Fire alarm system battery replacement/upgrade

  Рет қаралды 6,533

NIC’S - SYSTEMS & ELECTRIC

NIC’S - SYSTEMS & ELECTRIC

9 ай бұрын

Пікірлер: 53
@PowderMill
@PowderMill 8 ай бұрын
I have over 1300 Radionics (purchased by Bosch quite a while back) combo fire/burglar alarm systems installed. They are mostly 9112 and 9412 systems with max of 250 zones and in very high end residential settings. I’m just not capable of replacing the SLA lead acid batteries every 2-3 years. Most of the systems have 2x 12v 7 or 9 Ah batteries connected in parallel w/ their listed “dual battery harness”. But.. quite a few a,so have 1 or 2 additional 12v 33ah SLA batteries installed in a separate housing with a separate AC power supply/charger. We used these mainly for peripherals and for system keypads/annunciators in systems with more than 6 hardwired keypads. I’d LOVE to be able to switch out to a “drop-in” lithium LifePo4 solution. It’s definitely going to void the UL / FM / NFPA listings and ratings BUT, with a disclaimer, should be fine if the homeowner opts to change. Even if I can’t find a drop in solution for the control/communicator, I’d love to simply add a single 50 or 100ah LifePo4 battery with charger and fused (or self resetting electronic fuses?) power distribution for the peripherals and extra keypads. The Radionics keypads have vacuum tube fluorescent displays and use 170ma idle and up to 320ma in alarm. (sounders in each keypad draw considerably more power when the system is in “alarm”. The less expensive LifePo4 lithium batteries have been very reliable for me in public safety radio primary power in some of my fire dept vehicles/trailers. We use the Li-Time 50 and 100ah 12v batteries. They are approx $180 for the 50ah and $260 for the 100ah. We use AC to DC 60a chargers from the diesel power3d generators we have on the vehicles to recharge during or after use.. The gensets provide very noisy (EMI/RFI) power out, so we use the 12vdc(actually higher , which helps transmit power) from the batteries to power the radio gear. After 16 months of use, they haven’t experienced a single issue or problem. They replaced a very large and heavy array of deep-cycle AGM lead acid batteries that could only be depleted to 50§ SOC. Lithium sure seems like a game changer for many applications. Anyone have additional info?
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
I don't have information for you as I've never done it or seen it done for those reasons of not being listed for that purpose from the alarm panel specs. however I'll pin your comment in case someone else does have some information.
@wesley00042
@wesley00042 9 ай бұрын
I found that age and heat are the most common factors for replacement. They're already sealed in an unvented or poorly vented enclosure so they tend to dry out faster when they're in a hot electrical room than in a conditioned space. Same goes for most consumer/small business UPSes which use the same types of batteries. I tend to replace them every 3 years in hot environments, 4 years in conditioned spaces and 5 years in conditioned spaces where the load is small. (That's for burgs; for fire systems I would generally replace every 3 years just out of an abundance of caution.)
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
I would agree heat is definitely an issue from what I've seen some in fire alarm and intrusion alarm panels where they don't get that much heat I've seen go for eight years or more but then in small self-contained emergency lights right beside a hot transformer I've seen them fail before two years
@wesley00042
@wesley00042 9 ай бұрын
Home Depot has that same brand batteries for good prices (about $20 for a 12V 7Ah). I used to order Power Sonic off of eBay but I had a few fail unexpectedly in a few weeks to months, probably because they were shipped with minimal padding and I think something internal got damaged. Home Depot seems to pad them better and I have them shipped to store so they never fall into USPS' hands.
@ebelray6890
@ebelray6890 9 ай бұрын
I need to start labeling my UPS batteries throughout my house like you do. I never know how old they are
