How to do an EICR start to finish - Electrical Safety Inspection and Test

  Рет қаралды 58,496

Mark The Sparky Allison

Mark The Sparky Allison

Жыл бұрын

I take a run through an EICR (electrical installation condition report) step by step and share some of my methods/experiences in the hope it helps others.
Everyone approaches these differently and no installation is exactly the same.
If you are a homeowner/landlord/tenant then this is roughly what an EICR or electrical safety inspection and test or PIR in old money should look like.
Thanks

Пікірлер: 101
@itanc1
@itanc1 Жыл бұрын
Really enjoyed this, especially the ‘extra’ bits you do for your own piece of mind. I have just bought my first mft and getting to grips with I&T. Your film was a great help and i have subscribed. Thanks again
@graemetaylor8933
@graemetaylor8933 Жыл бұрын
Really well put together video, good sensible explanation on how in depth you need to test
@SJM689
@SJM689 11 ай бұрын
Great video buddy, if you havent already get an apprentice, you would make a great teacher. My daughter loves yours videos and helped her in her exams immensely. The trade need more people like you in it to pass on your knowledge in yhe way you do.
@electrician247
@electrician247 11 ай бұрын
Thanks mate. Yeah we have apprentices. I do www.apprentice121.co.uk as well 🙌. Pleased to hear your daughter is doing well! If she would like an A121 support package drop an email over. Mark@apprentice121.co.uk
@munafmufc01
@munafmufc01 Жыл бұрын
Great video Mark. Very helpful and clear explanation. Thank you
@mohamedsiadabdille7631
@mohamedsiadabdille7631 Жыл бұрын
Thanks for your time and effort to put this interesting video for EICR
@mb-electricalservices
@mb-electricalservices Жыл бұрын
Excellent Mark. Perfect for my apprentice as he's never off his blinking phone 🤣
@electrician247
@electrician247 Жыл бұрын
🤭🤭🤭🤭🤭
@samclegg9319
@samclegg9319 5 ай бұрын
Thanks mark im just about to do my test and inspection exam in a few weeks and this was informative 👍
@andrewcadby
@andrewcadby Жыл бұрын
Good video Mark, it's always interesting to see how other sparks carry out their EICRs. Good (and often overlooked) point about EICRs not being IV. Some tests have little value for an installation that is already in service, eg IR between L and N, and time is better spent on other things IMO. I have found that continuity tests through lampholders using lightmate adaptors often return a higher result than when tested at the terminals. Wear and tear on the lampholder I guess.
@skabbymuff111
@skabbymuff111 Жыл бұрын
I really appreciate this video thanks for making it.
@ElectricianTV
@ElectricianTV Жыл бұрын
What a great video thanks for taking the time to make this mark. It’s so funny watching the video and hearing the smoke alarm chirping away Keep up the good work
@electrician247
@electrician247 Жыл бұрын
That bloody alarm was so annoying. Cheers Will! Appreciate it mate.
@user-fr4qm2ec5w
@user-fr4qm2ec5w 11 ай бұрын
Good video, really helpful for a wannabe sparky. Back to my books.. thumbs up 👍🏼👍🏼👍🏼
@alancooper7018
@alancooper7018 Жыл бұрын
Thanks Mark, all very interesting and educational. Keep up the good work.
@colingoode3702
@colingoode3702 10 ай бұрын
Great video. My son has just moved into a new / old house & needs to get an EICR done because the Curry's install team wouldn't connect his new oven up because there was an earth issue. When the circuit was tested it was tripping the main board 80 amp breaker & not the oven circuit 30 amp breaker - which should be 32amp. It's an old CU which probably needs replacing. Also, upon closer inspection we can't find an incoming earth / CPC & can't find an earth rod either! Not sure where all the socket earth wires go to then & I do wonder is there is any bonding of water / gas pipes either (1950's house)? All part of the fun when you buy an older house which hasn't been touched since the 1970's.
