How the Gas Furnace Pressure Switch Works & Testing!

  Рет қаралды 34,565

AC Service Tech LLC

AC Service Tech LLC

Күн бұрын

Пікірлер: 50
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Tool List- www.amazon.com/shop/acservicetech Support- www.patreon.com/acservicetech For those that are looking for the tools used in the videos: (Linked Below) Here is the link to the Fieldpiece SDMN6 Dual Pressure Testing Manometer with Pump-amzn.to/2jyK5Ka Here is a link to the UEI DL389 Multimeter used in the videos- amzn.to/2av8s3q Here is a link for the Supco Magnet Jumpers amzn.to/2gS4h6z Here is the link for the Irwin Wire Stripper/Cutter/Crimper amzn.to/2dGTj2V Other tool links can be found in the video description section. ACSERVICETECH is a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to Amazon.com.
@modsavant
@modsavant Жыл бұрын
It took me 12 KZbin videos and lots of reading to finally figure out my problem, and your explanation between the 8 and 9 minute mark was the key to putting the pieces together in my head. A simple fix of the air hose plumbing fixed everything and now we have heat again. Thank you!!
@lancerudy9934
@lancerudy9934 6 жыл бұрын
Very nice job . You very nice job on going over the rating of the switches thank for helping us
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks Lance!
@gilbertopatino2616
@gilbertopatino2616 8 жыл бұрын
Thank you very much for another excellent video. May God bless you.
@acservicetechchannel
@acservicetechchannel 8 жыл бұрын
May the Lord Bless you too Gilberto Patino! Thanks
@jermainemyers5596
@jermainemyers5596 Жыл бұрын
I needed this. Thank you.
@dennispittman4555
@dennispittman4555 7 жыл бұрын
Thanks for educating the masses. Great help in building my prototype
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Thanks Dennis Pittman!
@HsingSun
@HsingSun 2 жыл бұрын
Thank you for your video. Did you post the Electric Furnace Pressure Switch works & testing?
@keithrenison5730
@keithrenison5730 3 жыл бұрын
Great video! So here's a question: my Trane uses a dual port (with +/- connections) that requires a 1.4WC negative draft. I've tested the hose from the secondary exchanger which pulls 1.6 to 1.8 continuously while running. It's connected to the negative (-) side of the pressure switch. The hose from the burner box/gas draws about .10 to .08 negative pressure while running. For some strange reason, the switch will not close when the unit first starts. However the whole thing works perfectly (on/off/run) if I disconnect just the hose from the burner box (the differential is just the atmospheric pressure). If I reconnect the burner box hose while running it keeps running, but won't work when it cycles off and back on. I replaced the sensor, vacuumed all lines, cleared the trap, etc. I also replaced the inducer motor to ensure it wasn't the issue. The HVAC guy says the only thing it could be is a bad secondary exchanger (which is under warranty even though the unit is 14 yrs old). When I replaced the inducer motor I caught a glimpse of the secondary exchanger and it looks really clean. Any ideas? I can only guess that for some reason there's too much pressure in the burner box or not enough in the secondary exchanger (clogs I can't see?) and indeed it needs replaced? Blerg!!!!
@ilovenythismuchilovenewyor5801
@ilovenythismuchilovenewyor5801 2 жыл бұрын
pay your professionals
@fourfoldarchives
@fourfoldarchives Жыл бұрын
I've got a Trane XB90 doing the exact same thing. Manometer results are simliar to yours, plenty of pressure to open/close the switch. Tried new pressure switch, inducer motor, and control board. Did you ever resolve this?
@capitolrefrigerationheatin7501
@capitolrefrigerationheatin7501 8 жыл бұрын
nice presentation!!!!!!!!!
@acservicetechchannel
@acservicetechchannel 8 жыл бұрын
Thanks Capitol!
@esbigerodeo1
@esbigerodeo1 8 жыл бұрын
any idea on when you may do the video on the diffrence of microns and inches of mercury?
@acservicetechchannel
@acservicetechchannel 8 жыл бұрын
Sorry Evan, I do not know as of yet. I will have to work that topic into a video maybe on prepping for epa608. Thanks for reminding me!
@wangandrew607
@wangandrew607 4 жыл бұрын
Thanks, good demo and explanation. I have a question why the condenser trap clogged affect the pressure switch?
@meerscan9101
@meerscan9101 8 жыл бұрын
another a1 video! You sure make it simple for new guys coming into trade
@acservicetechchannel
@acservicetechchannel 8 жыл бұрын
Thanks Refrigeration Tech!
@joellmota8600
@joellmota8600 Жыл бұрын
The inducer has positive pressure right blow air to the switch right. ?
@mark.r8900
@mark.r8900 6 жыл бұрын
please help as i am a bit confused. as long as the furnace is calling for heat the inducer continues to run. but on a 2 stage gas valve why do we need two pressure switches? one for low heat and one for high heat. many inducers have only one speed. so , the inducer closes BOTH (low and high) pressure switches at the same time on low AND high fire ? is this correct? but it only has one speed. thanks
@vandalhero
@vandalhero 2 жыл бұрын
In this case, even with one speed before switching to high flame you still want to know you have enough draft for proper operation. For example you could have a 1st stage at .5 and second stage at 1.0 but your inducer is pulling only .8 wc, high enough to run 1st stage but not for second stage.
@stevendennis8225
@stevendennis8225 6 жыл бұрын
Great teaching!
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks Steven!
@yonofui9682
@yonofui9682 5 жыл бұрын
Teacher you don’t have for sale the fitting for the big hose that connects the gage maniful
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