@thegamingbros787
@thegamingbros787 9 ай бұрын
I have an idea for the bathroom. Maybe you could add one of those automatic door things that have a button and lock when occupied if possible
@ForTheBirbs
@ForTheBirbs 9 ай бұрын
There are lifep04 batteries available that can directly directly replace lead acid types as they have an internal BMS (battery management system). Longer life and a lot lighter. There's a maximum string voltage but fine for 24V systems.
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
That might work well for non-life safety equipment but the charger in them is meant for sealed lead acid batteries and it's what you are required to use you don't have a choice with it
@That_2_guy2T
@That_2_guy2T 9 ай бұрын
The old batteries served all those power outages and now the new ones have years to come!
@atab101
@atab101 Ай бұрын
When one of the battery is faulty, do you replace both of the battery of just the faulty one?
@GaryBeltz
@GaryBeltz 8 ай бұрын
How long did the batteries take to fully charge?
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Usually they will charge within 24 hours
@spykillergames8402
@spykillergames8402 9 ай бұрын
fun fact my HS wasnt always on top of their battery changes so i would often see the fire panel giving battery voltage faults..once the batterioes got so low that the CPU must of glitched out as it kept firing the relays on the address bus (which did the bells/doors) so youd just have a random blast of "brring" or youd find the blast doors not latching open as they think its a fire
@firealarm421
@firealarm421 6 ай бұрын
I just installed new batteries in my new addressable panel. I paid $50 for 2 pack on Amazon. They’re mighty max brand
@Random_Emergency_Light
@Random_Emergency_Light 9 ай бұрын
How often do Emergency light batteries need to be replaced?
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
if they are sealed lead acid batteries than 3 to 5 years
@Harper_DobniYT
@Harper_DobniYT 6 ай бұрын
What are the wires called that connect the batteries to the panel?
@nics-systems-electric
@nics-systems-electric 6 ай бұрын
Battery connecter
@leebailey1220
@leebailey1220 7 ай бұрын
Why does one negative black go to positive red? I didn't take a picture before I took them apart and got a spark and now damaged wire
@nics-systems-electric
@nics-systems-electric 7 ай бұрын
The jumper wire between goes from one positive to the other battery's negative to put the batteries in series then the wires to the panel will go on red for positive black for negative
@robbsutube
@robbsutube 5 ай бұрын
Because two 12 volt in series is 24volt...99% fire alarm systems are 24vdc for standby power..
@robbsutube
@robbsutube 5 ай бұрын
Would be nice if you would go into acceptance vs reaaceptance, annual testing requirements for SLA Batts...
@nics-systems-electric
@nics-systems-electric 5 ай бұрын
I haven't been trained on it much and they just changed the way you have to do it here I don't like to speak on things I'm not super confident on. I'd totally like to someday though.
@leebailey1220
@leebailey1220 7 ай бұрын
I just two old batteries out wothiut taking a picture and i went to put it bwck together and the black with black red with red on one battery that leaves 2 blacks remaining it spark in me what am I doing wrong? Any help is much appreciated
@Granth_Man
@Granth_Man 9 ай бұрын
Lead acid battery’s are my favorite I love them so much that I bought a 12v 12ah battery for my testing and use😂 edit I have the same company mighty max is a really good battery
@topher8634
@topher8634 9 ай бұрын
Vaseline is a great dielectric grease.
@bobbylawless
@bobbylawless 9 ай бұрын
What does the rising link device do
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
Send me email and text message when the fire alarm system goes off I have a video of installing it
@bobbylawless
@bobbylawless 9 ай бұрын
Thanks nic for your reply I did wonder what it does Iol I have a browse for that video now
@jassiyadav4621
@jassiyadav4621 7 күн бұрын
Panel output battery charger voltage how many
@cameronbyrne7970
@cameronbyrne7970 9 ай бұрын
Did you or are you gonna put batteries in the fire alarm panel inside the house?