@dansparkyintraining
@dansparkyintraining Жыл бұрын
Nice one Mark
@peaceonearth9550
@peaceonearth9550 Жыл бұрын
Great video
@montystelevision3238
@montystelevision3238 Жыл бұрын
This isn't just a video. It's enrichment for anyone watching. Thanks so much.
@LindaTheLearner
@LindaTheLearner 10 ай бұрын
Thanks Mark … really great video .. I learnt loads 👷‍♀️
@electrician247
@electrician247 10 ай бұрын
Glad it was helpful!
@mathewthomas1164
@mathewthomas1164 Жыл бұрын
What a brilliant video!
@electrician247
@electrician247 Жыл бұрын
To kind. Thanks
@jonnykay8820
@jonnykay8820 Жыл бұрын
Good stuff👍
@yngndrw.
@yngndrw. Жыл бұрын
A few things that I spotted, but I'm not sure if they are something you'd typically report on: 1) No clamp on the tails where they go into the main switch. (Not sure if that one is only for TT systems?) 2) The tails run over and touching a pipe from the heating system. 3) The "Do not store combustible materials near to this equipment" sign right next to the gas meter.
@electrician247
@electrician247 Жыл бұрын
The flapping cables under the CU could be one of them mate lol. Good spot!
@davidcarr291
@davidcarr291 Ай бұрын
Do NOT miss house bashing. A really great walk through video, lots of knowledge imparted in an easily comprehendabe manner. Got to admire your patter as well, some of the other guys make my brain commit sepu ku in under 5 minutes. I'd love to see what you'd make of the hotel refurbs i work on... Eternally bemused at what they get away with. Seriously you'd have a heart attack 😂. Still... I don't sign them off, so not my problem 😬🤠🙈🙉🙊
@electrician247
@electrician247 Ай бұрын
lol, yeah I’ve seen some shockers in the commercial world that’s for sure! Cheers mate.
@TheHomeent
@TheHomeent Жыл бұрын
Hi. Mark Did you get to the bottom of the extractor hood, whether it was on an isolator or prmantly wired in.? And just broken.
@edwardduffy6813
@edwardduffy6813 Жыл бұрын
Another great video and again full of content. What code did you give CU ?. Apart from the " hole " in top, would you C2 based on CU being plastic, understairs, no RCD or SPD ? Napit Codebreakers still saying C3 unless thermal damage. It is still the biggest bone of contention on EICR's....Thanks
@electrician247
@electrician247 Жыл бұрын
If its not showing thermal damage then C3 for me. However the sockets used outside I would C2. Makes a lot of sense to just upgrade in any case.
@somefin
@somefin Жыл бұрын
Good video👆
@electrician247
@electrician247 Жыл бұрын
Thanks
@ChristmasCrustacean1
@ChristmasCrustacean1 5 ай бұрын
interesting that the board has the split busbars for RCD protection and they were never utilised.
@jcf828
@jcf828 Жыл бұрын
Thanks for the upload. Just asking a question as I watch. How did you know the boiler spur was double pole just from looking at the external?
@electrician247
@electrician247 Жыл бұрын
I opened it and read the label 🤭
@3789gaz
@3789gaz Жыл бұрын
As always, brilliant content Mark! If I had a quid for every single time I forgot to switch a socket switch, I'd be able to buy David Savery (and Nige) a round or two. Just out of curiosity, did you tick TN-S or TN-C-S for the earthing arrangement on this EICR? I know the DNO typically won't guarantee TN-S if you enquire with them but physically it is a TN-S head but we know it's realistically going to be TN-C-S. Spotted something I didn't like the look of - the elbow union on what looks like the return/flow of the central heating system, which is directly above the electricity meter and with a bit of a green hue. I'd be concerned about leaks - could get interesting. Keep up the great work!
@electrician247
@electrician247 Жыл бұрын
Hi mate, thanks! Went down as a TNCS I know its PME in the street and tbh keeps me on the side of caution lol. Good Ze value as well.
