Troubleshooting the Pressure Switch in a Gas Furnace!

  Рет қаралды 36,306

AC Service Tech LLC

AC Service Tech LLC

Күн бұрын

Пікірлер: 57
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Tool List- www.amazon.com/shop/acservicetech Support- www.patreon.com/acservicetech For those that are looking for the tools used in the videos: (Linked Below) UEI Digital Dual Manometer- amzn.to/2CWC6BD Fieldpiece SDMN6 Dual Pressure Testing Manometer with Pump-amzn.to/2jyK5Ka UEI DL479 Multimeter with temp sensor- amzn.to/2jtsUbJ 3/16" x 3/16" x 3/16" brass barbed tee- amzn.to/2INSRhQ 1/8" NPTF x 3/16" barb fitting for reading wc pressure- amzn.to/2G563Bq Supco Universal Adjustable Pressure Switch -.01wc -10.0wc amzn.to/2G1y0py Supco Magnet Jumpers amzn.to/2gS4h6z 2 pairs of alligator clips- amzn.to/2CtIL5z Here is the Link for the Yellow Jacket Refrigerant Manifold Gauge Set used in the videos amzn.to/2aenwTq Here is a link to Refrigerant hoses with valves used in the videos amzn.to/2aBumVI Here is a link for RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn Here is the link to the Appion Valve Core Removal Tool- amzn.to/2uYr8WL Here is the link for the Ratcheting Service Wrench amzn.to/2dGV4Nh Here is the link to the CPS Vacuum Micron Gauge- amzn.to/2v1nM3O Here is the Link to the Appion Blue 3/8" to 1/4" Vacuum Hose- amzn.to/2uYlVyc Here is the Link to the Appion Red 3/8" to 1/4" Vacuum Hose- amzn.to/2uYg6Ro Here is the link to the Yellow Jacket 1/4" by 1/4" heavy duty hose straight- amzn.to/2umtcod Here is the link to the pack of 25 C&D valve cores- amzn.to/2J1lurm Here is the link for the C&D Valve Core Wrench, Container, and 3 valve cores- amzn.to/2EVGkps Other tool links can be found in the video description section. Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal- www.amazon.com/shop/acservicetech All of the ACSERVICETECH Playlists- kzbin.info/door/OZR-1IqsAer9wzlvFgb4mAplaylists?view_as=public
@nurfetalic205
@nurfetalic205 6 жыл бұрын
For new technicians this is the gentleman that you have to pay attention it will teach you all kinds of stuff and believe me you got to have a little patient and down the road you going to be just fine he's got a lot of knowledge to share with you guys. Craig well done as allways.
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks a lot Nurfet Alic!
@truthfiend6909
@truthfiend6909 3 жыл бұрын
not only for the new techs , this channel is the best HVAC channel there is imo...ve been in the trade for more than a decade and i'm still learnin new things watching his vids
@drifter436
@drifter436 6 жыл бұрын
You are the best on KZbin sir. You have the gift to teach. Thank you for all these videos , they are a huge help.
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks Drifter436!
@Digitaldendo
@Digitaldendo 6 жыл бұрын
Just getting started in the industry with 2 levels of school, this channel is great Thank you.
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks a lot Dennis!
@chriscooper9729
@chriscooper9729 6 жыл бұрын
Thank you very much. I'm a new technician I need all the help I can get your videos or not just informative but their inspirational as well.
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Well thank you very much Chris! I really appreciate your note!
@whitesheatingairappliancer7101
@whitesheatingairappliancer7101 6 жыл бұрын
You are a great teacher. I will use this setup for troubleshooting. Thank you for the video.
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks Ron!
@ejohnfall
@ejohnfall 6 жыл бұрын
Thanks again perfect time it started to get cold
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks ejohnfall!
@bills6946
@bills6946 Жыл бұрын
You can tell an instructor from a KZbin service Technician. A technician will usually slip in something bad about Goodman, because Goodman doesn’t pay companies incentives like some other brands. An instructor will teach you that if you install a system correctly, they are all good