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
Yes you have to have battery back up I showed installing them in the install videos
@cameronbyrne7970
@cameronbyrne7970 9 ай бұрын
@@nics-systems-electric I live in Ireland so I have Apollo fire alarms and shit.
@cameronbyrne7970
@cameronbyrne7970 9 ай бұрын
@@nics-systems-electric I like the fore alarms you guys have in Canada
@Blueboy197
@Blueboy197 9 ай бұрын
I love these panels
@auswaz4323
@auswaz4323 9 ай бұрын
Why can't you replace with lithium?
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
Charger isn't meant for lithium batteries fire alarm has to be powered by sealed lead acid acid
@joeysmiff1746
@joeysmiff1746 13 күн бұрын
Why arent you load testing the batteries?
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
Because they are brand new... and I don't have a load tester. And the ULC requirements have been changed for what's required for a load test made it more of a pain not that I'm required to anyway.
@joeysmiff1746
@joeysmiff1746 13 күн бұрын
@@nics-systems-electric i meant load testing the old batteries. Just curious. If its not required then no need.
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
@@joeysmiff1746 I was replacing them due to their age that regardless of if they passed a load test they should be replaced
@CJ9899
@CJ9899 9 ай бұрын
See ya in 4 years when these ones get replaced 👋
@firealarm421
@firealarm421 9 ай бұрын
I still have my batteries for my panel since 2021 so I still got a couple of years left with them. They’re Duracell brand
@leafmk
@leafmk 9 ай бұрын
Wow that's some mid old battery's
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
Average age for batteries to get changed is 3 to 5 years so this was pretty normal I wouldn't consider them anything that old I've seen batteries more than 10 years old in fire alarm systems before lol.
@leafmk
@leafmk 9 ай бұрын
@@nics-systems-electric Dang!
@CGray1234
@CGray1234 9 ай бұрын
Must be nice to actually have batteries and not get a system + power trouble when you reset the panel lol. Rest in peace, batteries 🫡
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
Just pick up some sealed lead acid batteries they're pretty cheap most panels can use as small as 7 amp hour
@CGray1234
@CGray1234 9 ай бұрын
@@nics-systems-electricOh okay. I don’t know a lot about batteries tho lol. Did you use those for your old MS-4?
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
@@CGray1234 the batteries that were in my 9200 before the new ones were also in my 10 UD and MS-4
@CGray1234
@CGray1234 9 ай бұрын
@@nics-systems-electricOh okay
@pfilip2346
@pfilip2346 9 ай бұрын
Hi
Setting off 40 fire alarms 2024 New Year's fire alarm ringing/sound off! Happy New Year!
12:58
Three Types of Alarm System Signals and System Monitoring
7:43
GPSTC Productions
Рет қаралды 32 М.
НРАВИТСЯ ЭТОТ ФОРМАТ??
00:37
МЯТНАЯ ФАНТА
Рет қаралды 2,6 МЛН
KINDNESS ALWAYS COME BACK
00:59
dednahype
Рет қаралды 167 МЛН
DAD LEFT HIS OLD SOCKS ON THE COUCH…😱😂
00:24
JULI_PROETO
Рет қаралды 15 МЛН
Llegó al techo 😱
00:37
Juan De Dios Pantoja
Рет қаралды 45 МЛН
Vintage Burglar and Fire Alarm System In A 1970’s Mansion
29:56
UPS BATTERY UPGRADE USING CAR BATTERIES
16:39
DIY-CIRCUIT
Рет қаралды 214 М.
Testing of the new demo Board  with CJ9899
9:16
Canadian alarms
Рет қаралды 905
Fire alarm design - Battery Calculation #Design #Batterycalculation
18:46
All about Fire Protection
Рет қаралды 10 М.
EARTH FAULT - Fire Detection and Alarm System
17:36
FIRE PROTECTION GUY
Рет қаралды 6 М.
Real power outage!!!
10:40
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 14 М.
VERY Expensive Fire Alarm Power Supply | Can I FIX it?
26:44
Buy it Fix it
Рет қаралды 85 М.
Fire alarm ground fault trouble and crashing car into parking lot gate at elementary school
32:40
Stop A Smoke Alarm Chirping With 3 Quick Fixes
5:31
Everyday Home Repairs
Рет қаралды 2,4 МЛН
HOW TO FIX BATTERY FAULT IN FIRE ALARM PANEL ?
5:48
FIRE PROTECTION GUY
Рет қаралды 19 М.
This or That 🛍️
0:52
A4
Рет қаралды 11 МЛН
MISS CIRCLE STUDENTS BULLY ME!
0:12
Andreas Eskander
Рет қаралды 8 МЛН