If you are talking about the brass barbed fitting with the threads or the brass barbed tee, I have them linked at www.amazon.com/shop/acservicetech
@geojor
@geojor 7 жыл бұрын
great teaching videos, thanks ...
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
I appreciate it!
@kevinkevin9448
@kevinkevin9448 5 жыл бұрын
Are pressure switches interchangeable as long as water column is same ???
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Yes as long as they are the same amount of ports and type and also the same small orifice insert at the inlet that the original one had, thanks
@mazyarkhanlar8134
@mazyarkhanlar8134 3 жыл бұрын
I have question , When inducer motor works ,pressure switch closes ,igniter gets red but no voltage to gas valve , When I separate the 24 volt wires from gas valve
@mazyarkhanlar8134
@mazyarkhanlar8134 3 жыл бұрын
Hello , I have question , I have furnace ,the inducer runs ,the pressure switch closes,the igniter turns red but no voltage to gas valve , I replaced the board and same problem , But when I disconnect the orange wire (the 24 volt wire from gas valve ,I see that I have 24 volt to the disconnected wire after igniter gets red , What’s the reason , It does not make sense for me ,
@keitharoo1962
@keitharoo1962 7 жыл бұрын
Very helpful! I think I got it now. Thanks!
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Awesome Keith!
@keitharoo1962
@keitharoo1962 7 жыл бұрын
It worked! I did the stuff you said, found the problem, and the furnace is working again! Thanks!
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
That is awesome to hear! That is what we are looking for! Thanks!
@somap8380
@somap8380 3 жыл бұрын
Do the micro-switches contacts get bad (carbon up) in furnaces; as in say microwave appliances.
@waytospergtherebro
@waytospergtherebro 2 жыл бұрын
Anything that involves two parts rubbing up against each other repeatedly is going to fail eventually.
@estrelladelnorte1308
@estrelladelnorte1308 7 жыл бұрын
0:58 please help, i don't understand when you refer to "negative" inch water pressure, i thought inches of water was actually pressure not vacuum, yous say that switch is 0.3 which is equivalent to 0.0108274 psi, to me negative pressure means vacuum not pressure , doesn't vacuum always refers to inches of mercury?? 0 inches of water= 0 psi
@acservicetechchannel
@acservicetechchannel 7 жыл бұрын
Hey estrelladelnorte1308, so this is different than refrigerant vacuum levels. Our Manometers read in - and + water column levels. This is what our pressure switches are labeled as and this is what manufacturers state in their literature. I understand it is confusing when thinking of it compared to refrigerant pressures, inch hg, psia, and psig, thanks
@estrelladelnorte1308
@estrelladelnorte1308 7 жыл бұрын
ok .. so when you refer as negative inches of water column ,it is an actual vacuum but measured in inches of water
@houseofhappiness4987
@houseofhappiness4987 6 жыл бұрын
I have a 2 stage kelvinator 2 different pressure switches..1.3 and the other is 0.80 is that normal or can you use an 1.3 in place of the 0.80?
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
You should replace the pressure switch with the exact same size if needed. You may have 2 switches acting as a differential from the flame box to the inducer or you may have a two speed furnace. For safety only replace with the same size, thanks
@mark.r8900
@mark.r8900 6 жыл бұрын
hi, today i saw a furnace pressure switch that says 1.0wc PR. i tested and found out that this switch is normally closed. the pressure switch is connected to the condensate trap . the other two pressures were PF (for the gas stages) switches were normally open. is it normal for the 1.0wc PR to be normally closed? thank you.
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Hey Mark, most pressure switches are normally open but it is possible to have one that is supposed to be normally closed, in fact there are some like that but they are older with a lot of relays instead of boards. You would need to look at the wiring diagram to see if it is supposed to be NC, thanks Mark
@jimbola77
@jimbola77 8 жыл бұрын
thank you for sharing!!!
@acservicetechchannel
@acservicetechchannel 8 жыл бұрын
Thanks Jimbola77!
@johnaries9301
@johnaries9301 2 жыл бұрын
Can you wire a pressure switch backwards?
@vandalhero
@vandalhero 2 жыл бұрын
its a set of NO contacts so no you cannot. Landing 24v hot on NO will produce the same effect once the switch is closed. Signal will still return to the control board through the common terminal.
The Real Operation of a PRESSURE SWITCH in a GAS FURNACE Heater! Also Testing!
13:37
Quilt Challenge, No Skills, Just Luck#Funnyfamily #Partygames #Funny
00:32
Family Games Media
Рет қаралды 55 МЛН
Honeywell Smart Valve Operation, Testing, Wiring! HVAC Gas Furnace Training!
18:40
HVAC Thermal Limit Switches, Safety Sensors, & Troubleshooting!
16:22
AC Service Tech LLC
Рет қаралды 188 М.
Prevent this Common Manometer Mistake
3:57
HVAC School
Рет қаралды 58 М.
How to Test Pressure Switch on a Furnace
14:14
Word of Advice TV
Рет қаралды 686 М.
Gas Furnace SPARK IGNITION Operation and Testing!
17:07
AC Service Tech LLC
Рет қаралды 108 М.
Fieldpiece SDMN6 Review EP23
14:40
Nighthawk HVAC
Рет қаралды 17 М.
SDMN6 Calibrating an Adjustable Switch with the SDMN6
4:04
Richard McFarland
Рет қаралды 38 М.
Gas Furnace Not Heating Typical Lennox Problems
18:54
HVACR Survival
Рет қаралды 46 М.
How To Use A Manometer For Gas Pressure (Rheem Furnace)
7:14
HVAC Tech Tips
Рет қаралды 141 М.
Quilt Challenge, No Skills, Just Luck#Funnyfamily #Partygames #Funny
00:32
Family Games Media
Рет қаралды 55 МЛН