@burg5556
@burg5556 Жыл бұрын
Arrived at service call. Wiped top cabinet with a rag. Conclusion: its goodman
@stephens1950
@stephens1950 3 жыл бұрын
Just replaced a pressure that was BAD. The replacement just gave me problems after a week of working. Thoughts?
@caseyfike226
@caseyfike226 2 жыл бұрын
Thank you for your great content & sharing your expertise with us. But 1 question I have that I've wondered is, say the furnace goes through its sequence and starts heating. What if the pressure switch opens back up after it's already started heating, will the system shut back down or will it wait until next start up cycle. Thank you so much again.
@ghleader2179
@ghleader2179 6 жыл бұрын
Thnx for your video, i love your Chanel.
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks GH Leader!
@gilbertopatino2616
@gilbertopatino2616 6 жыл бұрын
Thank you very much for another great video 👍👍👍👍🇺🇸
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks Gilberto Patino!
@davidhazas7162
@davidhazas7162 2 жыл бұрын
I've found the water column rating for the pressure switchs on the actual schematic in small writing in some cases.
@robcarnaroli269
@robcarnaroli269 6 жыл бұрын
Great video but now I'm dying to know what was the blockage!
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
This was a birds nest scenario, thanks Rob!
@MrDmadness
@MrDmadness 6 жыл бұрын
ha, pulled a squirrel carcass from one today with my k 50 cables.
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Ha ha wow!
@BoffinGrusky
@BoffinGrusky 6 жыл бұрын
Well done!
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks Watcherjohnny!
@johnsonvideos1450
@johnsonvideos1450 Ай бұрын
hi i have the 24v going from pressure switch back to control board but still not moving to next sequence i think i have abad board?
@Rezcat-y6r
@Rezcat-y6r 6 жыл бұрын
Hey my friend. I’m still going to purchase a dual manometer but without it the furnace does everything. Cfm on, pressure switch closed, HSI lit, burners on with a flame sensor, then off 4-7 seconds.
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Sounds like flame rectification, board or pressure switch but you would need to test each function individually, thanks
@fazesenso2864
@fazesenso2864 10 ай бұрын
Hello! I noticed that you had the positive port of the manometer hooked to the - Side of the switch (more of a vacuum ) . And the negative port of the manometer hooked to the + side of the switch that connects to the burner box which is atmospheric. For ur differential. Is that a mistake ? Or does it not matter ??? I’m a new technician out of school and I am constantly running into pressure switch issues and I am trying to really grasp what readings I’m looking at and what readings I should have 100%. So I am not just guessing
@chrisswofford5757
@chrisswofford5757 2 жыл бұрын
Could you do a video about correctly hooking up manometer hoses in line with pressure switches? I always get mixed up.
@acservicetechchannel
@acservicetechchannel 2 жыл бұрын
look up "acservicetech pressure switch" and "gas furnace component history"
@benkuxhouse787
@benkuxhouse787 6 жыл бұрын
Great video. I've been doing HVAC for a 30 years 33 to be exact and have never had a really good procedure on very tough pressure switch problems. I work for a school district now and don't have to deal with it as much but we still have some furnaces there. How did you figure out it was the induction tube by your pressures that you were reading? Cuz they both right about the same. What I've done in the past is I've just disconnected both the supply in the exhaust and see if it would come on to see if it is the exhaust or intake piping. Real good video and I know it's going to help me in the future but how did you figure that one out by just looking at those pressures that it was the intake?
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
