұрын
Hi, I have a Victron 150/85 regulator and I would like to use the relay to control a 220 volt contactor to turn on a diesel generator. Is this possible?
@easypowerwall
@easypowerwall 18 күн бұрын
Hi Gio, thanks for your question. You can use the relay but keep in mind that it has limitations 230V/4A or 60V DC/1A. If you need higher current you should use an extra external contactor. Good luck. Franky - EASYPOWERWALL
@PhG1961
@PhG1961 Ай бұрын
Op 2:04 wordt vermeld dat de panelen van elk 175W in serie geschakeld zijn. Dit zou op 350W totaal vermogen komen. Ik vind dit merkwaardig. Bij serieschakelingen verhoogt men de spanning, het vermogen blijft toch gelijk?! Om 350W te bekomen zou men toch de panelen in parallel moeten schakelen?! Kun je dit verduidelijken?
@easypowerwall
@easypowerwall Ай бұрын
Hi, bedankt voor je vraag. Je stelling klopt. Bij serieschakeling verhoogt de spanning. De formule voor vermogen is P (vermogen) = Spanning x stroom. Dus voor serieopstelling is vermogen (29V + 29V) * 9A = 522W. Bij parallell opstelling is vermogen 29V * (9A+9A) = 522W. Conclusie, voor vermogen is het niet belangrijk als je de panelen in serie of parallell plaats. Vg Franky - EASYPOWERWALL
@larstomasson9244
@larstomasson9244 Ай бұрын
is one of those links the manual?
@easypowerwall
@easypowerwall Ай бұрын
Lars, very sorry forget to add link to manual. I'm few days off with my better half, will add link sunday evening. Have a nice weekend.
@easypowerwall
@easypowerwall Ай бұрын
The software & manual is available. Link in the description of the video.
@WiSeNhEiMeR-1369
@WiSeNhEiMeR-1369 Ай бұрын
Thanks COOP ...
@rongray4118
@rongray4118 Ай бұрын
Thank you for posting your video! MY wife and I are preparing to go off grid and will have a metal roof just like your roof - I appreciate seeing your installation! Where did you get your work gear (brand) - would love to have flexible clothing to work in!
@easypowerwall
@easypowerwall Ай бұрын
Hi Ron, I got this from a discounter store (Lidl - EU brand) It's available in any hardware shop. Just choose pants with polyester, it give a warm feeling in winter. Good luck with the off-grid built. Frank - EASYPOWERWALL
@jake-hy2zb
@jake-hy2zb 2 ай бұрын
Thank you, Sir. The most comprehensive description of building a combiner box I have found. Subbed!
@easypowerwall
@easypowerwall Ай бұрын
Thanks for your great & kind comment Jake. These kinds of comments make my day and boost my energy to keep going. Have a nice day Jake. Franky - EASYPOWERWALL
@χρηστοςκαραζερης
@χρηστοςκαραζερης 2 ай бұрын
il porta batterie che dimensioni ha ;;;E la distanza fra i due pianni delle batterie qualle e ;;;
@xlgoldfish
@xlgoldfish 2 ай бұрын
Thank you
@easypowerwall
@easypowerwall 2 ай бұрын
The pleasure is all mine. Have a nice day. Easypowerwall
@koenburkink2704
@koenburkink2704 2 ай бұрын
I have a question, My 2x JK-BMS (JK PB2A16S20P) are configured to let my victron multiplus 2 (3x / 3 phase) load my 2 batterypacks (16x320Ah LiFeP04 Cell) (JK BMSes connected to eachother, then 1 can cable to the Cerbo GX. My Charging (absorption) voltage is about 54,7V with high current for an hour, and then raises to about 56,7V with low current. Thats the wrong way in voltage!?? Cerbo is set to DVCC Mode. My most important BMS settings are: Cell OVP: 3.65 V Vol. Cell RCV: 3.6 V = 57.6 V SOC 100% Volt: 3.55 V = 56.8 V Cell OVPR: 3.54 V Cell UVPR: 3.02 V SOC 0% Volt: 3.0 V = 48 V Cell UVP: 2.8 V Power off vol: 2.65 V Vol. Cell RFV: 3.50 V = 56 V RCV time: 1.0 H RFV time: 6.0 H Someone can help me to get this right? My thougths are first high voltage and amps absoption, then lower voltage and amps for float? What settings in BMS do i have to change?? Many thanks for reading this,
@Greenwashedhipppie
@Greenwashedhipppie 2 ай бұрын
Great video! Does the solar panel maximum fuse rating apply to the wiring past the combiner box? Let's say have 4 panels with 6 amp rating. And a 15 amp max Fuse rating. If I parallel them once before the combiner box it would be 12 amps then at the box it would be 24 Amps on the way to the charger. Can that flow backwards toward the panels?