@drpantastic1969
@drpantastic1969 Жыл бұрын
Im just at the point where you take the board cover off but im having to rewind a lot as you speak kinda fast lol just something i wanted to add.thanks for this video its helping a lot i actually passed my 2391-52 last year but have done no inspection or testing since and feel like im forgetting stuff i have been offered a testing role however im bricking it but im trying to watch video and will hit the books again.any tips you have would be grateful
@coreybart2783
@coreybart2783 6 ай бұрын
How did it go?
@EdwardBretherton
@EdwardBretherton Жыл бұрын
great video , would have been even better with codes , keep them coming
@williambrown1073
@williambrown1073 Жыл бұрын
Holes in surface mounted back boxes above cu.
@dssumner
@dssumner Жыл бұрын
Hi Mark, very interesting & informative video. Did you not show the Main Earth Ze test on purpose?
@electrician247
@electrician247 Жыл бұрын
Was careful not to make an entire how to, same as always. While showing plenty of stuff to try help apprentices. Plus at 45 mins this was a lot of editing effort/time.
@usoip8482
@usoip8482 7 ай бұрын
at the start you done the r1 r2 test is that big r1 r2 ?
@waithereivegonetogethelp3240
@waithereivegonetogethelp3240 Жыл бұрын
I think I would've taken the battery out of that smoke detector
@electrician247
@electrician247 Жыл бұрын
Didn't notice it at the time tbh
@Ultraharv1
@Ultraharv1 Жыл бұрын
@@electrician247 you mention it at 3:25 liar
@electrician247
@electrician247 Жыл бұрын
It was a joke Harvey. Quite clearly it was impossible not to notice 🤣. Relax a bit. Plus who goes around taking smoke detection out of service and disables alarms? Not a sensible person that's for sure. Have a good weekend #bekind
@LeighWinspear
@LeighWinspear Жыл бұрын
Another useful video for all, including us older sparks, newer to domestic electricks. Just wondering, how much time do you dedicate as a maximum per circuit whilst doing a typical EICR? Also, what is the average time for a full, dare I say, properly done EICR on a 3 bed home for example? Just to let the estate agents/landlords know a timescale. Then, how do you arrange the remedial work to ensure a pass/satisfactory inspection? Maybe another video..... Cheers n stuff.........;)
@barnabybot
@barnabybot Жыл бұрын
Yeah, I'm always suspicious of these videos when they've tested "properly". Yet manage to do it all in a suspiciously prompt amount of time. Would love to see a real time stopwatch in the corner and edited for easy viewing.
@cranefamily
@cranefamily Жыл бұрын
Mark is it me as you did not show everything in video but did you not test light switch for polarity switching ?
@electrician247
@electrician247 Жыл бұрын
Light switches are all checked Kevin. Didnt show the full thing but focused on a few bits. Still went on 45 mins which is a long video to edit lol
@tomistallard
@tomistallard 8 ай бұрын
Hi mate. Cheers for the video. I'm looking to do my courses next year and am looking at Multifunctional testers.... Can you tell me a list of tests that are needed for an ECIR so I can get a good tester now that can do the job.. Continuity Insulation Rcd (all types?) Etc Thank you. Keep up the good work. Regards Tom
@electrician247
@electrician247 8 ай бұрын
Thanks mate TIS eco and mft plus are the best options imho but we all prefer different things. The tests needed are in GN3 and vary a little based on the installation. But generally continuity, insulation resistance, Zs/Ze, pfc pssc, RCD. Other options are Ra for electrode measurement, phase rotation, EVSE, volt drop, power quality etc. The TIS mft does this
@tomistallard
@tomistallard 8 ай бұрын
@@electrician247 cheers mate
@duckman5642
@duckman5642 Жыл бұрын
Thats about the max time 45 mins on one +another 2 hrs for the bureaucratic paperwork.
