How to check the windings of a refrigeration compressor

  Рет қаралды 488,150

grayfurnaceman

grayfurnaceman

Күн бұрын

Пікірлер: 126
@andrewmack5146
@andrewmack5146 9 жыл бұрын
Well done you would be amazed how many engineers do not know this and how to check a compressor
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@doncocorote1
@doncocorote1 5 жыл бұрын
I have learned more with your videos than school. Thanks 🙏🏼
@grayfurnaceman
@grayfurnaceman 5 жыл бұрын
Welcome GFM
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@MrBlaklip
@MrBlaklip 12 жыл бұрын
I really appreciate your simplicity along with a visual of your meter readings
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@yongminhuh5605
@yongminhuh5605 7 жыл бұрын
You're so right! This ac hasn't been used for 20 years. I finally got it started it worked for 10 to 15 seconds, and then there were arching and fire burning of dead bugs, spider web and dried grass, etc.... I shut breaker off, and waited for 5 mins and then restarted it worked a several seconds there again arching and burnt rest of those stuffs. And then it finally died. I restarted again now just humming bird. I gave a closer look at contactor there are metal burnt color. I guess I have to replace contactor. Thanks!
@grayfurnaceman
@grayfurnaceman 7 жыл бұрын
Welcome GFM
@grayfurnaceman
@grayfurnaceman 11 жыл бұрын
Yes. When the 2 windings are read in series (R to S), they should read the total of R to C and S to C. Hope this helps. GFM
@christiand.6112
@christiand.6112 7 жыл бұрын
grayfurnaceman What if you have 2.1 between common and run and 2.3 between common and start but only have 3.2 between start and run? Shouldn't I have 4.4 between start and run?
@arnelespena5469
@arnelespena5469 11 жыл бұрын
Thanks for the upload of this video. I learned a lot!
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@grayfurnaceman
@grayfurnaceman 12 жыл бұрын
OL means there is no continuity. Windings should have continuity from one end to the other. Windings should not have continuity to the body of the compressor. Hope this helps. GFM
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@SamsFootballFreestyle
@SamsFootballFreestyle 11 жыл бұрын
nice video man good tutorial even ppl who dont understand can understand this video
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@mpugliano
@mpugliano 12 жыл бұрын
Well done great video ty very much!!!! I liked it so much i even watch the advertisement hope it puts a few cents in your pocket!
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@grayfurnaceman
@grayfurnaceman 11 жыл бұрын
The meter is a Fluke 16, now replaced with the 116 and is a megohm meter. Also, some techs use an insulation tester to test the winding at a high voltage, which the windings are exposed to. For me the jury is still out on these meters, as they may diagnose a compressor as bad that may not actually fail for some time. Certainly, if the unit is high liability such as a blood cooler, I would use them. GFM
@grayfurnaceman
@grayfurnaceman 12 жыл бұрын
It is single phase. If it was 3 phase, it would be the same resistance on all 3 legs. GFM
@PigSpinnin
@PigSpinnin 8 жыл бұрын
test worked perfect. Helped me narrow the prob to a bad cap. Thanks for posting this!!!!
@grayfurnaceman
@grayfurnaceman 8 жыл бұрын
Welcome GFM
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@ChrisV-
@ChrisV- 10 жыл бұрын
Good video, just starting to get into hvac myself.
@stanleysanders8310
@stanleysanders8310 10 жыл бұрын
Thanks alot
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@grayfurnaceman
@grayfurnaceman 11 жыл бұрын
I'll try to keep them coming. GFM
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@jgvaz
@jgvaz 11 жыл бұрын
Nice explanation. Is your fluke multimeter suitable for windings insulation test to ground? Shouldnt it be a megohmeter with higher voltage to be sure theres no fault to ground? Thank you
@spamh3591
@spamh3591 6 жыл бұрын
Another great video!
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@Hvacmaniac97
@Hvacmaniac97 Жыл бұрын
Thank you gray!!
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@AJRestoration
@AJRestoration 10 жыл бұрын
Good video!
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@mtbbiker6401
@mtbbiker6401 5 ай бұрын
I can't access the compressor plug directly (5 ton Trane unit), but I checked it at the wires after disconnecting from the contactor and capacitor. My numbers are 1.0, 1.4, 2.0 so my total is off by -0.4. Does this mean the compressor is going bad? No grounding issues. It's currently pulling 21.5A (105 degrees ambient temp) on the common wire (followed your other video). RLA is 26A. It's a 14 year old 5 ton Trane R410 heat pump. The compressor is noisy at start/stop but otherwise seems to run okay.
