Replacing fire alarm system at elementary school. Full addressable replacement day #3/4

  Рет қаралды 18,254

NIC’S - SYSTEMS & ELECTRIC

NIC’S - SYSTEMS & ELECTRIC

Күн бұрын

Пікірлер: 87
@hobbesip1
@hobbesip1 8 ай бұрын
Lessons learned from software development that applies here: common courtesy indicators/colors will never be accurate when the lowest bidder did the last rush job. You can expect to track down the sum of everyone elses short cuts. Humans will always make a fool of hardware to software interfaces. Never quote a job without padding for the unexpected. You did very well, kid. Keep up the quality work.
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Thank you, I appreciate your comment. That is absolutely true!
@CmasterCXXV
@CmasterCXXV 8 ай бұрын
Excellent video. I have always been curious about the things that go on when replacing systems. Thank you for sharing!
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Glad you enjoyed thanks for the comment
@mikeross880
@mikeross880 8 ай бұрын
Coming along nicely and the new annunciator looks/fits great in the vintage Edwards cabinet. You are a genius Nic
@stevewilliam
@stevewilliam 8 ай бұрын
Next time you have messed up wire colors just take old devices down put bases up and wire nut + and - then when you're loop is powered up go around and meter polarity and install new devices it shouldn't be that difficult
@WilmingtonOHProductions
@WilmingtonOHProductions 8 ай бұрын
Thank goodness for removable detector heads when it came to tracking down that short
@FourtyFiftyEighty
@FourtyFiftyEighty 8 ай бұрын
damn that annunciator retrofit be saddening. But it do make sense
@a.r.aproductions1569
@a.r.aproductions1569 8 ай бұрын
Dude I felt the pain in everyone’s voice when those isolators all came on😭😂. Awesome work bro! Keep up the great work!
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
It was like a bad dream came true I think all of our hearts sunk into our stomach when we saw that lol
@TokkiLiin-p1z
@TokkiLiin-p1z 2 ай бұрын
The kids: what happened to the fire alarms???
@jimmysullivan6054
@jimmysullivan6054 Ай бұрын
I know most kids wouldn’t bat an eye but I definitely would’ve
@UKsystems
@UKsystems 8 ай бұрын
Wouldn’t you thing installing with correct colours is easier for the first person. ?
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
It didn't matter for the original install as it was conventional non-polarity sensitive
@tomewatson
@tomewatson 8 ай бұрын
Great video. You did a very good job under difficult circumstances.
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Thank you, I'm glad you enjoyed it!
@TejasGomadam
@TejasGomadam 3 ай бұрын
i like the scissor lift. it will be fun to ride on it.
@Siren_StrObE
@Siren_StrObE 8 ай бұрын
My old school, a very long time ago, only had ten detectors in the entire building but hundreds of sprinkler heads in every room, including bathrooms and storage closets
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
You wouldn't need heat detectors in the classrooms and any other rooms if you have automatic sprinkler heads
@Antenna300-gr5pk
@Antenna300-gr5pk 8 ай бұрын
Cool video man!
@Dilsonalarmsandradios
@Dilsonalarmsandradios 8 ай бұрын
Nic did you hit the table on purpose?
@craigbuchanan1126
@craigbuchanan1126 8 ай бұрын
yeah thought that was a bit rough
@EYL8902
@EYL8902 8 ай бұрын
Nice job! I like your content, keep up the good work.
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Thanks!
@reffthecanadien1328
@reffthecanadien1328 8 ай бұрын
Good stuff nic. Was looking forward to this episode!
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Glad you enjoyed it!
@reffthecanadien1328
@reffthecanadien1328 8 ай бұрын
Do you work for notifier by the way?@@nics-systems-electric
@firealarm421
@firealarm421 8 ай бұрын
Amazing video. Will there be a part 4
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Thanks, yes
@Pookie_Bear935
@Pookie_Bear935 6 ай бұрын
The fact that he just pushed the table with the scissor lift 5:35
@christopherrios8393
@christopherrios8393 8 ай бұрын
Is there any law that says there has to be heat detectors in the classrooms rather than smoke detectors? Do they put Heats for a reason or does it just not matter?
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
It's a direct one for one replacement and a smoke detector is not required in the classroom so it's cheaper to do heat detectors
@keithpierce8458
@keithpierce8458 8 ай бұрын