@easypowerwall
@easypowerwall 2 ай бұрын
HEy, Because of the anti-flow-back diodes in the combiner box there's no flow backwards from combined power towards solar. Your numbers are correct. Check your charger, if possible go for a higher voltage input. Most MPPT accept 100V and convert to 12V. Good luck. Franky - EASYPOWERWALL
@Greenwashedhipppie
@Greenwashedhipppie 2 ай бұрын
@@easypowerwall Thanks. I have asked this question all over the internet.
@reyonwilson9334
@reyonwilson9334 2 ай бұрын
Hell. What setting should I set my charg controller using lifepo4 3.5V 30A+30A 16S. What amp should I set my charg controller?
@easypowerwall
@easypowerwall 2 ай бұрын
Not really sure what 30A+30A means. is it the capacity of your lifepo4 cells? If so charge both banks with 30A (= 1C). Always good to check the spec sheet of your batteries. In my case battery bank is +1000Ah so there's no limit in charge current as I will never charge above 1C, it's more like 0.1C Frank - EASYPOWERWALL
@Drillmechanic
@Drillmechanic 3 ай бұрын
Aluminum is metal too not only the steel!
@markrohrlach920
@markrohrlach920 3 ай бұрын
In your parts list I can not find any fuse board . I seen you have your name on your balancing fuse board where can I find the s16 board
@easypowerwall
@easypowerwall 2 ай бұрын
Hey, Under the video you can find a link to my google drive. There you can download the gerber files to order the PCB from you favorite PCB factory. I ordered mine from JLCPCB. If it doesn't work send me another message, try to help you out. Franky - EASYPOWERWALL
@markrohrlach920
@markrohrlach920 3 ай бұрын
The fuses are 32v is this a problem with 52v system
@easypowerwall
@easypowerwall 2 ай бұрын
I noticed that too. Fuses are there to limit the current, actuall can't think of any reason why a fuse would work at 32V but not at 52V DC. Installed it and never failed....
@001jurgen
@001jurgen 3 ай бұрын
Hey Franky, en hoe 'proper' zijn die dingen qua RF? Want het is niet omdat mijn buren heel het spectrum mogen vervuilen met hun omvormers dat ik er zelf nog een schepje bovenop moet doen.
@easypowerwall
@easypowerwall 2 ай бұрын
Goeie vraag....als radioamateur is dat ook een bezorgdheid voor mij. Ga dit zeker aankaarten in een vervolgfilmpje. Bedankt voor de opmerking. Franky - EASYPOWERWALL - ON7RU
@WiSeNhEiMeR-1369
@WiSeNhEiMeR-1369 3 ай бұрын
= I admire your USE of "ferrules" COOP ...
@WiSeNhEiMeR-1369
@WiSeNhEiMeR-1369 3 ай бұрын
Thank YOU I really LIKE your ANTI-FLOW-BACK Diodes COOP the WiSeNhEiMeR from Richmond, INDIANA - USA ...
@easypowerwall
@easypowerwall 3 ай бұрын
Thanks for great comment, hope to serve you in the future with more great tips and tricks
@pascalbudin2983
@pascalbudin2983 3 ай бұрын
Good evening, Thank you for all the videos and all these explanations. I have a problem with the JK BMS connected with a Growatt hybrid inverter and a 16S Lifepo4 battery, the SOC drops from 60% or 50% to 1% in less than a minute. The batteries seem correct to me. How can I solve this problem. Thank you for your feedback. Pascal
@easypowerwall
@easypowerwall 2 ай бұрын
Pascal this is very strange. Have you done a capacitest of the batteries? What's your max. charge and min. discharge voltage?