@davewilson9472
@davewilson9472 9 ай бұрын
Please can I ask how long it roughly takes to get the inspection results/certificate once you've completed an inspection? Thanks
@electrician247
@electrician247 9 ай бұрын
We issue smaller certs same day. Larger programs longer as they require more time in review.
@squakkers
@squakkers Жыл бұрын
Did you change the batteries in the smoke alarm. I found myself having a “Here’s Johnny!” Moment
@electrician247
@electrician247 Жыл бұрын
No mate they need changing as way out of date.
@user-iz6sp6pe1r
@user-iz6sp6pe1r Жыл бұрын
How long the proses take for 3 bedrooms semi detached pls? Because the electrican i paid to do the checked only took him 10 minuted, please answer me, Thank you
@Stepho91x
@Stepho91x Жыл бұрын
I think these tests take around an hour so 10 mins seems very rushed! I would ask them why it was so quick & that you just want to make sure they did it properly.
@paulstimpson8977
@paulstimpson8977 8 ай бұрын
10 Minutes means your EICR is worthless. As for time that can vary quite a bit, is it empty like this one, stuff in the way, number of circuits etc A properly done EICR on a 3 Bed semi should be a couple of hours minimum imo.
@user-iz6sp6pe1r
@user-iz6sp6pe1r 8 ай бұрын
@@Stepho91x thank you, the electrician conned me indeed
@user-iz6sp6pe1r
@user-iz6sp6pe1r 8 ай бұрын
@@paulstimpson8977 thank you the electrician conned me indeed
@BowdenBuilders
@BowdenBuilders 3 ай бұрын
what do you use for the dual camera recording?
@electrician247
@electrician247 3 ай бұрын
Samsung Galaxy series phones do directors view recording
@chrissharpe2106
@chrissharpe2106 Ай бұрын
Just started doing EICRs and school boy errors are tripping me up. I spent an hour tracing a fault before I remembered my link was wrong side of a split load board.
@electrician247
@electrician247 Ай бұрын
It happens lol.
@billsbasementworkshop1902
@billsbasementworkshop1902 Жыл бұрын
Do you need an AFDD in a domestic property?
@persona250
@persona250 Жыл бұрын
Only if the premises is high risk for example HMO high rise flats .And only on socket circuits
@Mulisha0071
@Mulisha0071 5 күн бұрын
Nope.
@Saf_
@Saf_ Жыл бұрын
How come you don't pull the fuse and re seal it after?
@electrician247
@electrician247 Жыл бұрын
Because I don't
@Saf_
@Saf_ Жыл бұрын
@@electrician247 fair enough 😂 was curious if there was a legal reason or just personal preference
@electrician247
@electrician247 Жыл бұрын
@@Saf_ it is illegal to interfere with metering and dno equipment. Grey ish area
@scott4shell
@scott4shell Жыл бұрын
Where did you get that sexy r1+r2 clip I WANT ONE!!!
@electrician247
@electrician247 Жыл бұрын
The one in the light pendent? Those are TIS lightmate adaptors.
@scott4shell
@scott4shell Жыл бұрын
@@electrician247 I was talking about the crock clips one really good idea
@electrician247
@electrician247 Жыл бұрын
@@scott4shell ahh those are kewtech clips. Most wholesalers have them mate.
@scott4shell
@scott4shell Жыл бұрын
@@electrician247 Sweet thanks for the reply I use Edmundsons Sunderland and they don’t do kewtech I’m glad you replied and I watched your vid without people sharing knowledge you don’t know these things exist your a Star ⭐️
@MrImATarget
@MrImATarget Жыл бұрын
Don't do yourself down on the schoolboy errors. Error number two wasn't an error, you were simply testing polarity of the switching arrangement of the socket.
@electrician247
@electrician247 Жыл бұрын
I like it 🤣🤣🤣
@ef7480
@ef7480 Жыл бұрын
No PFC at origin?
@electrician247
@electrician247 Жыл бұрын
Of course but like I said, not a full testing run through. Was hard enough editing up 45 minutes worth lol.