@grayfurnaceman
@grayfurnaceman 11 жыл бұрын
Thanks for the support. GFM
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@goonzsquad1
@goonzsquad1 8 ай бұрын
So Gary your not actually putting your leads inside the terminal, just clipping to that metal part ?
@jonerasmus9399
@jonerasmus9399 Жыл бұрын
Make a vid of testing a single phase motor without marked leads plz .
@baderfrdan447
@baderfrdan447 4 жыл бұрын
Does the decrease in the resistance value between the common terminal and the start terminal imply that the compressor is malfunctioning? Example, the resistance between the common & start is 1 while the resistance between the common & the run is 1.3 (resistance total between run & start is 2.3). Noting that the compressor needs a start capacitor to make it running. Without that start capacitor, the compressor cannot work. So, two questions are here: 1. Do these resistance values indicate an issue with the compressor? 2. Does this need of start capacitor to start the compressor indicate that there is an issue with the compressor? Thanks
@grayfurnaceman
@grayfurnaceman 4 жыл бұрын
First, the resistance values should be compared to the factory specs. Generally, the resistance of the run to common will be the lowest. If you are saying the compressor will not start without a start capacitor, and the start cap was not original equipment, either the compressor is on its last legs or the run capacitor has failed. GFM
@grayfurnaceman
@grayfurnaceman 12 жыл бұрын
Ok. I misunderstood your comment. Are you using a digital ohmmeter? Set at the X1 setting? Is it a very small compressor? GFM
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@kevinvu2009
@kevinvu2009 10 жыл бұрын
It's old . But old is good. Sometime you are getting ohm reading good but compressor lock out then you looking for the new compressor.
@SamsFootballFreestyle
@SamsFootballFreestyle 11 жыл бұрын
wondering if theres any other important tests i should preform if i find a old or new compressor laying around to make sure its working properly etc
@grayfurnaceman
@grayfurnaceman 12 жыл бұрын
The reason I asked is the numbers are too small. Most compressors will have single digit resistance in their windings. GFM
@feenixb1o7
@feenixb1o7 12 жыл бұрын
I have 2 at 17 and 1 at 34... which is the run and which is start? So I know which is the common and that the two pins remaining are either run or start, but how do I tell which is which?
@emptech
@emptech 6 жыл бұрын
I'm assuming you are using those new test leads that have zero resistance? Wouldn't you first short the leads together, find their approximate resistance, could be a few tenths of an ohm and subtract that value from your total resistance? To eliminate the error from the lead resistance, some people would use a four wire ohmmeter. Readingss of hundreds of ohms or more, who cares about a few tenths of an ohm, but when measuring resistances of about half an ohm, a few tenths of error can be quite significant, would you think? Jim
@grayfurnaceman
@grayfurnaceman 6 жыл бұрын
As the potential resistance of the probes will be always the same, and the readings of compressor windings are comparative, I do not think it is necessary. And in fact, I have not seen the resistance of the leads be anything other than 0. GFM
@bensenoussitahri7034
@bensenoussitahri7034 6 жыл бұрын
thank you ,i found a good informatios here , i just want to ask you a question ,can we fix the windings of three-phase compressor?
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@samuraix8903
@samuraix8903 10 жыл бұрын
Hi, do you have a video on how to check on a 3 phase HVAC compressor windings? I recently have the compressor breaker tripping and I found out due to the compressor having no continuity on all phase ( L1-L2, L1-L3 & L1-L3 ). I also found the resistance to be very high.. around 300ohms between L1-L3 & L2-L3. Can i conclude that the compressor breaker trip due to the compressor bad/Open winding? I check the breaker & contactor, they are OK.I found so many videos here & i found yours to be the most helpful. Thanks in advance.
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@myraza86
@myraza86 11 жыл бұрын
Thanks alot.. Hope to see more good stuff like that.. :)
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@grayfurnaceman
@grayfurnaceman 12 жыл бұрын
If you know common, then hold probe on common. Touch other probe to a terminal and record. Then touch probe to remaining terminal and record. The higher number is start and the lower number is run. If you still are having trouble I can send you a diagram. GFM
@U-TUBER88
@U-TUBER88 2 жыл бұрын
Hello sir will u give the diagram Student from India
@allykeyes8171
@allykeyes8171 4 жыл бұрын
Hi. Thanks so much for your video here and BIG THANKS for explaining how to understand Ohm readings between C, R & S when l didn't know what they should be in the first place. I'm just using a basic cheap multimeter and assuming that '1' is equivalent to O.L. I hope I'm correct? As l cannot afford a high end Fluke such as the two you've mentioned (16 & 116), could you tell me what you think of the 101 model please? I'm new to electronics although I've been trying to understand how to accurately use a multimeter for years (and getting nowhere.. Lol). Cheers.