@柯盈琪
@柯盈琪 3 ай бұрын
Hi there! We are the distributors of the Zmai-90. If anyone is interested in this product, please contact us. The retail price is $19 per unit. For bulk orders, please confirm with us for better price!
@reyonwilson9334
@reyonwilson9334 3 ай бұрын
Hey Frankey, thanks for videos.
@easypowerwall
@easypowerwall 3 ай бұрын
Hey Wilson, the pleasure is all mine. See you soon with more videos.
@Νίκο-δ7τ
@Νίκο-δ7τ 3 ай бұрын
73s
@easypowerwall
@easypowerwall 3 ай бұрын
73s de ON7RU. QRZ?
@Drillmechanic
@Drillmechanic 3 ай бұрын
Agree with you that BMS should be as simple as possible!
@immrnoidall
@immrnoidall 3 ай бұрын
"USER PRIVATE DATA" , Is 13 spaces to store your password so you don't forget it.
@goofykl9
@goofykl9 3 ай бұрын
you helped me understand the combiner box wiring.👍
@easypowerwall
@easypowerwall 3 ай бұрын
Thanks for the nice comment, that's what my video are all about. KISS keep it stupid simple. No overkill. See you soon with more content. Franky - EASYPOWERWALL
@rizgarn.311
@rizgarn.311 3 ай бұрын
Nice Video mate. my inverter is only rated for 27 amp input from PV. if connect all 4 strings in parallel in the combiner box I will exceed the rated amp for the inverter is safe to do so? thanks
@easypowerwall
@easypowerwall 3 ай бұрын
I would not exceed the rated amperage for your inverter. You can use 2 panels and eventually install seperate MPPT charger.
@murat5985
@murat5985 3 ай бұрын
72v 42ah bms advance setting ideal?
@marcvandaele1878
@marcvandaele1878 3 ай бұрын
Hi Franky ik ben nu al uw video’s van voor naar achteren aan het bekijken en zelfs dubbel😅 Maar als ik het goed begrijp, tussen uw panelen en Mppt zijn er fuses breakers en nogmaals breakers met spd gemonteerd.. is dit voor een bepaalde reden? Is het niet voldoende om fuses of breaker en spd tussenin Bedankt Marc vanuit de Filipijnen en bijna startens klaar om ermee te starten
@easypowerwall
@easypowerwall 3 ай бұрын
Hey Marc, Correct, die dubbele zekering & SPD tussen combinerbox en MPPT is misschien overkill. Je kan ze zeker weglaten zonder aan veiligheid in te boeten. Succes met het bouwen, kijk uit naar je project. Groeten uit Belgie.
@peterk.1246
@peterk.1246 3 ай бұрын
Nice Setup, thx for the Informations and go on 🤩
@easypowerwall
@easypowerwall 3 ай бұрын
Thanks for nice comment Peter. Have a great day. Franky - EASYPOWERWALL
@michalknapek5697
@michalknapek5697 4 ай бұрын
One thing is not clear to me. How you connect MPPT and Multiplus together? If you put Batt connector to Batt from MPPT OK and then BATT connector to Multiplus? How?
@easypowerwall
@easypowerwall 3 ай бұрын
Hi Michal, It's all explained in this video: kzbin.info/www/bejne/lWjHaICgYrWif9E Cables from MPPT and the multi plus all connect to the copper busbars above the battery shelf. Check the video. If it's still not clear don't hesitate to contact me. EASYPOWERWALL is also on facebook. Have a nice day. Franky - EASYPOWERWALL
@XanthossNL
@XanthossNL 4 ай бұрын
Nice set up, very clean!!. I have some fears buying from Ali as not all products are good quality, are you sure it is 99,9% copper? Have you measured the resistance?
@easypowerwall
@easypowerwall 3 ай бұрын
Well it was check by a pro electrician and he confirmed it was legit copper. Resistance for short distance is close to 0 ohm. So far no issue, works great since > 12 months. The links in the clip are from thrustworty sellers.
@BasarOzgurKahraman
@BasarOzgurKahraman 4 ай бұрын
I have panels of the same model and specifications. Due to space limitations, I have to mount them in 3 different areas. I want to place the maximum number of panels in each area. In this case 3 different strings will generate electricity at 3 different output voltages. Can I connect these 3 strings to the mppt after making parallel connections in the combiner box? Or in such a necessity, with considering the minimum cost and maximum efficiency, what would be your solution?
