TRANE RTHD Loss Of Oil Alarm… RTHC No Evap Flow … Both Chillers Not Working Call

  Рет қаралды 6,326

Subcool HVAC

Subcool HVAC

5 ай бұрын

Got a work order for chillers not resetting and buildings are warm , weather has been rather cold lately…here’s what I found #chiller #hvac #trane #hvacrepair
youtube.com/@jasonjohnsonHVAC...

Пікірлер: 28
@jasonjohnsonHVAC
@jasonjohnsonHVAC 4 ай бұрын
Very nicely done. Handled it like a pro. I have ringing ears when i get around those RT's....the loudest screw ever i encountered was a RTHB. I especially like how you methodically and slowly brought the current up and allowing it time to stabilize in-between. One of the my favorite videos yet.....and they've all been excellent. Love the channel
@subcoolHVAC
@subcoolHVAC 4 ай бұрын
Thanks Jason, I had a site with RTHB chillers , the oil baffles had cracked/broken. Replaced and broke again. The noise was horrible, you couldn’t be in the room the harmonics were so bad. Neighbors would complain several blocks away. Chillers finally got replaced.
@topher8634
@topher8634 5 ай бұрын
I had the same problem back in December, the drives has a enable command fault and the tower fans were not coming on. It was a warm day here in central Georgia and they were needed, so I put them in hand and the temp plummeted overnight to the 30s. Next morning both chillers were in alarm for loss of oil and no differential refrigerant pressure. Took me 3 tries of restarting, alarming, then the "no differential refrigerant pressure" timer had to expire before it would let me restart it. 30 minutes each time. Had to get Trane out and reprogram the algorithm for bringing fans on. They had it wrong. It was only looking at one chillers condenser water temp so when it was shutdown, the water was never reaching the enable setpoint of the drive. Great video, I enjoy this type of content.
@subcoolHVAC
@subcoolHVAC 5 ай бұрын
That’s a good call, RTHD doesn’t like cold condenser water for sure.
@douro20
@douro20 5 ай бұрын
R134A screw chillers? Good thing they have the cooling tower drives indoors- I hate seeing those things outside where the heat will get to them.
@subcoolHVAC
@subcoolHVAC 5 ай бұрын
Yep R134a screws, I prefer them indoors too. Thanks for the comment
@user-lq4yx1ee2t
@user-lq4yx1ee2t 4 ай бұрын
You are awesome man I have learned a lot from your videos please keep them coming, you got my support you got my vote I will vote for you if you decide to run for presidency one day .
@subcoolHVAC
@subcoolHVAC 4 ай бұрын
Thanks for the support 👍 think I’ll stick to HVAC
@zekenzy6486
@zekenzy6486 4 ай бұрын
Great Video. Thank you for sharing. Have a nice weekend. I'm new to chiller.
@subcoolHVAC
@subcoolHVAC 4 ай бұрын
You too, Thanks for watching!
@hvacrnortheastern2110
@hvacrnortheastern2110 29 күн бұрын
Great job that surprised at they didn’t know chiller were off whole week or having problems l operate a #2 YK York 800 ton chiller we have alarm when chiller go off on an warning or any chiller pump and cooling pumps or any other problems we have the in the utility plant l guess that they doing a big project hated when they upgrade and the cause a problem due to the construction.
@subcoolHVAC
@subcoolHVAC 29 күн бұрын
Yeah EMS doesn’t have alarms enabled at these sites during unoccupied or occupied times, building maintenance has to check physically… Thanks for commenting 👍
@georgebrabec1749
@georgebrabec1749 4 ай бұрын