@jaileal8806
@jaileal8806 3 жыл бұрын
1 is equivalent to OL. :)
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@TripCoolLang
@TripCoolLang 3 жыл бұрын
Thanks!!!
@robviolin1
@robviolin1 11 жыл бұрын
Great vid. Thanks
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@venkatkasa5819
@venkatkasa5819 5 жыл бұрын
I couldn't understand clearly. Is that winding good or not. Usually when I checked motor or anything winding the good winding is denoted to three phases equal resistance of winding. That the winding is correct but here not like that
@grayfurnaceman
@grayfurnaceman 5 жыл бұрын
The winding is good. It is a single phase compressor. GFM
@yongminhuh5605
@yongminhuh5605 7 жыл бұрын
If I sent you a few pictures, can you tell me where did those wires came off? I believe those wires came off of relay but there are no visible sign( no screws joints, etc... May be grounded or chassis I don't know.
@grayfurnaceman
@grayfurnaceman 7 жыл бұрын
I can try. Send to Grayfurnaceman@gmail.com GFM
@danielpadilla3968
@danielpadilla3968 6 жыл бұрын
How do you know if the windings are going bad? Sorry if it’s a dumb question
@grayfurnaceman
@grayfurnaceman 6 жыл бұрын
If the resistance of each winding matches the manufacturer specs and there is no continuity to ground, the windings are ok. Not dumb. GFM
@GuruHandyman
@GuruHandyman 11 жыл бұрын
Loved Evercoat commerical
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@yongminhuh5605
@yongminhuh5605 7 жыл бұрын
Thanks for responding to my questions! I think I figured it out where those wires are broken off - compressor relay. I wish if there's a way to send email.
@grayfurnaceman
@grayfurnaceman 7 жыл бұрын
You can send to Grayfurnaceman@gmail.com GFM
@stanleysanders8310
@stanleysanders8310 10 жыл бұрын
I have a trane dual unit heat pump the fan on top of the motor want shut off.but thermostat cuts fan off that blows through duct work into house.what is the reason fan outside want shut off?
@grayfurnaceman
@grayfurnaceman 10 жыл бұрын
Stanley Sanders I assume you mean the outdoor fan won't shut down. It could be the contactor in the outdoor unit is stuck on. If so, it needs to be replaced. GFM
@feenixb1o7
@feenixb1o7 12 жыл бұрын
14 ohms doesn't seem that small to me, maybe the compressor is shorted somewhere. Thanks for your help though :)
@grayfurnaceman
@grayfurnaceman 12 жыл бұрын
Thanks, Is that a ferret?
@Ryan96se
@Ryan96se 8 жыл бұрын
I got exactly what he got here. 3.0 / 2.5 / 0.5 but my compressor just shakes hums then clicks off. Tested the start run capacitor (only 5mo old) and MFD tested good on it. Contactor is sending 240V so I guess my compressor has a mechanical failure like a seized piston correct?
@grayfurnaceman
@grayfurnaceman 8 жыл бұрын
I would check amp draw. Should be locked rotor amps as shown on the compressor plate. Yes it is dead. The rotor is locked. Most common failure. GFM
@wolfgangsnitsar4739
@wolfgangsnitsar4739 6 жыл бұрын
I've had several that the rotor was locked after sitting for a long time. On many of them, I've used a Rubber mallet and gave it a medium tap on the side a few times as I powered it up. This has unlocked the rotor but I would not count on it being a fix. It could buy you some time to repair or replace the compressor or unit.
@tommyj2859
@tommyj2859 8 жыл бұрын
Why take the wires off? If compressor is still in unit it seems difficult to check this. Can you just discount the wires from contactor and capacitor and use the wires?