@easypowerwall
@easypowerwall 4 ай бұрын
Hi, In this case I suggest to use 3 MMPT chargers. One charger for each direction. If panels with different azimuth will be connected to the same combinerbox, this will not work properly. Good luck.
@pr5991
@pr5991 4 ай бұрын
Hi Mate, I have a Solis hybrid 5KW inverter, and I'm using it with 16 EVE 304 cells and a JK inverter BMS with an active balancer. I've been running this setup for the past five months. The JK BMS communicates the state of charge (SOC) to the inverter, but the SOC keeps drifting over time. Here's the issue: even when the BMS indicates a 100% SOC, the voltages drift slightly lower with each cycle. Over the weeks, the SOC gradually drifts, so while it shows 100%, each cell and the overall pack voltage are slightly lower than the previous cycle. If I adjust the battery capacity settings, the BMS resets to 70% SOC, and the inverter charges another 3 or 4 kWh. This SOC drift is frustrating because on cloudy days, my 16 kWh battery effectively only charges to 11 or 12 kWh. The remaining 4 kWh stays uncharged because the BMS incorrectly reports 100% SOC to the inverter. To fully charge the battery, I have to keep changing the capacity settings in the BMS back and forth. Is there a way to use this inverter without CAN communication or by setting it as a generic battery? If anyone else has the same issue or knows a solution, please comment and suggest how to fix this problem. Thanks!
@easypowerwall
@easypowerwall 4 ай бұрын
Hi, I know SOC and JK BMS is not a great combo, specially with the older BMS. I suggest to use a decent SOC meter (like the victron) to measure and report the SOC. The latest JK-BMS with the breakout board has a better SOC tracking. Hope this helps. Franky - EASYPOWERWALL
@danielo8566
@danielo8566 4 ай бұрын
The earthing
@nickgkogkas7279
@nickgkogkas7279 4 ай бұрын
Earthing is missing. SPD will not work. I am believe that earthing will be setup later.
@easypowerwall
@easypowerwall 3 ай бұрын
In the meantime the earthing is done. When covers are closed will do another tour round the powershed.
4 ай бұрын
I have 4 different Android devices and none of them can install the app to access the JK BMS controllers.. Had to use a Windows 11 Pro laptop to program them and bring the 30kw of batteries online.. The controllers themselves seem to do their job and keep the cells in line but the compatibility of the app is very lacking and it is not that big or complex of an app.. I think it has more to do with security and whatever silliness is going on there.. I wish they would just spend the extra 50 cents and install a Wi-Fi chip that has its own local network homepage built in like routers have..
@ricardophelps6323
@ricardophelps6323 5 ай бұрын
If you only charge to 3.45 why don't you have 18S config? Victron equipment is happy right up to 66V so even a full charge twice a year you would go to 65.7V.
@PhilippeCJR
@PhilippeCJR 5 ай бұрын
If you run 2x JK newinverter BMS in parallel, and connect it to Deye (or some other inverter with CANbus), does the SOC be reported in the inverter from the Main BMS, is a mix of pack 1 + pack 2?
@nategunn2830
@nategunn2830 5 ай бұрын
Im also having trouble pairing regularly. It works maybe 1 out of 10 times.
@easypowerwall
@easypowerwall 5 ай бұрын
Hi Nate, I'm a bit surprised by your message. Never had to pair again after the initial pairing with my cellphone. Just launch the app and it works straight away. Have you tried that? Can you try with other device if you have the same issue, just to make sure it's not linked to your device. Franky, EASYPOWERWALL
@nategunn2830
@nategunn2830 5 ай бұрын
Thanks yeah I tried that. I also have a golf cart with a JK BMS that is acting the same. I'm able to get into both if I retry over and over including restarting the app. Also restarting the BMS helps. I believe it's an app issue or maybe it's just my android phone. 🤷
@SkypowerwithKarl
@SkypowerwithKarl 5 ай бұрын
The JK BMS is still one of the best and getter better. Both the original form factor and the new inverter (closed loop/networked) keep improving. I have four and once I figured out the settings they have been running for close to a few years trouble free. I will say that documentation is only fair. Like anything, there will be some duds but this isn’t too common with these. The most common problem isn’t the bms, it’s an error in installation. And usually if it fails, it just stops unlike some others that can wreak your cells. I highly recommend these
@easypowerwall
@easypowerwall 5 ай бұрын
Great comment, thanks for sharing your experience. Have a nice day. Franky - EASYPOWERWALL
@ccarstea
@ccarstea 5 ай бұрын
Nice job there! One question: why do you have second SPD on the braker box below MPPT?