I don't know what the money spent limit was with this install, but a water temp control valve operated from the chiller commands can control the condensing temp. along with the VFD's to control feed temp. to the chillers. Also could use a tower by-pass valve that would operate when the VFD gets to 30%. I probably saud too much as I know that you are a great chiller tech. and you know what you are doing.
@subcoolHVAC
@subcoolHVAC 4 ай бұрын
Yeah, I know. This is an older installation and unfortunately it was most likely lowest bid. Thanks for the comment 👍
@ccthepope
@ccthepope 5 ай бұрын
Wow, yo smart man!
@subcoolHVAC
@subcoolHVAC 5 ай бұрын
😎Just a guy that shows up to work. You’re faithful 👍
@garbo8962
@garbo8962 5 ай бұрын
See they have both ABB & Danfoss VFD'S. Good luck with snob nogoodnic ABB tech support. They always gave me the fifth degree when I contacted them. Took me 5 E mails & ten days for ABB to finally tell me how to locate the DC Buss voltage off the touch screen. Asked me no interrogated me why the need to know that. Da have to put it on PM form & use it to trouble shoot. If you have over 655 volts DC Buss voltage on a three phase 480 volt drive then all three line fuses are good and line voltage is not low. Contractor that installed over 50 POS ABB drives kept the manuals. Danfoss tech support never let me down. Wonder what guys think of JCI chiller drives that on our 100HP units used cold water to keep drive from getting too hot. They cut corners by using flimsy plastic water hose fittings for cold water right over the drives. Guess during water leaking would blow up the 480 volt drives.
@subcoolHVAC
@subcoolHVAC 4 ай бұрын
I think Danfoss Is ABB also
@sterlingarcher46
@sterlingarcher46 5 ай бұрын
Nice one 👍 Just wondering, does the tower shut the fans off completely passed a low condenser water temperature setpoint ? Or is there some kind of low ambient proof system . Cheers mate 👍.
@subcoolHVAC
@subcoolHVAC 5 ай бұрын
They do turn off once setpoint is achieved. Minimum speed is 20hz though when signal given to start
@sterlingarcher46
@sterlingarcher46 5 ай бұрын
@@subcoolHVAC I didn't quite understand why water temp got so low . I'm kinda slow sometimes to be fair ...
@subcoolHVAC
@subcoolHVAC 4 ай бұрын
Ambient temperature had dropped into the 40’s which doesn’t happen often here causing the drop. Thanks for the questions!
@joeyoung2834
@joeyoung2834 5 ай бұрын
Do they not have any economizers for the ahus?
@subcoolHVAC
@subcoolHVAC 5 ай бұрын
Precoolers being installed with new ahus
@marcobeltrandiaz3954
@marcobeltrandiaz3954 17 күн бұрын
Los of oil at compresor, do You know what is the cause?
@subcoolHVAC
@subcoolHVAC 16 күн бұрын
Here it was oil had migrated to condenser with low ambient conditions
@isaiahsmith1933
@isaiahsmith1933 5 ай бұрын
Are the drives off the chiller or the BAS?
@subcoolHVAC
@subcoolHVAC 5 ай бұрын
Independent off the T775 Tstat.
Каха заблудился в горах
00:57
К-Media
Рет қаралды 5 МЛН
УГАДАЙ ГДЕ ПРАВИЛЬНЫЙ ЦВЕТ?😱
00:14
МЯТНАЯ ФАНТА
Рет қаралды 4,2 МЛН
Ice-O-Matic CIM Error Light Diagnostics
7:21
techtown
Рет қаралды 8 М.
How to replace a refrigeration compressor
38:49
Nor-Cal Refrigeration & H.V.A.C
Рет қаралды 12 М.
Troubleshooting A Call Back For Air Handler Down
12:16
Subcool HVAC
Рет қаралды 2,8 М.
WOW! SMART idea and very USEFUL 👓 👁 p5 #camping #survival #bushcraft #outdoors
0:17
Ăn Vặt Tuổi Thơ 2024
Рет қаралды 72 МЛН
Waka Waka #10 🤣 #shorts #adanifamily
0:15
Adani Family
Рет қаралды 8 МЛН
Проверил, как вам?
1:00
Коннор
Рет қаралды 6 МЛН
Телега - hahalivars
1:00
HAHALIVARS
Рет қаралды 5 МЛН
На сколько опасна рыба меч?
0:40
Fact Fusion
Рет қаралды 2,9 МЛН