I would never have suspected that BX would do that. You learn something new every day. Good work.
@subcoolHVAC Жыл бұрын
Yep, seen it quite often in older equipment. Didn’t really expect it on this newer unit . Thanks for watching!
@thesilentonevictor Жыл бұрын
Fantastic work tech
@jessemayra Жыл бұрын
Excellent work!…it pays to be diligent and thorough …well done
@subcoolHVAC Жыл бұрын
Thanks , yes it does
@jasonjohnsonHVAC Жыл бұрын
Good stuff brother. Nice find on the short. Awesome video
@subcoolHVAC Жыл бұрын
Thanks Jason, I like a good hunt 👍
@dougking7592 Жыл бұрын
You are exactly right brother, I would also replace with liquid tight to keep that from happening nice video
@subcoolHVAC Жыл бұрын
Thanks, definitely going back with liquid tight. Unit is just 2 yrs old too
@scaldinghotcoffee3206 Жыл бұрын
Nice find
@subcoolHVAC Жыл бұрын
👍 Thanks for watching!
@stevencossaboon3237 Жыл бұрын
Nice work Subcool. Thank you for the knowledge.
@subcoolHVAC Жыл бұрын
Thanks for commenting Steven 👍
@HenryMancini-rg3xm Жыл бұрын
Great find, keep up the good work
@subcoolHVAC Жыл бұрын
Thanks, will do!
@jaedenspider877 Жыл бұрын
I like how the entire room is used for the return duct
@subcoolHVAC Жыл бұрын
Yep, just don’t touch the walls, they’re fiberglass 😬 Thanks for commenting!
@jaedenspider877 Жыл бұрын
@@subcoolHVAC yw
@ccthepope Жыл бұрын
Good find!
@subcoolHVAC Жыл бұрын
Thanks r aeronca 👍👍
@c21meister Жыл бұрын
Had something similar happen yesterday with a intellipak vfd blower motor
@subcoolHVAC Жыл бұрын
Yep, not a fan of the flex conduit . Thanks for sharing 👍
@inothome Жыл бұрын
Wonder if that was the cause originally. I don't remember if that wire nut was actually worn through on the last video. I know it was definitely worn but don't remember if there were actual arc marks or conductive parts showing on it (and too lazy to rewatch it). And of course, moving those wires around could have cleared that rub through on the wires. But good example of how experience plays a part in troubleshooting. Knowing to look at the wires inside that BX on something that is vibrating or moving. Good call on going right to that.
@subcoolHVAC Жыл бұрын
No doubt the wire rub through was happening for awhile, originally the short to ground wasn’t present after removing the motor lead cover where the wire connector rubbed through and arced. Thanks for watching again!
@MrJujubean Жыл бұрын
Good catch
@subcoolHVAC Жыл бұрын
Thanks for watching 👍
@mwdub029 ай бұрын
Excellent attention to details. Love your channel bro.
@subcoolHVAC9 ай бұрын
I appreciate that 👍
@willfergusson724 Жыл бұрын
Cool Video.
@subcoolHVAC Жыл бұрын
Thanks for watching Will 👍
@PyramidHvac Жыл бұрын
GREAT JOB!!!
@subcoolHVAC Жыл бұрын
I appreciate you watching 👍
@moodyga40 Жыл бұрын
something is drawing some amps to pop a fuse cooked windings in the motor 2200 million ohms looks good
@subcoolHVAC Жыл бұрын
It was the direct short to ground on phase A. Motor is good. Thanks for commenting👍
@zekenzy64868 ай бұрын
Great Video. Thank you for sharing.
@subcoolHVAC8 ай бұрын
Thanks for watching!
@RoaddogRoaddog Жыл бұрын
Nice. I thought there was a motor starter on there. Should’ve the overloads have tripped before the blown fuse?
@subcoolHVAC Жыл бұрын
Good question, the fuse blew on phase A as a result of the current spike when the path shorted to ground protecting the wire. Overload relay protects the motor in an over current / thermal condition, more delayed reaction. When the fuse opened it also stopped supplying volts to one primary side of control transformer resulting in control power loss stopping the starter at same time.
@RoaddogRoaddog Жыл бұрын
@@subcoolHVAC hell yeah. Thank you for the education. Love the vids and the knowledge.
@subcoolHVAC Жыл бұрын
💯Thanks RoaddogRoaddog 👍
@syedbasheer2299 Жыл бұрын
👍👍👍
@stangaloski4208 Жыл бұрын
Great catch! What kind of air handler was it? Did it come from the factory in that or was it wired by electricians like that?
@subcoolHVAC Жыл бұрын
It’s a York, looks like it was field wired by electrician. Thanks for commenting
@wd8557 Жыл бұрын
Good catch, my megger would have caught that.
@subcoolHVAC Жыл бұрын
That’s what I thought too 👍
@josephradford96655 ай бұрын
What type of megaohm meter was that? Fairly new to HVAC and i appreciate the lessons
@subcoolHVAC5 ай бұрын
Fluke 1503 insulation tester, Thanks for watching! All the best 👍
@rickbarber67587 ай бұрын
Curious why they don't connect the return air directly to the air handler?
@subcoolHVAC7 ай бұрын
The air handler room is the return plenum, old design new units