@easypowerwall
@easypowerwall 5 ай бұрын
Hi, One breaker is for the solar side, the other breaker is for the connection towards the battery. Hope this helps. Frank - Easypowerwall.
@marcvandaele1878
@marcvandaele1878 4 ай бұрын
@@easypowerwallyes but on solar side you have fuses and breaker also and only short distance between m… is it overkill or does I miss something
@universeisundernoobligatio3283
@universeisundernoobligatio3283 5 ай бұрын
What is the fuse internal resistance, the higher the resistance the more it will drop your balance current.
@easypowerwall
@easypowerwall 3 ай бұрын
Fuse IR must be close to 0. All leads are equally long, so if there's a little drop, it's the same drop over all leads. So far it's running great for 18 months, minimal balancing when cell hit 3.45V.
@ricog1497
@ricog1497 5 ай бұрын
You also can include the smartshunt in the ve.smartnetwork. it tells the the correct battery voltage and current to the charge controllers. so the voltage drop between battery and the charge controllers doesn´t matter.
@wilcostienezen9403
@wilcostienezen9403 5 ай бұрын
Heb je de RS450/100 nog overwogen om toe te passen?
@easypowerwall
@easypowerwall 5 ай бұрын
Nee, enkele panelen liggen in de winter in de schaduw van het huis waardoor de de opbrengt bijna nihil zou zijn. Bij de RS450 dien ik alle panelen in serie te plaatsen....Toch bedankt om mee te denken. Franky - EASYPOWERWALL
@haiderhussain2619
@haiderhussain2619 6 ай бұрын
You are doing a great job.
@easypowerwall
@easypowerwall 6 ай бұрын
Thanks for this great comment, gives me a boost to keep working on new content. Have a nice day. Franky - Easypowerwall
@I_m_watching_you
@I_m_watching_you 6 ай бұрын
knappe installatie Franky
@foxeclips9868
@foxeclips9868 6 ай бұрын
What is password i dont have mannual
@easypowerwall
@easypowerwall 6 ай бұрын
Hey, have you watched the movie? I invest quite a lot of time to create this content. I'm entering the pasword during the movie.....and the manual (one pager) is available as download in the comment section under the video. Franky - easypowerwall
@cyberdjro
@cyberdjro 6 ай бұрын
The oil lamp comparison is not very good. I use 2 separate battery banks, consisting of 2x16 EVE280Ah, each with it's own JK BMS v3, communicating with each other and with the charger. Let's continue with your example, one bank has problems and the bms is stopping the charge, but at such a large capacity (560Ah) it is not uncommon to charge it, or discharge it even with 200-300Ah. If a bms enters in the protection mode, you would push all that current in the remaining bank, which depending on how it is setup, will either enter also in protection, either will push it hard. Either way, not optimal. With the communication you don't have that issue, as soon as a bms is out, the charger will decrease the charging current. This was just an example, issues can be multiple, a cell or bms temperature, cell voltage etc. PS: just o e more UTP cable between wthen2 bms's and one to your charger. Nothing complicated.
@haseebahmed3262
@haseebahmed3262 6 ай бұрын
Hey Great tutorial, could you please confirm the peak temp recorded on these DC diods and their Brand?
@easypowerwall
@easypowerwall 6 ай бұрын
Will check temperature on sunny day. The model/brand/specsheet of the DC diodes is in the discription of the video. If you can't find it, contact me via my FB page "easypowerwall" Good luck. Franky
@hunter8202
@hunter8202 6 ай бұрын
battery 24v 100ah charger 20 amperes is it normal or is it very strong ampers?
@easypowerwall
@easypowerwall 6 ай бұрын
Hey, looks normal to me. Power = voltage * amps. In your case 480W = 24V * 20A. Greetings
@hunter8202
@hunter8202 6 ай бұрын
​@@easypowerwallThank you