@grayfurnaceman
@grayfurnaceman 8 жыл бұрын
+Tommy Jarrett So, how would you feel if there was a short or open in one of the wires, perhaps at the connection to the compressor terminals and you diagnose a shorted or failed compressor. Oops! GFM
@condor5635
@condor5635 4 жыл бұрын
grayfurnaceman excellent point exactly what happened to me the spade connector at the compressor was toast. Had to replace wire and coonector
@MuhammadKhan-di1oz
@MuhammadKhan-di1oz 9 жыл бұрын
Like very use full
@pawelb1564
@pawelb1564 11 жыл бұрын
I have another problem my compressor do not start - grounding test ok, ohm test between pins ok I did also another test I mean continuity between windings. . I was checking is there is continuity with meter probes and beep signal from meter. There is a beep only between upper and one lower pin, upper and second lower pin no beep - that means that compressor is broken electrically ?. To be more precise in tree possible combination of touching pins with meter probes there is only one beep + my connector was different from yours 1 pin in upper position + 2 pins in lower position. Please give your explanation,
@grayfurnaceman
@grayfurnaceman 11 жыл бұрын
Ignore the beep. It is only there to tell you if there is a very low resistance. Measure each resistance and record using a drawing. One should be lowest (1 to 3 ohms). The second higher added to the first should equal the 3d reading. If they read normal, the capacitor is good, the compressor is probably locked up (read dead). Hope this helps. GFM
@pawelb1564
@pawelb1564 11 жыл бұрын
grayfurnaceman I checked that once again and it was ok electrically and did not mind about continuity test. So I looked deeper and started it finally (by wire) omitting all electronic boards in my device and it worked - so the reason was not broken compressor but poor electronic - now it works fine without it - for my application it is enough. Thanks for you help, and youtube clip that make me think
@Sto20784
@Sto20784 12 жыл бұрын
I don't understand OL meaning you have no resistance? meaning the windings are good?
@MrHarbinged
@MrHarbinged 7 жыл бұрын
open line or open load, how I heard it
@mankalarao
@mankalarao 7 жыл бұрын
I checked compressor its values are C to S :4.5ohms, C toR :1.55, and S to R : 6.5ohms when supply is given compressor gets over heat but Cooling wsa not coming give me suggestion to solve the problem.
@dusangajdos4672
@dusangajdos4672 10 жыл бұрын
thanks - Y T videos , for not to give up on my frig . watched it and decided to fix my Frigidaire if I could , even though I shorted cord (for millisecond) when I plugged it in during my attempted repair . little smoke , spark, burned off tiny bit of one prong was still nothing , since I quickly puled it out , compare to puzzle - why I had no more power in frig. I am not and never be a electrician , but I can do simple things . ( I left alig. clip on run tit of comp. touching other and grounded them all by axid. or beer ) did not even trip breaker , but lost power to ice box. period . after tracing all wires , connections , plugins , looking for fuse ?, I knew there is none , cussing , make beer run , I was about to give up . but I was goanna at last salvage bulbs and get rough with ice maker to fined out why sometime wasn't dumping cubes like 9 years ago . luckily box was still plugged in , while I for no reason wiggled temp. setting knob when and suddenly lights and blower come on . I was surprised and little pissed off , that I didn't think of check its relay as a first thing . instead of tracing those wires . anyhow , 9 year old side by side box was pretty much fixed by accident with new start relay , few hammer blows on comp. and some beer . so don't give up , cut corners if needed, keep trying and improving . thanks again for this video, it helped a lot , save some dinero $ and gave bid of a satisfaction . even with pukito buzz .
@grayfurnaceman
@grayfurnaceman 11 жыл бұрын
Glad it helped. GFM
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@TOYOTER0
@TOYOTER0 11 жыл бұрын
1:00 Are the two windings the highest resistance of the three combinations?
@lupojacobo9892
@lupojacobo9892 4 жыл бұрын
The highest reading it's the run and star ends
@phillipalv8641
@phillipalv8641 7 жыл бұрын
Hi there my compressor is not starting, I check the windings from common to start I have 2.6 and from start to run I have 2.7 and from common to run I have a 0 . what's wrong here?
@grayfurnaceman
@grayfurnaceman 7 жыл бұрын
If you are doing the measurements correctly, you have a shorted compressor. Check from a winding to the compressor body. You could be shorted to ground. In any case, the wires should be removed from the compressor before testing. GFM
@jimbola77
@jimbola77 12 жыл бұрын
good vid thanx!!!
@javeedhvactechnician7760
@javeedhvactechnician7760 6 ай бұрын
kzbin.info/www/bejne/aaKUgK2ChKhroJosi=vh-JehxyvRl1Ad_y
@feenixb1o7
@feenixb1o7 12 жыл бұрын
I am indeed, It's not too small no. I'll figure it out.