You are right, I just opened up the combustion air inlet and the pressure changed. Also, when the inducer is high enough to allow the pressure switch to close and the intake is just as high then you know the problem is on the intake or heat exchanger side, thanks
@benkuxhouse787
@benkuxhouse787 6 жыл бұрын
@@acservicetechchannel how would you know if you had a problem with the heat exchanger looking at those readings?
@greghuber9773
@greghuber9773 Жыл бұрын
If you can’t suck right , there’s not much air to push ! Like if you put a box fan against a wall , you won’t get much air flow on the outlet !
@Matthew-jr1xr
@Matthew-jr1xr Жыл бұрын
Im wondering why on a new install why sometimes priming the drain trap is needed so the pressure switch makes but then the same issue is present when the trap is clogged..🤔
@johnaries9301
@johnaries9301 2 жыл бұрын
Can you wire a pressure switch backwards?
@geojor
@geojor 6 жыл бұрын
enjoyable to watch ...
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks Pei Broker!
@mark.r8900
@mark.r8900 6 жыл бұрын
hi, so on the + side of the pressure switch the vacuum is created through the heat exchanger? is this correct? thanks.
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
yes correct, thanks
@CheiithooCat
@CheiithooCat 6 жыл бұрын
Awesome...
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks N Eliseo S Carranza!
@heatncool
@heatncool 6 жыл бұрын
Sweet. Look forward to your videos! I get to be the first comment 😋😀
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks Daniel!
@clintglasgow5633
@clintglasgow5633 6 жыл бұрын
👍
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Thanks Clint!
@madurasenju2015
@madurasenju2015 6 жыл бұрын
One small questions . I get the pressure switch hose that runs directly to the inducer . But right here I see it hooks up to the gas valve then goes to the burners to just have a hoe inside the cage burners . ? Why ?! Can you please explain throughly . Thank u
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
That is so that the atmospheric pressure at the burners remain the same as at the gas valve so there is no problems with the flame or at the pressure switch!
@الجمهوريةالشيطانيةراعيةللارهاب
@الجمهوريةالشيطانيةراعيةللارهاب 6 жыл бұрын
Can this furnace be used for a down flow application ?
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Yes it is can be installed horizontal right, horizontal left, upflow or downflow, thanks
@الجمهوريةالشيطانيةراعيةللارهاب
@الجمهوريةالشيطانيةراعيةللارهاب 6 жыл бұрын
AC Service Tech LLC thank you very much Craig
@acservicetechchannel
@acservicetechchannel 6 жыл бұрын
Glad to help Thomas!
How the Gas Furnace Pressure Switch Works & Testing!
15:50
AC Service Tech LLC
Рет қаралды 33 М.
The Real Operation of a PRESSURE SWITCH in a GAS FURNACE Heater! Also Testing!
13:37
ТВОИ РОДИТЕЛИ И ЧЕЛОВЕК ПАУК 😂#shorts
00:59
BATEK_OFFICIAL
Рет қаралды 7 МЛН
How To Choose Mac N Cheese Date Night.. 🧀
00:58
Jojo Sim
Рет қаралды 115 МЛН
What type of pedestrian are you?😄 #tiktok #elsarca
00:28
Elsa Arca
Рет қаралды 42 МЛН
Why no RONALDO?! 🤔⚽️
00:28
Celine Dept
Рет қаралды 101 МЛН
How to Test Pressure Switch on a Furnace
14:14
Word of Advice TV
Рет қаралды 650 М.
HVAC Thermal Limit Switches, Safety Sensors, & Troubleshooting!
16:22
AC Service Tech LLC
Рет қаралды 180 М.
Gas Furnace SPARK IGNITION Operation and Testing!
17:07
AC Service Tech LLC
Рет қаралды 100 М.
Furnace Pressure Switch Troubleshooting
16:57
Word of Advice TV
Рет қаралды 853 М.
Gas Furnace Parts and Functions! Operation Explained!
18:46
AC Service Tech LLC
Рет қаралды 246 М.
Prevent this Common Manometer Mistake
3:57
HVAC School
Рет қаралды 55 М.
Checking Furnace Pressure Switches
10:53
Tec Tube
Рет қаралды 52 М.
NO HEAT? Top 10 Problems on a Gas Furnace Package Unit!
13:18
AC Service Tech LLC
Рет қаралды 128 М.
ТВОИ РОДИТЕЛИ И ЧЕЛОВЕК ПАУК 😂#shorts
00:59
BATEK_OFFICIAL
Рет қаралды 7 МЛН