are you going to put system sensor l led series in the building
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Just watch the videos and you would know what was installed
@keithpierce8458
@keithpierce8458 8 ай бұрын
okay@@nics-systems-electric
@Julian_The_techie
@Julian_The_techie 8 ай бұрын
Very nice work!
@Siren_StrObE
@Siren_StrObE 8 ай бұрын
So few detectors in the gym but the classrooms get the same amount even though the gym is 5 times the size
@mattdude
@mattdude 7 ай бұрын
If I may ask, how did you start working in this industry?
@nics-systems-electric
@nics-systems-electric 7 ай бұрын
Started working with the school district electrical department for work experience hours and apprenticeship field hours
@drum-corps-fan
@drum-corps-fan 8 ай бұрын
Have had to swap devices at some schools in my district, and some of the older ones have horrible wiring just like this school. Surprised this one had it even in the '70s, as all of our schools built 70s onward have the correct polarity. Only the ones in the '60s have awful wire coloring. Weirdly, for whatever reason, polarity was like 95% correct in the school built in 1959, so I don't know how they went from good to horrible in about 2 years. Maybe it's just a different code thing or something, as I'm down in Wisconsin.
@victoriapedraza4514
@victoriapedraza4514 4 ай бұрын
Hi I live right in front of a elementary school and there’s always a false alarm that goes for hours and it seems like they fix it but then it comes back on.
@alarmsandamtrak
@alarmsandamtrak 8 ай бұрын
Will you start replacing with LED L-Series?
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Assuming they have been tested and listed for use in Canada CSA/ULC listed then they could theoretically be installed once they replace any old stock left of the xenon strobes
@zachlecave3906
@zachlecave3906 8 ай бұрын
The gym pull stations are the same at my school
@hotbytesB
@hotbytesB 8 ай бұрын
How can I send a picture to you?
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Instagram.
@All_ConsumingBandu
@All_ConsumingBandu 8 ай бұрын
Why are you replacing bells with horns? There's nothing wrong with bells. The only reason I can think of is that they die after a few years.
@achannelwithnopurpose1977
@achannelwithnopurpose1977 8 ай бұрын
System is no longer under grandfathered code. The newest revision of the fire code now applies as the system is being replaced and that does technically mean that a new system is installed which means you have to use the most recent fire code revision applicable and that code says synchronized horn-strobes that are 15db over ambient and use temporal 3 for signal coding are required.
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Because they need to be compatible listed devices and reliability is important when some of the bells are failing and you get lower draw with horn strobes and it is known model so easier for any calculations that need to be done
@adamcrane1436
@adamcrane1436 8 ай бұрын
Hello ​@@nics-systems-electric
@mimi2
@mimi2 8 ай бұрын
Also it wasn't nicks decision what devices to put up That would be the contractors. And it's cheaper to install horn strobes vs bell strobes. Both due to the device itself being costly, and because you might need more nac booster panels.
@jimstettler3445
@jimstettler3445 8 ай бұрын
current code requires speakers in K thru 12. They can be separate intercom or integrated in the fire alarm system. Regarding bells, they aren't as noticable
@JoshuaKing-qb4fj
@JoshuaKing-qb4fj 8 ай бұрын
is there going to be videos on the screwed up middle school?
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
I don't think so
@JoshuaKing-qb4fj
@JoshuaKing-qb4fj 8 ай бұрын
@@nics-systems-electric If you can please try I just wanna see how screwed up wireong for fire alarm in this school it's makes me happy seeing this school cause it never fails to have something wrong for us to enjoy
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
@@JoshuaKing-qb4fj the existing system wasn't installed super long ago so there shouldn't be too many problems with polarity as far as the SLC loop goes and the only issues that I can predict is not properly isolated zones but I don't think I will be around for that replacement
@JoshuaKing-qb4fj
@JoshuaKing-qb4fj 8 ай бұрын
@@nics-systems-electric what i would be exited for is seeing how yall are going to do with the wood shop duct collector
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