@MuhammadIbrahim-nu7rj
@MuhammadIbrahim-nu7rj 9 жыл бұрын
I changed the compressor today ...but I checked the wiring according to the diagram but it was keep tripping the breaker
@grayfurnaceman
@grayfurnaceman 9 жыл бұрын
Jawad Ibrahim Does it trip the breaker immediately or does it run for a while before it kicks off? GFM
@MuhammadIbrahim-nu7rj
@MuhammadIbrahim-nu7rj 9 жыл бұрын
It was tripping immediately ...but I checked the compressor tag was in the comp was three phase but actually it was one phase compressor ...
@kdotwaoselrahc2294
@kdotwaoselrahc2294 9 жыл бұрын
it can be wrong wirring
@MuhammadIbrahim-nu7rj
@MuhammadIbrahim-nu7rj 9 жыл бұрын
It was one phase compressor instead of three that's why
@johnnygallardo76
@johnnygallardo76 11 жыл бұрын
Are you using amps?
@grayfurnaceman
@grayfurnaceman 11 жыл бұрын
No. This test is the last test you do to make sure the compressor is the problem. This one will tell you if the windings are shorted or open to each other or if they are open or shorted to ground. Hope this helps. GFM
@johnnygallardo76
@johnnygallardo76 11 жыл бұрын
So what are you using oms? What do you set your multimeter to?
@grayfurnaceman
@grayfurnaceman 11 жыл бұрын
Johnny onthespot Yes, ohms. When checking continuity of the windings, it should be set at 1X. When checking resistance to the body of the compressor, you should a megohm meter. Many of the newer digital meters are auto ranging like the one in the video, so you do not have to set it. GFM
@donmelone5945
@donmelone5945 10 жыл бұрын
grayfurnaceman
@johnvivian175
@johnvivian175 7 жыл бұрын
how about a 12v compressor, Im getting 4 all around
@grayfurnaceman
@grayfurnaceman 7 жыл бұрын
I don't know what design of compressor you have. If it is 3 phase DC, it would be the same on all windings. GFM
@yongminhuh5605
@yongminhuh5605 7 жыл бұрын
I will.
@christopherpaul2938
@christopherpaul2938 8 жыл бұрын
yes sir
@vasanthmech9142
@vasanthmech9142 10 жыл бұрын
1)I recently checked one single phase compressor, the connectivity is good (beep sound there), no ground value comes, comp is not grounded, but the resistance between the terminals is displayed as zero and the value is fluctuating in other terminals.compressor taking high amps 14.7amps recommended is 1.2 amps and gets tripped in olp. can you provide any solution for this issue,it is clear that the compressor gets jammed internally but i want to understand y the resistance value fluctuates, whether the problem is with the multimeter. 2) would you share what are all the abnormalities we can measure in a grounded compressor, will the compressor works by drawing high amps or it will not start itself.
@kdotwaoselrahc2294
@kdotwaoselrahc2294 9 жыл бұрын
its hi amphre. need to replace compressor
@feenixb1o7
@feenixb1o7 12 жыл бұрын
That's the thing, they're both the same.
@christopherpaul2938
@christopherpaul2938 8 жыл бұрын
a compressor can fail electrically and mechanically.
@grayfurnaceman
@grayfurnaceman 8 жыл бұрын
It can. This one is just about electrical failures. GFM
@raybosflorida4928
@raybosflorida4928 7 жыл бұрын
C S R,,,????
Testing if an HVACR Compressor is Shorted to Ground, Open, or Overload Tripped!
11:06
Гениальное изобретение из обычного стаканчика!
00:31
Лютая физика | Олимпиадная физика
Рет қаралды 4,8 МЛН
How to Test an Overheated Compressor (Diagnosis & Causes)
22:35
HVAC School
Рет қаралды 197 М.
How to Read Ohms on a Compressor
5:38
Lennox Learning Solutions
Рет қаралды 92 М.
Diagnosing a Grounded Compressor 3D
6:30
HVAC School
Рет қаралды 34 М.
simple way to make mini heating stove.free energy for your home!awesome
18:09
HVAC Compressor Checks - Short to Ground
5:11
John Jennings
Рет қаралды 47 М.
Refrigerator Compressor Wiring Connections are Easy As Using Your Phone
7:45
Forever Tech English
Рет қаралды 856 М.