@PT4LifeYO
@PT4LifeYO 8 ай бұрын
Replace for a class 2.
@pokaacyce
@pokaacyce 6 ай бұрын
Why would you not pull the main fuse? You are qualified, competent and doing so for your safety whilst performing the EICR, therefore nothing illegal.
@electrician247
@electrician247 6 ай бұрын
You are correct as we do work with the DNO. However without that DNO training I would be none of the above. It is illegal in any application without direct permission unless it’s an emergency situation. Not that anyone would ever be prosecuted. But for me and us it’s a no. Anyone admitting to the opposite should think very carefully. Especially on a public platform…..
@stevedebbiemoore
@stevedebbiemoore Жыл бұрын
The no trip test fools the RCD into not tripping, once upon a time the MFT used to flood the RCD with a DC current to achieve this, not sure if this is how the TIS works. Incidentally this is the reason why we need to use type A RCD's tied with an RDCDD in EV charging.
@barnabybot
@barnabybot 3 ай бұрын
One day a youtube spark will show a full timelapse video of testing rather than this Mary Poppins bullshit.
@electrician247
@electrician247 3 ай бұрын
One day all comments will be useful and productive rather than a vent at someone else sharing. The answer to your problem is make the content you want to see. Clearly not getting it here 🤣
@michaellack5139
@michaellack5139 11 ай бұрын
First thing first…..put smoke detector in garden ffs
@asarkiro
@asarkiro 2 ай бұрын
far too much waffling
@electrician247
@electrician247 2 ай бұрын
And yet not enough detail for some. Such is the way of sharing videos on KZbin. Have a lovely day
@n3ilvincent870
@n3ilvincent870 Жыл бұрын
Liked your video but I’m sorry. But you just talk to much
@electrician247
@electrician247 Жыл бұрын
Kinda the point of making a video and discussing it 🤣. Feel free to make a video how you want just like I did 💪
@mastergraphic9998
@mastergraphic9998 11 ай бұрын
How can you do a guidance video without giving guidance.... what did you want to watch someone just walking around inspecting and testing without any talking 😅
@electrician247
@electrician247 11 ай бұрын
@mastergraphic9998 I must do better lol. Can't help talking tbf I enjoy waffling 🤭
@mastergraphic9998
@mastergraphic9998 11 ай бұрын
@electrician247 lol love your video mate. Keep doing what ur doing and if they don't like them they don't have to watch... i always learn something useful 👍
Initial Verification - Testing someone else's crap work
32:55
SparkyNinja
Рет қаралды 272 М.
7 EICR FAILS - Inspection and Testing DEEP DIVE
1:05:42
Artisan Electrics
Рет қаралды 71 М.
Stay on your way 🛤️✨
00:34
A4
Рет қаралды 20 МЛН
Smart Sigma Kid #funny #sigma #comedy
00:26
CRAZY GREAPA
Рет қаралды 22 МЛН
НРАВИТСЯ ЭТОТ ФОРМАТ??
00:37
МЯТНАЯ ФАНТА
Рет қаралды 7 МЛН
Full Electrical Testing With DSES - House Rewire
35:21
N Bundy Electrical
Рет қаралды 61 М.
Earth Continuity Test
5:43
Master Electricians New Zealand
Рет қаралды 39 М.
How I do EICR Testing | Thomas Nagy
18:27
Thomas Nagy
Рет қаралды 109 М.
Teaching How To Do an EICR - Electrician Training Life
18:57
Artisan Electrics
Рет қаралды 106 М.
Just One HUGE SCAM?! 😤 The Problem With EICR's!
14:43
Artisan Electrics
Рет қаралды 30 М.
EICR Tips & Tricks for Beginners + Free Checklist | Electrician TV
15:09
Carrying out an EICR - an overview of what we do!
12:14
Justin Bucknell Electrical Ltd
Рет қаралды 13 М.
Electrical Channel - Testing Sequence - Dead
8:19
Warrington & Vale Royal College Electrical Training
Рет қаралды 101 М.