@@JoshuaKing-qb4fj it will need shut down so the contactor will be controlled by a control module I would assume but couldn't tell you for sure I won't be there for it
@pacfilming8117
@pacfilming8117 8 ай бұрын
how do you replace things like pulls and bells and not get zapped by exposed wires
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Fire alarm is low-voltage
@KanoaDeCastro
@KanoaDeCastro 8 ай бұрын
Wow! That wiring really is just awful. For the gym pull stations, given how toghtly they fit in the original backboxes, what if you used a backbox made specifically for those pulls? This would provide better space and prevent that broken resistor. (By a backbox, im talkikg sbout turning the stations surface mount)
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
It could be done if necessary however we try not to in the gyms it's the same reason that the pull stations are recessed in the new builds. Metal object like fire alarm and other electrical devices can leave nasty injuries in gymnasium from people running into them especially in an elementary school where they can be at face level for the students so we usually try and keep all objects as close to the wall as possible in gyms
@KanoaDeCastro
@KanoaDeCastro 8 ай бұрын
@@nics-systems-electric I completely understand that. As far as the injury concern, do kids still get injured from those metal pulls? If so, perhaps a good STI stopper can help prevent that due to it's rounded corners.
@drum-corps-fan
@drum-corps-fan 8 ай бұрын
​@@KanoaDeCastromight be regulation thing, I know some jurisdictions that don't allow stoppers for "lowering the simplicity of effectively operating the pull station" I think this regulation is kind of BS, given that you have to have an IQ of probably below 40 to not know how to lift a cover.
@KanoaDeCastro
@KanoaDeCastro 8 ай бұрын
@@drum-corps-fan I'm based in the United states so I don't know much about Canadian fire code, but I find that regulation pretty stupid.
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Stoppers can be used if needed though it usually isn't as from our experience they cause more problems than they solve
@eggfriedrice-gj8jc
@eggfriedrice-gj8jc 5 ай бұрын
Rip Edwards 6500
@Moonlight_Production1112
@Moonlight_Production1112 8 ай бұрын
i lov ur vids
@Colorblind_Guy
@Colorblind_Guy 8 ай бұрын
Hey, I’m colorblind! Put me in coach!!
@nekolivegaming
@nekolivegaming 8 ай бұрын
Well i guess thats what happens when you swap to a Adressable system where polarity matters from a system where "ah we are short on wire, ah its convetional so it dossent matter which color" lol
@eDoc2020
@eDoc2020 8 ай бұрын
Mixed up wiring seems to be a common issue in replacement installs. You'd think they'd just make the addressable devices polarity-insensitive to make it easier. I _think_ the addition of a ten cent bridge rectifier would make this possible but I'd need to know the details of the signaling to be sure.
@FireTech7
@FireTech7 8 ай бұрын
lol nice
@wibwabz
@wibwabz 8 ай бұрын
Do you think anyone working at Notifier watches your videos?
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Better not be watching me
@wibwabz
@wibwabz 8 ай бұрын
@@nics-systems-electric why?
@dutchwolf2675
@dutchwolf2675 8 ай бұрын
Great video! what happend to the fucked mps? keep up the great work.
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
I fixed it but it can't be used legally anymore
@dutchwolf2675
@dutchwolf2675 8 ай бұрын
yes makes sense@@nics-systems-electric
Fire alarm testing/verification of brand new notifier install at Elementary School
48:51
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 19 М.
Testing Both My Fire Alarm Systems And Back-up Generator/Emergency Lighting | October Testing
30:13
ДЕНЬ УЧИТЕЛЯ В ШКОЛЕ
01:00
SIDELNIKOVVV
Рет қаралды 3,4 МЛН
The selfish The Joker was taught a lesson by Officer Rabbit. #funny #supersiblings
00:12
Spongebob ate Michael Jackson 😱 #meme #spongebob #gmod
00:14
Mr. LoLo
Рет қаралды 11 МЛН
The Joker wanted to stand at the front, but unexpectedly was beaten up by Officer Rabbit
00:12
Yes, I still use a landline.
11:27
Surrealnumber
Рет қаралды 16 М.
Vintage Burglar and Fire Alarm System In A 1970’s Mansion
29:56
SHORT: Wilkinson Fire Alarm
5:41
Our Own Devices
Рет қаралды 10 М.
No Power Fire Alarm System Testing! August Emergency Testing.
30:23
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 11 М.
System Test 27:  NEW HOUSE!
21:34
FrostedStrobes
Рет қаралды 76 М.
ДЕНЬ УЧИТЕЛЯ В ШКОЛЕ
01:00
SIDELNIKOVVV
Рет қаралды 3,4 МЛН